Bryant 556A warranty Accessory Usage Guideline

Models: 556A

1 8
Download 8 pages 52.27 Kb
Page 5
Image 5

ACCESSORY USAGE GUIDELINE

 

REQUIRED FOR

REQUIRED FOR

REQUIRED FOR

REQUIRED FOR

ACCESSORY

LOW-AMBIENT

LONG-LINE

BURIED LINE

SEA COAST

APPLICATIONS

APPLICATIONS*

APPLICATIONS²

APPLICATIONS

 

 

(BELOW 55°F)

(OVER 50 FT)

(OVER 3 FT)

(WITHIN 2 MILES)

Crankcase Heater

Yes

Yes

Yes

No

Evaporator Freeze Thermostat

Yes

No

No

No

Winter Start Control

Yes³

No

No

No

Accumulator

No

No

Yes

No

Compressor Start Assist

Yes

Yes

Yes

No

Capacitor and Relay

 

 

 

 

Low-Ambient Controller,

 

 

 

 

MotorMaster® Control,

Yes

No

No

No

or

 

 

 

 

Low-Ambient Pressure Switch

 

 

 

 

Wind Baffle

See Low-Ambient Instructions

No

No

No

Coastal Filter

No

No

No

Yes

Support Feet

Recommended

No

No

Recommended

Liquid-Line Solenoid Valve

 

See Long-Line

 

 

or

No

Application

Yes

No

Hard Shutoff TXV

 

Guideline

 

 

Ball Bearing Fan Motor

Yes**

No

No

No

 

 

 

 

 

*For tubing line sets between 50 and 175 ft, refer to the Application Guideline and Service Manual for Residential Split-System Air Conditioners and Heat Pumps using R-410A Refrigerant.

²For buried line applications, refer to Residential Split System Buried-Line Application Guideline. ³ Only when low-pressure switch is used.

** Required for Low-Ambient Controller (full modulation feature) and MotorMaster® Control only.

Ð5Ð

Page 5
Image 5
Bryant 556A warranty Accessory Usage Guideline