ELECTRICAL DATA
|
|
|
|
|
|
|
| MIN | MIN | MAX | MAX | MAX | |
(VOLTAGE) |
|
|
|
|
|
|
| FUSE** | |||||
| OPER VOLTS* | COMPR | FAN |
| WIRE | WIRE | LENGTH | LENGTH | |||||
UNIT SIZE | V/PH |
|
|
|
|
| MCA | SIZE{ | SIZE{ | (FT)} | (FT)} | or CKT | |
|
|
|
|
|
|
|
|
|
|
| BRK | ||
| MAX | MIN | LRA | RLA | FLA |
| 60° C | 75° C | 60° C | 75° C | |||
|
|
| AMPS | ||||||||||
(N) |
|
|
| 41 | 9.0 | 0.5 | 11.70 | 14 | 14 | 166 | 158 | 20 | |
(N) |
|
|
| 54 | 11.3 | 0.8 | 14.80 | 14 | 14 | 131 | 125 | 25 | |
(N) |
|
|
| 72.5 | 14.8 | 0.8 | 19.20 | 12 | 12 | 161 | 154 | 30 | |
(N) | 208/230/1 | 253 | 187 | 88 | 17.0 | 0.9 | 22.10 | 12 | 12 | 140 | 133 | 35 | |
(N) |
|
|
| 104 | 21.2 | 0.9 | 27.40 | 10 | 10 | 181 | 172 | 40 | |
(N) |
|
|
| 137 | 21.2 | 1.2 | 27.60 | 10 | 10 | 179 | 170 | 40 | |
(N) |
|
|
| 148 | 28.9 | 1.2 | 37.30 | 8 | 8 | 207 | 197 | 60 | |
(P) |
|
|
| 63 | 10.4 | 0.75 | 13.75 | 14 | 14 | 66 | 63 | 20 | |
(P) |
|
|
| 77 | 11.3 | 0.9 | 15.03 | 12 | 12 | 96 | 92 | 25 | |
(P) | 208/230/3 | 253 | 197 | 88 | 13.4 | 0.9 | 17.65 | 12 | 12 | 82 | 78 | 25 | |
(P) |
|
|
| 91 | 13.78 | 1.2 | 18.43 | 10 | 10 | 125 | 119 | 30 | |
(P) |
|
|
| 123 | 18.7 | 1.2 | 24.58 | 8 | 10 | 146 | 89 | 35 | |
(E) |
|
|
| 39 | 5.5 | 0.5 | 7.38 | 14 | 14 | 247 | 235 | 15 | |
(E) | 460/3 | 506 | 414 | 44 | 6.4 | 0.5 | 8.50 | 14 | 14 | 214 | 203 | 15 | |
(E) | 46 | 7.1 | 0.6 | 9.41 | 14 | 14 | 193 | 184 | 15 | ||||
|
|
| |||||||||||
(E) |
|
|
| 62 | 8.6 | 0.6 | 11.35 | 14 | 14 | 160 | 152 | 15 |
* Permissible limits of the voltage range at which the unit will operate satisfactorily
{If wire is applied at ambient greater than 30° C (86° F), consult table
or 75° C (140 or 167° C) insulation, copper wire (solid wire for 10 AWG or smaller, stranded wire for larger than 10 AWG) is used, consult applicable tables of the NEC (ANSI/NFPA 70).
}Length shown is as measured 1 way along wire path between unit and service panel for voltage drop not to exceed 2%. **
FLA | |
LRA | |
MCA | |
RLA |
NOTE: Control circuit is
A-WEIGHTED SOUND POWER (DBA)
UNIT SIZE | STANDARD | TYPICAL OCTAVE BAND SPECTRUM (without tone adjustment) | |||||||
RATING | 125 | 250 | 500 | 1000 | 2000 | 4000 | 8000 | ||
| |||||||||
75 | 52 | 59.5 | 64.5 | 71 | 67 | 61.5 | 54.5 | ||
76 | 52.5 | 63.5 | 69.5 | 72 | 67.5 | 64.5 | 59.5 | ||
76 | 52 | 64 | 70 | 71 | 68 | 66.5 | 65 | ||
76 | 53 | 69 | 66.5 | 69.5 | 66.5 | 63.5 | 62 | ||
76 | 57 | 65 | 68 | 72.5 | 67.5 | 64 | 59 | ||
76 | 57.5 | 65 | 68 | 70.5 | 69 | 64 | 60.5 | ||
77 | 61 | 62.5 | 70 | 72.5 | 70 | 67 | 60 |
A-WEIGHTED SOUND POWER (DBA) WITH SOUND HOOD
UNIT SIZE | STANDARD | TYPICAL OCTAVE BAND SPECTRUM (without tone adjustment) | |||||||
RATING | 125 | 250 | 500 | 1000 | 2000 | 4000 | 8000 | ||
| |||||||||
74 | 52.0 | 59.5 | 64.0 | 68.0 | 64.0 | 60.0 | 52.5 | ||
75 | 53.5 | 63.0 | 69.0 | 70.5 | 66.5 | 64.0 | 58.5 | ||
75 | 53.0 | 64.5 | 69.5 | 70.5 | 67.5 | 64.5 | 60.5 | ||
75 | 54.0 | 68.5 | 65.5 | 68.0 | 65.0 | 62.0 | 57.5 | ||
76 | 58.0 | 64.5 | 67.0 | 71.0 | 65.5 | 61.0 | 54.5 | ||
75 | 58.0 | 64.0 | 68.0 | 69.0 | 65.5 | 60.5 | 55.5 | ||
75 | 59.5 | 61.5 | 67.5 | 70.0 | 68.0 | 64.0 | 57.5 |
CHARGING SUBCOOLING (TXV-TYPE EXPANSION DEVICE)
UNIT | REQUIRED SUBCOOLING (_F) |
11 | |
11 | |
9 | |
11 | |
13 | |
13 | |
11 |
213R
7