PHYSICAL DATA

UNIT SIZE---SERIES

018---C

024---B

030---C

30---B

 

36---C

42---B

48---B

60---B

(Voltage)

(N)

(N)

(N)

(P)

 

(N, P, E)

(N, P, E)

(N, P, E)

(N, P, E)

 

 

 

 

 

 

 

 

 

 

Operating Weight lb (kg)

174

183

206

206

 

203

263

283

299

(78.9)

(83.0)

(93.4)

(93.4)

 

(92.1)

(119.32)

(128.4)

(135.6)

 

 

Shipping Weight lb (kg)

201

210

235

235

 

241

295

313

331

(91.2)

(95.3)

(106.6)

(106.6)

 

(109.3)

(133.8)

(142.0)

(150.1)

 

 

Compressor Type

 

 

 

 

Scroll

 

 

 

Refrigerant

 

 

 

Puron￿ (R---410A)

 

 

 

Control

 

 

 

TXV (Puron Hard Shutoff)

 

 

 

Charge lb (kg)

6.4 (2.9)

5.5 (2.5)

7.5 (3.4)

8.2 (3.7)

 

7.2 (3.2)

8.1 (3.7)

11.6 (5.3)

12.4 (5.6)

Outdoor Heating Piston #

42

46

55

55

 

57

61

61

76

 

 

 

 

 

 

 

 

 

Cond Fan

 

 

 

Propeller Type, Direct Drive

 

 

 

Air Discharge

 

 

 

 

Vertical

 

 

 

Air Qty (CFM)

2614

2614

2614

2614

 

3472

3810

4046

4046

Motor HP

1/10

1/10

1/10

1/10

 

1/8

1/5

1/4

1/4

Motor RPM

800

800

800

800

 

800

800

800

800

Cond Coil

 

 

 

 

 

 

 

 

 

Face Area (Sq ft)

15.09

15.09

21.56

25.87

 

20.12

25.15

20.12

22.63

Fins per In.

20

20

20

20

 

20

20

20

20

Rows

1

1

1

1

 

1

1

2

2

Circuits

5

5

5

6

 

6

6

8

8

Valve Connect (In.) ID

 

 

 

 

 

 

 

 

 

Vapor

5/8

5/8

3/4

3/4

 

3/4

7/8

7/8

7/8

Liquid

 

 

 

 

3/8

 

 

 

Refrigerant Tubes (In.) OD

 

 

 

 

 

 

 

 

 

Rated Vapor*

5/8

5/8

3/4

3/4

 

3/4

7/8

7/8

1---1/8

Liquid

 

 

 

 

3/8

 

 

 

*Units are rated with 25 ft (7.6 m) of lineset length. See Vapor Line Sizing and Cooling Capacity Loss table when using other sizes and lengths of lineset. Note: See unit Installation Instruction for proper installation.

VAPOR LINE SIZING AND COOLING CAPACITY LOSS

LONG LINE APPLICATION: An application is considered

vertical separation is 200 ft. (60.96 m) when outdoor unit is

”Long line” when the total equivalent tubing length exceeds 80

above indoor unit, and up to 80 ft. (24.38 m) when the outdoor

ft. (24.38 m) or when there is more than 20 ft. (6.09 m) vertical

unit is below the indoor unit. Refer to Accessory Usage Guideline

separation between indoor and outdoor units. These applications

below for required accessories. See Longline Application

require additional accessories and system modifications for

Guideline for required piping and system modifications. Also,

reliable system operation. The maximum allowable total

refer to the table below for vapor tube diameters based on the

equivalent length is

up to 250

ft. (76.2 m).

The

maximum

total length to minimize the cooling capacity loss.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Cooling Capacity Loss (%)

 

 

 

 

 

Maximum

Vapor Line

 

 

 

 

 

Total Equivalent Line Length ft. (m)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Unit Nominal Size

 

Liquid Line

 

Standard

 

Long Line Application Requires Accessories

 

 

Diameters

 

 

 

(Btuh)

 

Diameters

 

Application

 

 

 

(In.) OD

 

 

 

 

 

 

 

 

 

 

(In.) OD

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

26---50

 

51---80

81---100

101---125

126---150

151---175

176---200

201---225

226---250

 

 

 

 

 

 

 

 

 

 

 

(7.9---15.2)

