SPECIFICATIONS Continued
UNIT SIZE |
|
|
|
| |
Operating Weight (Lb) | 206 | 199 |
| 217 | |
ELECTRICAL |
|
|
|
| |
Unit |
|
|
| ||
Operating Voltage Range* |
|
|
| ||
Compressor— Rated Load Amps | 19.0 | 24.4 |
| 28.8 | |
| Locked Rotor Amps | 105.0 | 140.0 |
| 165.0 |
Condenser Fan | 1.4 | 1.4 |
| 1.4 | |
Min Unit Ampacity for Wire Sizing | 25.2 | 31.9 |
| 37.4 | |
Min Wire Size (75°C Copper) AWG† | 10 | 10 |
| 8 | |
Min Wire Size (60°C Copper) AWG† | 10 | 8 |
| 8 | |
Max Wire Length (Ft) (75°C Copper)‡ | 73 | 59 |
| 78 | |
Max Wire Length (Ft) (60°C Copper)‡ | 77 | 97 |
| 82 | |
Max Branch Circuit Fuse Size** | 40 | 50 |
| 60 | |
COMPRESSOR and REFRIGERANT |
|
|
|
| |
Copeland Reciprocating | Millennium Scroll |
| Millennium Scroll | ||
Temperature and Current Protection | Internal Line Break | Internal Line Break and Dome Thermostat | |||
| |||||
CONDENSER COIL and FAN |
|
|
|
| |
Coil Face (Sq Ft) | 12.2 | 15.2 |
| 18.3 | |
Fins per |
| ||||
Fan |
| 1/4 PSC and 1100 |
|
| |
|
|
| |||
Condenser Airflow (CFM) |
| 3000 |
|
| |
OPTIONAL EQUIPMENT |
|
|
|
| |
Support Feet |
| KSASF0101AAA |
|
| |
Coastal Filter |
| KAACF0801MED |
|
| |
Time Delay Relay |
| KAATD0101TDR |
|
| |
Cycle Protector |
| KSACY0101AAA |
|
| |
Crankcase Heater | Standard |
| KAACH1201AAA | ||
Start | KSAHS1301AAA |
| KSAHS1601AAA | ||
Start |
| KAACS0201PTC |
|
| |
Sound Hood | KSASH1201COP |
| KSASH2001CYL | ||
TXV Kit (RPB) | KAATX0501RPB | KAATX0601RPB |
| KAATX0701RPB | |
TXV Kits (Hard Shutoff) | KSATX0601HSO |
| KSATX0701HSO | ||
| KAALP0101LPS |
|
| ||
| KSAHI0101HPS |
|
| ||
Filter Drier |
|
|
| ||
Evaporator Freeze Thermostat** |
| KAAFT0101AAA |
|
| |
| KAALS0101LLS |
|
| ||
Winter Start Control** |
| KAAWS0101AAA |
|
| |
| KSALA0201R22 |
|
| ||
MotorMaster® Control†† |
| 32LT660004 (RCD) |
|
| |
Ball Bearing Fan Motor |
| HC40GE232 (RCD) |
|
| |
Thermostat, Auto Changeover, |
|
|
|
| |
|
|
|
| ||
|
|
| |||
Thermostat, Auto Changeover, |
|
|
|
| |
|
|
|
| ||
|
|
| |||
Builder’s Thermostat, Manual |
|
|
|
| |
Changeover, |
|
|
|
| |
°F/°C, |
|
|
| ||
Thermidistat™ |
|
|
|
| |
|
|
|
| ||
Humidity Control |
|
|
| ||
Outdoor Air Temperature Sensor |
|
|
| ||
Backplate for |
|
|
|
| |
Thermostat |
| TSTATXXNBP01 |
|
| |
Backplate for Programmable Thermostat |
| TSTATXXPBP01 |
|
| |
Backplate for Builder’s Thermostat |
| TSTATXXBBP01 |
|
| |
Thermostat Conversion Kit (4 to 5 wire) |
|
|
|
| |
— 10 Pack |
| TSTATXXCNV10 |
|
|
*Permissible limits of the voltage range at which the unit will operate satisfactorily. Operation outside these limits may result in unit failure.
† If wire is applied at ambient greater than 30°C (86°F), consult Table
The ampacity of
‡ Length shown is as measured 1 way along wire path between unit and service panel for a voltage drop not to exceed 2%.
**Fan motor with ball bearings required. See
NOTE: Copper wire must be used from service disconnect to unit. All motors/compressors contain internal overload protection.