ELECTRICAL DATA
|
|
|
|
|
|
|
| MIN WIRE | MIN | MAX | MAX | MAX FUSE** |
|
| OPER VOLTS* | COMPR | FAN |
| WIRE | LENGTH | LENGTH | ||||
UNIT SIZE | V/PH | MCA | SIZE{ | or CKT BRK | ||||||||
|
|
|
|
|
|
|
|
| SIZE{ | (ft.)} | (ft.)} | AMPS |
|
| MAX | MIN | LRA | RLA | FLA |
| 60° C | 75° C | 60° C | 75° C | |
|
|
|
| |||||||||
|
|
| 48 | 9.0 | 0.75 | 12 | 14 | 14 | 66 | 62 | 20 | |
|
|
| 58.3 | 12.8 | 0.75 | 16.8 | 14 | 14 | 47 | 45 | 25 | |
|
|
| 77 | 14.1 | 0.75 | 21.4 | 12 | 12 | 58 | 56 | 30 | |
253 | 197 | 79 | 16.7 | 1.4 | 22.2 | 12 | 12 | 56 | 54 | 35 | ||
|
|
| 109 | 19.9 | 1.2 | 26 | 10 | 10 | 77 | 73 | 40 | |
|
|
| 117 | 21.8 | 1.2 | 35.4 | 8 | 8 | 88 | 84 | 50 | |
|
|
| 134 | 26.3 | 1.2 | 34.1 | 8 | 8 | 91 | 87 | 50 |
* Permissible limits of the voltage range at which the unit will operate satisfactorily
{If wire is applied at ambient greater than 30° C (86° F), consult table
or 75° C (140 or 167° C) insulation, copper wire (solid wire for 10 AWG or smaller, stranded wire for larger than 10 AWG) is used, consult applicable tables of the NEC (ANSI/NFPA 70).
}Length shown is as measured 1 way along wire path between unit and service panel for voltage drop not to exceed 2%. **
FLA | |
LRA | |
MCA | |
RLA |
NOTE: Control circuit is
A-WEIGHTED SOUND LEVEL (DBA)
213A
UNIT SIZE | STANDARD |
| TYPICAL OCTAVE BAND SPECTRUM (without tone adjustment) |
| ||||||
RATING | 125 |
| 250 | 500 | 1000 | 2000 | 4000 |
| 8000 | |
|
|
| ||||||||
75 | 54 |
| 63 | 68.5 | 71.5 | 68 | 63.5 |
| 57 | |
75 | 54.5 |
| 64 | 69 | 69.5 | 67.5 | 64 |
| 58 | |
74 | 52 |
| 62.5 | 66.5 | 68.5 | 65 | 63.5 |
| 59 | |
76 | 60 |
| 64 | 69.5 | 70 | 68.5 | 65.5 |
| 60.5 | |
77 | 55.5 |
| 60 | 63.5 | 71.5 | 65 | 62.5 |
| 59 | |
78 | 57 |
| 64 | 68 | 74 | 67 | 63 |
| 58.5 | |
76 | 58.5 |
| 63 | 68 | 70.5 | 66.5 | 64.5 |
| 59.5 |
A-WEIGHTED SOUND LEVEL (DBA) WITH SOUND SHIELD
UNIT SIZE | STANDARD |
| TYPICAL OCTAVE BAND SPECTRUM (without tone adjustment) |
| ||||||
RATING | 125 |
| 250 | 500 | 1000 | 2000 | 4000 |
| 8000 | |
|
|
| ||||||||
74 | 53.5 |
| 63.0 | 68.0 | 70.0 | 67.5 | 63.0 |
| 56.5 | |
74 | 54.0 |
| 63.5 | 69.0 | 69.0 | 67.5 | 63.5 |
| 57.5 | |
74 | 51.5 |
| 62.0 | 66.5 | 67.5 | 64.5 | 62.0 |
| 57.5 | |
76 | 58.5 |
| 63.5 | 69.5 | 70.5 | 69.0 | 65.5 |
| 60.5 | |
75 | 55.0 |
| 60.5 | 63.5 | 69.0 | 64.5 | 61.5 |
| 56.0 | |
75 | 57.5 |
| 63.0 | 67.5 | 71.5 | 65.5 | 60.5 |
| 54.5 | |
75 | 58.5 |
| 62.5 | 67.5 | 69.0 | 64.5 | 61.5 |
| 56.0 |
CHARGING SUBCOOLING (TXV-TYPE EXPANSION DEVICE)
UNIT | REQUIRED SUBCOOLING (_F) |
10 | |
12 | |
11 | |
10 | |
11 | |
11 | |
12 |
7