(15.5---24.4)

(24.7---30.5)

(30.8---38.1)

(38.4---45.7)

(46.0---50.3)

(53.6---60.0)

(61.3---68.6)

(68.9---76.2)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

18,000

 

 

1/2

 

1

 

2

3

4

6

7

8

9

10

1---Stage Puron HP

 

 

5/8

 

0

 

0

1

1

1

2

2

3

3

24,000

 

 

5/8

 

0

 

1

1

2

3

3

4

4

5

1---Stage Puron HP

 

 

3/4

 

0

 

0

0

0

1

1

1

1

1

30,000

 

 

5/8

 

1

 

2

3

3

4

5

6

7

8

 

 

3/4

 

0

 

0

1

1

1

2

2

2

3

1---Stage Puron HP

 

 

 

 

 

 

7/8

 

0

 

0

0

0

1

1

1

1

1

 

 

 

 

 

36,000

 

 

5/8

 

1

 

2

4

5

6

7

9

10

11

 

3/8

3/4

 

0

 

0

1

1

2

2

3

3

4

1---Stage Puron HP

 

 

 

 

 

7/8

 

0

 

0

0

0

1

1

1

1

2

 

 

 

 

 

42,000

 

 

3/4

 

0

 

1

2

2

3

4

4

5

6

1---Stage Puron HP

 

 

7/8

 

0

 

0

1

1

1

2

2

2

3

48,000

 

 

3/4

 

0

 

1

2

3

4

5

5

6

7

1---Stage Puron HP

 

 

7/8

 

0

 

0

1

1

2

2

2

3

3

60,000

 

 

3/4

 

1

 

2

4

5

6

7

9

10

11

 

 

7/8

 

0

 

1

2

2

3

4

4

5

5

1---Stage Puron HP

 

 

 

 

 

 

1---1/8

 

0

 

0

0

1

1

1

1

1

1

 

 

 

 

 

Applications in this area

are long line.

Accessories are

required as shown

recommended

on Long Line

Application

Guidelines

 

 

 

Applications in this area may have height restrictions that limit allowable total equivalent length, when outdoor unit is below indoor unit See Long Line Applica- tion Guidelines

223A

3

Page 3
Image 3
Bryant 223A manual Physical Data, Vapor Line Total Equivalent Line Length ft. m, Liquid Line, Btuh

223A specifications

The Bryant 223A is a cutting-edge air conditioning unit that epitomizes modern cooling technology. Designed for both residential and commercial applications, this model stands out for its efficiency, reliability, and user-friendly features. One of the most significant aspects of the Bryant 223A is its energy efficiency, boasting a Seasonal Energy Efficiency Ratio (SEER) rating of up to 16. This high rating means lower energy consumption, translating into reduced utility bills for homeowners and businesses alike.

One prominent feature of the Bryant 223A is its environmentally friendly design. It utilizes Puron refrigerant, which has zero ozone-depleting potential, making it a responsible choice for those looking to minimize their environmental footprint. In addition to being eco-conscious, the unit is equipped with a variable-speed compressor, allowing for improved humidity control and enhanced comfort levels. This technology enables the system to adjust its cooling output based on the current indoor conditions, resulting in more consistent temperatures and quieter operation.

Another noteworthy characteristic of the Bryant 223A is its robust construction. The cabinet is designed with galvanized steel, offering durability and resistance to corrosion. This resilience ensures that the unit can withstand the rigors of various weather conditions, contributing to its longevity. Moreover, the unit features an innovative design that minimizes noise levels, ensuring that it operates quietly without disturbing daily activities.

Ease of installation is yet another advantage of the Bryant 223A. The unit comes with a compact design, allowing for straightforward placement in a variety of settings. Additionally, its integration with modern smart thermostats provides users with enhanced control over their indoor climate. This feature enables homeowners to monitor and adjust their air conditioning settings remotely, adding convenience and efficiency to their energy management.

The Bryant 223A also incorporates advanced filtration systems, which significantly improve indoor air quality. Enhanced filters capture a wide range of airborne particles, including allergens, dust, and pollutants, making it an excellent choice for households with allergy sufferers. Overall, the Bryant 223A combines state-of-the-art technology, eco-friendly operation, and user-centric features, making it a leading choice in air conditioning solutions for a variety of environments.