AIR CONDITIONER SYSTEM DESIGN

HUMIDIFIER

FURNACE COIL

VENT PERFECT

HOMEPERFECT PLUS

CONTROL CENTER

FURNACE

AIR CLEANER

A97092

SYSTEM DESIGN

1.Intended for outdoor installation with free air inlet and outlet. Outdoor fan external static pressure available is less than 0.01-in. wc.

2.Minimum outdoor operating air temperature without low-ambient operation accessory is 55°F (12.8°C).

3.Maximum outdoor operating air temperature is 125°F (51.7°C)

4.For reliable operation, unit should be level in all horizontal planes.

5.Maximum elevation of indoor coil above or below base of outdoor unit is: indoor coil above = 30 ft; indoor coil below = 30 ft. (See items 6 and 7 following.)

6.For interconnecting tubing lengths greater than 50 ft, consult the Residential Split-System Application Guideline and Service Manual for Air Conditioners and Heat Pumps using R-410A Refrigerant.

7.If ANY refrigerant tubing is buried, provide a minimum 6-in. vertical rise to the valve connections at the unit. Refrigerant tubing lengths up to 36 in. may be buried without further considerations. For buried refrigerant tubing lengths greater than 36 in., consult the Residential Split-System Buried-Line Application Guideline.

8.Use only copper wire for electric connection at unit. Aluminum and clad aluminum are not acceptable for the type of connector provided.

9.Mixmatches of indoor coil capacity of more than 2 sizes larger than outdoor unit capacity may result in inadequate indoor comfort.

10.Do not apply capillary tube indoor coils to these units.

11.Factory-supplied filter drier must be installed.