ACCESSORY USAGE GUIDELINE
| REQUIRED FOR | REQUIRED FOR | REQUIRED FOR | REQUIRED FOR | |
| BURIED LINE | SEA COAST | |||
| APPLICATIONS | APPLICATIONS* | APPLICATIONS† | APPLICATIONS | |
ACCESSORY | (Below 55°F) | (Over 50 Ft) | (Over 3 Ft) | (Within 2 Miles) | |
|
|
|
|
| |
Crankcase Heater | Yes | Yes | Yes | No | |
|
|
|
|
| |
Evaporator Freeze Thermostat | Yes | No | No | No | |
|
|
|
|
| |
Winter Start Control | Yes‡ | No | No | No | |
|
|
|
|
| |
Accumulator | No | No | Yes | No | |
|
|
|
|
| |
Compressor Start Assist |
|
|
|
| |
Capacitor and Relay | Yes | Yes | Yes | No | |
|
|
|
|
| |
Low Ambient Controller |
|
|
|
| |
or |
|
|
|
| |
MotorMaster® Control | Yes | No | No | No | |
|
|
|
|
| |
Wind Baffle | See | No | No | No | |
Instructions | |||||
|
|
|
| ||
|
|
|
|
| |
Coastal Filter | No | No | No | Yes | |
|
|
|
|
| |
Support Feet | Recommended | No | No | Recommended | |
|
|
|
|
| |
| See |
|
| ||
or |
|
|
| ||
Hard Shutoff TXV | No | Application Guideline | Yes | No | |
|
|
|
|
| |
Ball Bearing Fan Motor | Yes | No | No | No | |
|
|
|
|
|
*For tubing line sets between 50 and 175 ft, refer to Residential’s Split System
†For buried line applications, refer to Residential’s Split Systems Buried Line Application Guidelines.
‡ Only when
ACCESSORY DESCRIPTION AND USAGE (Listed Alphabetically)
1.Ball Bearing Fan Motor
A fan motor with ball bearings which permits speed reduction while maintaining bearing lubrication.
SUGGESTED USE: Required on all units where
2.Compressor Start Assist-Capacitor/Relay Type
Start capacitor and start relay gives “hard” boost to compressor motor at each
SUGGESTED USE: Installations where interconnecting tube length exceeds 50 ft. Installations where outdoor design temperature exceeds 105°F (40.6°C).
Replacement installations with hard shutoff expansion valve on indoor coil. Units installed with
3.Compressor Start Assist-PTC Type
SUGGESTED USE: Installations with marginal power supply.
Replacement installations with rapid pressure balance (RPB) expansion valve on indoor coil.
4.Crankcase Heater
An electric resistance heater which mounts to the base of the compressor to keep the lubricant warm during off cycles. Improves compressor lubrication on restart and minimizes chance of refrigerant slugging. May or may not include a thermostat control.
SUGGESTED USE: When interconnecting tube length exceeds 50 ft.
When unit will be operated below 55°F (12.8°C) outdoor air temperature. (Use with
5.Evaporator Freeze Thermostat
An SPST temperature actuated switch which stops unit operation when evaporator reaches
SUGGESTED USE: With
6.Filter Drier—Bi-flow
A device for removing contaminants from refrigerant circulating in a heat pump system;
SUGGESTED USE:
7.Interface Control
An electric control for controlling a heat pump and gas or oil furnace system for maximum energy savings. It allows heat pump to operate down to a predeter- mined economic balance point temperature, then switches to allow furnace operation only below that temperature. Requires outdoor thermostat (Item 12) to be adjusted for economic balance point temperature.
SUGGESTED USE: For heat pump and gas- or
8.Isolation Relay
An SPDT relay which switches the
SUGGESTED USE: All heat pumps where
9.Liquid Solenoid Valve (LSV)
An electrically operated shutoff valve to be installed at the outdoor unit and which stops and starts refrigerant liquid flow in response to compressor operation. Maintains a column of refrigerant liquid ready for action at next compressor operation cycle.
SUGGESTED USE: In certain
10.Low-Ambient Controller
Head pressure controller is a cycle control device activated by a temperature sensor mounted on a header tube of the outdoor coil. It is designed to cycle the
outdoor fan motors in order to maintain condensing temperature within normal operating limits (approximately 130 to 110°F high, 70 to 50°F low). The control will maintain working head pressure at
SUGGESTED USE: Cooling operation at outdoor temperatures below 55°F (12.8°C).
11.MotorMaster® Control
A fan speed control device activated by a temperature sensor. Designed to control condenser fan motor speed in response to the saturated, condensing tem-
perature during operation in cooling mode only. For outdoor temperatures down to
All commercial installations.
12.Outdoor Thermostat
An SPDT temperature actuated switch which turns on supplemental electric heaters when outdoor air temperature drops below set point.
SUGGESTED USE: Heat pump installations with