Bryant 556A warranty Tested Combination Ratings, Recommended Tube Diameters, Metering Device

Models: 556A

1 8
Download 8 pages 52.27 Kb
Page 3
Image 3

TESTED COMBINATION RATINGS*

 

 

 

 

 

SEER

 

 

 

INDOOR

TOTAL

Factory-

 

 

Bryant Gas

 

 

UNIT SIZE-SERIES

CAPACITY

Supplied

Standard

 

Furnace or

Accessory

EER

MODEL

 

 

BTUH

Enhance-

Rating

 

Accessory

TXV³

 

 

 

 

 

 

 

 

ment

 

 

TDR²

 

 

024-A

CJ5A/CK5A/CK5BA036

26,600

TXV

Ð

 

14.00

Ð

12.00

030-A

CJ5A/CK5A/CK5BA042

30,500

TXV

Ð

 

14.10

Ð

12.00

036-A

CJ5A/CK5A/CK5BA048

36,500

TXV

Ð

 

14.10

Ð

11.90

042-A

CJ5A/CK5A/CK5BA060

42,000

TXV

Ð

 

14.00

Ð

11.90

 

 

 

 

 

 

 

 

 

* Outdoor section/indoor section combination tested in accordance with DOE test procedure for electric air conditioners.

²In most cases, only 1 method should be used to achieve TDR function. Using more than 1 method in a system may cause degradation in performance. Use either the accessory Time-Delay Relay KAATD0101TDR or a furnace equipped with TDR. All Bryant furnaces are equipped with TDR except for the 394HAD.

³Based on computer simulation. TXV must be R-410A compatible and hard shutoff type. EERÐEnergy Efficiency Ratio

SEERÐSeasonal Energy Efficiency Ratio TDRÐTime-Delay Relay TXVÐThermostatic Expansion Valve

NOTES: 1. Ratings are net values reflecting the effects of circulating fan heat. Supplemental electric heat is not included.

2.Determine actual CFM values obtainable for your system by referring to fan performance data in fan coil or furnace coil literature.

3.Do not apply with capillary tube coils as performance and reliability are significantly affected.

RECOMMENDED TUBE DIAMETERS

UNIT

LIQUID TUBE DIAMETER (IN.)

VAPOR TUBE DIAMETER (IN.)

0 to 50 Ft

 

0 to 50 Ft

Long-Line Applications*

SIZE

Long-Line Applications*

Tube Length

Tube Length

(Maximum Diameter)

 

 

 

 

 

 

 

024

3/8

3/8

5/8

3/4

030

3/8

3/8

3/4

7/8

036

3/8

3/8

3/4

7/8

042

3/8

3/8

7/8

1-1/8

 

 

 

 

 

* Tube diameters are for lengths up to 50 ft. For tubing lengths greater than 50 ft, consult the Application Guideline and Service Manual for Residential Split-System Air Conditioners and Heat Pumps Using R-410A Refrigerant.

NOTE: Refrigerant tubes and indoor coils must be evacuated to 500 microns to minimize contamination and moisture in the system.

METERING DEVICE

UNIT SIZE

INDOOR TXV*

REQUIRED SUBCOOLING

(°F)

 

 

024-A

KSATX0201HSZ

TBD

030-A

KSATX0201HSZ

TBD

036-A

KSATX0301HSZ

TBD

042-A

KSATX0301HSZ

TBD

 

 

 

*TXV must be installed when indoor coil is not equipped with an R-410A approved TXV. TXV listed is for any approved coil combination. All TXVs are R-410A specific hard shutoff.

TBDÐTo Be Determined

 

SOUND RATING (DBA)

UNIT SIZE-SERIES

 

SOUND RATING

024-A

 

70

030-A

 

72

036-A

 

74

042-A

 

74

 

 

 

Ð3Ð

Page 3
Image 3
Bryant 556A warranty Tested Combination Ratings, Recommended Tube Diameters, Metering Device, Sound Rating Dba