HEAT PUMP HEATING PERFORMANCE Continued

 

INDOOR

 

 

 

 

 

 

OUTDOOR COIL ENTERING AIR TEMPERATURES °F

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AIR

 

–3

 

 

7

 

 

17

 

 

27

 

 

37

 

 

47

 

 

57

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Capacity

Total

Capacity

Total

Capacity

Total

Capacity

Total

Capacity

Total

Capacity

Total

Capacity

Total

 

 

 

 

(MBtuh)

Pwr

(MBtuh)

Pwr

(MBtuh)

Pwr

(MBtuh)

Pwr

(MBtuh)

Pwr

(MBtuh)

Pwr

(MBtuh)

Pwr

 

 

EDB

CFM

Total

Int*

Kw†

Total

Int*

Kw†

Total

Int*

Kw†

Total

Int*

Kw†

Total

Int*

Kw†

Total

Int*

Kw†

Total

Int*

Kw†

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

697C036-B Outdoor Section With FC4BN(F,B)042 Indoor Section Continued

 

 

 

 

 

 

 

1100

16.0

14.7

2.43

19.3

17.7

2.53

22.8

20.8

2.64

26.7

23.7

2.74

31.2

28.4

2.87

36.1

36.1

3.03

41.8

41.8

3.23

 

 

65

1200

16.2

14.9

2.46

19.4

17.9

2.55

23.0

21.0

2.65

26.9

23.9

2.75

31.4

28.6

2.87

36.4

36.4

3.03

42.1

42.1

3.22

 

 

 

1300

16.4

15.1

2.48

19.7

18.1

2.58

23.2

21.1

2.66

27.1

24.1

2.76

31.6

28.7

2.88

36.6

36.6

3.03

42.4

42.4

3.22

 

 

 

1100

15.7

14.5

2.52

19.1

17.5

2.64

22.6

20.6

2.75

26.5

23.5

2.87

30.9

28.1

3.00

35.7

35.7

3.17

41.3

41.3

3.37

 

 

70

1200

15.9

14.6

2.55

19.2

17.7

2.66

22.8

20.8

2.76

26.7

23.7

2.87

31.1

28.3

3.00

36.0

36.0

3.16

41.6

41.6

3.36

 

 

 

1300

16.1

14.8

2.57

19.4

17.8

2.68

23.0

20.9

2.78

26.9

23.9

2.88

31.3

28.5

3.01

36.2

36.2

3.16

41.9

41.9

3.35

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1100

15.4

14.1

2.62

18.9

17.3

2.74

22.4

20.4

2.87

26.2

23.3

2.99

30.6

27.8

3.14

35.4

35.4

3.31

40.9

40.9

3.52

 

 

75

1200

15.6

14.3

2.64

19.0

17.5

2.76

22.6

20.6

2.88

26.4

23.5

3.00

30.8

28.0

3.14

35.6

35.6

3.30

41.2

41.2

3.50

 

 

 

1300

15.7

14.5

2.67

19.2

17.6

2.78

22.7

20.7

2.89

26.6

23.6

3.01

31.0

28.2

3.14

35.9

35.9

3.30

41.5

41.5

3.50

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Multipliers for Determining the Performance With Other Indoor Sections

 

Indoor

 

 

Heating

Indoor

 

 

Heating

 

 

 

 

 

 

 

 

 

 

 

 

Section

Size

Capacity

 

Power

Section

Size

Capacity

 

Power

 

 

COILS + 355MAV060100 VARIABLE-SPEED FURNACE

COILS + 355MAV060120 VARIABLE-SPEED FURNACE

 

 

CC5A/CD5A/CD5BA

042

0.99

 

0.97

CJ5A/CK5A/CK5BA

042

0.99

 

0.95

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CD3(A,B)A

042

0.99

 

0.97

CJ5A/CK5A/CK5BW

036

0.99

 

0.95

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CJ5A/CK5A/CK5BA

042

0.99

 

0.95

CK3BA

036

0.99

 

0.95

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CJ5A/CK5A/CK5BW

036

1.00

 

0.96

 

042

0.99

 

0.95

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CK3BA

036

1.00

 

0.96

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

042

0.99

 

0.95

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

See notes on page 34.

—31—

Page 31
Image 31
Bryant 697C warranty Heat Pump Heating Performance