TABLE 4ÐELECTRICAL DATA
UNIT | VOLTSÐ | OPERATING | MAX | UNIT | MIN | MAX WIRE | MAX FUSE | ||
HERTZÐ | VOLTAGE RANGE | UNIT | WIRE | LENGTH | OR CKT BKR | ||||
SIZE | AMPACITY² | ||||||||
PHASE | Max* | Min* | AMPS | GAGE | (FT)³ | AMPS** | |||
|
| ||||||||
024040 | 115Ð60Ð1 | 127 | 104 | 6.1 | 8.4 | 14 | 44 | 15 | |
036040 | 115Ð60Ð1 | 127 | 104 | 7.3 | 10.0 | 14 | 37 | 15 | |
024060 | 115Ð60Ð1 | 127 | 104 | 6.1 | 8.4 | 14 | 44 | 15 | |
036060 | 115Ð60Ð1 | 127 | 104 | 7.1 | 9.8 | 14 | 38 | 15 | |
048060 | 115Ð60Ð1 | 127 | 104 | 9.5 | 12.8 | 14 | 29 | 15 | |
036080 | 115Ð60Ð1 | 127 | 104 | 7.6 | 10.4 | 14 | 36 | 15 | |
048080 | 115Ð60Ð1 | 127 | 104 | 10.0 | 13.4 | 14 | 28 | 15 | |
060080 | 115Ð60Ð1 | 127 | 104 | 14.1 | 18.4 | 12 | 31 | 20 | |
048100 | 115Ð60Ð1 | 127 | 104 | 10.2 | 13.5 | 14 | 27 | 15 | |
060100 | 115Ð60Ð1 | 127 | 104 | 14.8 | 19.3 | 12 | 30 | 20 | |
060120 | 115Ð60Ð1 | 127 | 104 | 14.6 | 19.1 | 12 | 30 | 20 | |
→060140 | 115Ð60Ð1 | 127 | 104 | 14.3 | 18.8 | 12 | 30 | 20 | |
|
|
|
|
|
|
|
|
|
* Permissible limits of voltage range at which unit will operate satisfactorily.
²Unit ampacity = 125 percent of largest operating component's full load amps plus 100 percent of all other potential operating components' (EAC, humidifier, etc.) full load amps.
³Length shown is as measured 1 way along wire path between unit and service panel for maximum 2 percent voltage drop. **
III.ACCESSORIES
1.Electronic Air Cleaner (EAC)
Two
TEST/TWIN
2. Humidifier (HUM)
A
NOTE: A
G | ||
TERMINALS | ||
| ||
R |
| |
Y |
| |
W | HUMIDIFIER TERMINAL | |
COM 24V | ||
| ||
HUM | LED OPERATION & | |
| ||
| DIAGNOSTIC LIGHT |
| HARNESS CONNECTOR | |
| ||
COOL | ||
BLOWER SPEED | ||
HEAT | ||
| SELECTION TERMINALS | |
| ||
| ||
| ||
| TERMINALS | |
POWER SUPPLY | ||
| ||
| CONNECTION | |
HOT SURFACE | INDUCER MOTOR | |
IGNITOR CONNECTOR | CONNECTOR |
A95086
Fig. 25ÐControl Center
Ð20Ð