SPECIFICATIONS
UNIT SIZE |
|
|
|
|
| |
Operating Weight (Lb) | 137 | 143 |
| 161 | 169 | |
ELECTRICAL |
|
|
|
|
| |
Unit |
|
| ||||
Operating Voltage Range* |
|
|
| |||
Compressor— Rated Load Amps | 8.6 | 10.9 |
| 13.7 | 15.0 | |
| Locked Rotor Amps | 49.0 | 56.0 |
| 75.0 | 82.0 |
Condenser Fan | 0.5 | 0.5 |
| 0.8 | 1.4 | |
Min Unit Ampacity for Wire Sizing | 11.3 | 14.1 |
| 17.9 | 20.2 | |
Min Wire Size (75°C Copper) AWG† | 14 | 14 |
| 14 | 12 | |
Min Wire Size (60°C Copper) AWG† | 14 | 14 |
| 14 | 12 | |
Max Wire Length (Ft) (75°C Copper)‡ | 62 | 50 |
| 42 | 57 | |
Max Wire Length (Ft) (60°C Copper)‡ | 66 | 53 |
| 44 | 60 | |
Max Branch Circuit Fuse Size** | 15 | 20 |
| 25 | 30 | |
COMPRESSOR and REFRIGERANT |
|
|
|
|
| |
| Copeland Reciprocating |
| ||||
Temperature and Current Protection |
| Internal Line Break |
| |||
| ||||||
CONDENSER COIL and FAN |
|
|
|
|
| |
Coil Face (Sq Ft) | 7.2 | 7.2 |
| 8.8 | 10.9 | |
Fins per |
| |||||
Fan | 1/12 PSC and 1100 |
| 1/10 PSC and 1100 | 1/4 PSC and 1100 | ||
|
| |||||
Condenser Airflow (CFM) | 1900 | 1900 |
| 2100 | 2600 | |
OPTIONAL EQUIPMENT |
|
|
|
|
| |
Support Feet |
| KSASF0101AAA |
| |||
Coastal Filter |
| KAACF0701SML |
| |||
Time Delay Relay |
| KAATD0601TDR |
| |||
Cycle Protector |
| KSACY0101AAA |
| |||
Crankcase Heater |
| KAACH1001AAA |
| |||
Start |
| KSAHS1001AAA |
| |||
Start |
| KAACS0201PTC |
| |||
Sound Hood | KSASH1101COP |
| KSASH1201COP | |||
TXV Kit (RPB) | KAATX0201RPB | KAATX0301RPB |
| KAATX0401RPB | KAATX0501RPB | |
TXV Kits (Hard Shutoff) |
| KSATX0601HSO |
| |||
| KAALP0101LPS |
| ||||
| KSAHI0101HPS |
| ||||
Filter Drier |
|
| ||||
Evaporator Freeze Thermostat** |
| KAAFT0101AAA |
| |||
| KAALS0101LLS |
| ||||
Winter Start Control** |
| KAAWS0101AAA |
| |||
| KSALA0201R22 |
| ||||
MotorMaster® Control†† |
| 32LT660004 (RCD) |
| |||
Ball Bearing Fan Motor |
| HC34GE232 (RCD) |
| |||
Thermostat, Auto Changeover, |
|
|
|
|
| |
|
|
|
|
| ||
|
| |||||
Thermostat, Auto Changeover, |
|
|
|
|
| |
|
|
|
|
| ||
|
| |||||
Builder’s Thermostat, Manual |
|
|
|
|
| |
Changeover, |
|
|
|
|
| |
°F/°C, |
|
| ||||
Thermidistat™ |
|
|
|
|
| |
|
|
|
|
| ||
Humidity Control |
|
| ||||
Outdoor Air Temperature Sensor |
|
| ||||
Backplate for |
|
|
|
|
| |
Thermostat |
| TSTATXXNBP01 |
| |||
Backplate for Programmable Thermostat |
| TSTATXXPBP01 |
| |||
Backplate for Builder’s Thermostat |
| TSTATXXBBP01 |
| |||
Thermostat Conversion Kit (4 to 5 wire) |
|
|
|
|
| |
— 10 Pack |
| TSTATXXCNV10 |
|
See notes on page 5.