SPECIFICATIONS Continued
| UNIT  | 
 | ||
| 
 | |||
| Operating Weight (Lb) | 265 | 
 | 327 | 
| ELECTRICAL | 
 | 
 | 
 | 
| Unit  | 
 | ||
| Operating Voltage Range | 
 | ||
| Unit Ampacity for Wire Sizing | 34.0 | 
 | 45.0 | 
| Min Wire Size (60°C/75°C Copper) (AWG)* | 8/10 | 
 | 6/8 | 
| Maximum Length (60°C/75°C) (Ft)** | 91/56 | 
 | 116/66 | 
| Max. Branch Circuit Fuse Size (Amps)‡ | 50 | 
 | 60 | 
| Compressor Rated Load Amps | 26.5 | 
 | 34.9 | 
| Locked Rotor Amps | 129.0 | 
 | 169.0 | 
| Fan Motor HP and RPM | 1/8 and 820 | 
 | 1/5 and 820 | 
| Full Load Amps | 1.0 | 
 | 1.4 | 
| COMPRESSOR AND REFRIGERANT | 
 | 
 | 
 | 
| Compressor | 
 | Scroll | |
| 
 | |||
| OUTDOOR COIL AND FAN | 
 | 
 | 
 | 
| Coil Face Area (Sq Ft) | 18.18 | 
 | 24.89 | 
| Rated Airflow (CFM) | 2900 | 
 | 3600 | 
| OPTIONAL EQUIPMENT | 
 | 
 | 
 | 
| Support  | 
 | KSASF0101AAA | |
| Snow  | KHASS0206MPK | 
 | KHASS0306MPK | 
| 
 | KAATD0101TDR | ||
| Interface Control‡‡‡ | 
 | KHAIC0101AAA | |
| Service Alarm | 
 | KHASA0101AAA†† | |
| Outdoor Thermostat | 
 | KHAOT0301FST | |
| Secondary Outdoor Thermostat | 
 | KHAOT0201SEC | |
| Cycle Protector | 
 | Standard | |
| Crankcase Heater | 
 | Standard | |
| Start  | 
 | KAACS0201PTC | |
| Start Capacitor and Relay | 
 | KSAHS1601AAA | |
| Sound Hood | 
 | Standard | |
| KHATX1301HSO | 
 | KHATX1401HSO | |
| 
 | 
 | N/A | |
| 
 | Standard | ||
| 
 | Standard | ||
| Evaporator Freeze Thermostat | 
 | KAAFT0101AAA‡‡ | |
| Isolation Relay | 
 | KHAIR0101AAA‡‡ | |
| Liquid Solenoid Valve (LSV) | 
 | KHALS0101LLS | |
| Filter  | 
 | ||
| 
 | |||
| MotorMaster® Control | 
 | 32LT660004*** | |
| Ball Bearing Fan Motor | 
 | HC38GE230 (RCD) | |
| Thermostat, Auto Changeover, | 
 | 
 | 
 | 
| 
 | 
 | 
 | |
| 
 | |||
| Thermostat, Auto Changeover, | 
 | 
 | 
 | 
| 
 | 
 | 
 | |
| 
 | 
 | ||
| Thermostat, Manual Changeover, | 
 | 
 | 
 | 
| 
 | 
 | 
 | |
| 
 | HH07AT214 | ||
| Thermostat, Auto Changeover, | 
 | 
 | 
 | 
| 
 | 
 | 
 | |
| Dual Fuel Thermostat. Must be used with | 
 | 
 | 
 | 
| Outdoor Sensor (TSTATBBSEN01) | 
 | ||
| Outdoor Sensor | 
 | TSTATBBSEN01 | |
*If wire is applied at ambient greater than 30°C (86°F), consult Table 
(ANSI/NFPA 70) Article 
†The factory refrigerant charge is for 15 ft of interconnecting tubing. For tubing lengths other than 15 ft, see 
‡ 
**Length shown is as measured 1 way along the wire path between the unit and the service panel for voltage drop not to exceed 2%.
††For indicator light function, thermostat specified must be used and wired according to efficiency service alarm Installation Instructions. ‡‡ Used with 
***Fan motor with ball bearings required.
†††
‡‡‡ Outdoor thermostat required. 