| | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | BRANCH CIRCUIT | | | | | | | | | | | | |
| HEATER | | | KW | | INTERNAL | HEATER AMPS | | | Min Ampacity | | | Min Wire Size (AWG) | | | Min Gnd Wire Size | Max Fuse/Ckt Bkr Amps | | Max Wire Length |
| | | PHASE | CIRCUIT | | | 208/230V | | | | | | 208/230V** | | | | 208/230V†† | | | | | | | 208/230V | | | | 208/230V | | | | 208/230V (Ft)‡‡ |
| PART NO. | | | | | | | | | | | | | | | | | | | | | | | | | | | | |
| | | | | | | | | PROTECTION | Single | | Dual Circuit | | Single | Dual Circuit | Single | Dual Circuit | | Single | | Dual Circuit | Single | | Dual Circuit | Single | | Dual Circuit |
| | | 240v | | 208v | | | | Circuit | | L1,L2 | | L3,L4 | | Circuit | L1,L2 | L3,L4 | Circuit | L1,L2 | | L3,L4 | | Circuit | | L1,L2 | L3,L4 | Circuit | | L1,L2 | L3,L4 | Circuit | | L1,L2 | | L3,L4 |
| KFCEH0401N03 | | 3 | | | 2.3 | | 1 | None | 10.9/12.0 | | | — | | — | 15.9/17.3 | | — | | | — | 12/12 | — | | | — | | 12/12 | | — | — | 20/20 | | — | | — | 67/68 | | — | | — |
| KFCEH0501N051 | | 5 | | | 3.8 | | 1 | None | 18.1/20.0 | | | — | | — | 26.0/28.4 | | — | | | — | 10/10 | — | | | — | | 10/10 | | — | — | 30/30 | | — | | — | 66/66 | | — | | — |
| KFCEH0501N052 | | 5 | | | 3.8 | | 1 | None | 18.1/20.0 | | | — | | — | 31.2/33.5 | | — | | | — | 8/8 | — | | | — | | 10/10 | | — | — | 35/35 | | — | | — | 85/88 | | — | | — |
| KFCEH2401C051 | | 5 | | | 3.8 | | 1 | Ckt Bkr | 18.1/20.0 | | | — | | — | 26.0/28.4 | | — | | | — | 10/10 | — | | | — | | 10/10 | | — | — | 30/30 | | — | | — | 66/66 | | — | | — |
| KFCEH2401C052 | | 5 | | | 3.8 | | 1 | Ckt Bkr | 18.1/20.0 | | | — | | — | 31.2/33.5 | | — | | | — | 8/8 | — | | | — | | 10/10 | | — | — | 35/35 | | — | | — | 85/88 | | — | | — |
| KFCEH0801N08 | | 8 | | | 6.0 | | 1 | None | 28.9/32.0 | | | — | | — | 44.7/48.5 | | — | | | — | 8/8 | — | | | — | | 10/10 | | — | — | 45/50 | | — | | — | 59/60 | | — | | — |
| KFCEH2501C08 | | 8 | | | 6.0 | | 1 | Ckt Bkr | 28.9/32.0 | | | — | | — | 44.7/48.5 | | — | | | — | 8/8 | — | | | — | | 10/10 | | — | — | 45/50 | | — | | — | 59/60 | | — | | — |
| KFCEH2901N09*** | | 9 | | | 6.8 | | 1 | None | 32.8/36.0 | | | — | | — | 49.5/53.5 | | — | | | — | 8/6 | — | | | — | | 10/10 | | — | — | 50/60 | | — | | — | 54/87 | | — | | — |
| — | | 9 | | | 6.8 | | 3 | None | 18.8/20.8 | | | — | | — | 32.0/34.5 | | — | | | — | 8/8 | — | | | — | | 10/10 | | — | — | 35/35 | | — | | — | 83/85 | | — | | — |
| KFCEH0901N10 | | 10 | | | 7.5 | | 1 | None | 36.2/40.0 | | | — | | — | 53.8/58.5 | | — | | | — | 6/6 | — | | | — | | 10/10 | | — | — | 60/60 | | — | | — | 78/80 | | — | | — |
| KFCEH2601C10 | | 10 | | | 7.5 | | 1 | Ckt Bkr | 36.2/40.0 | | | — | | — | 53.8/58.5 | | — | | | — | 6/6 | — | | | — | | 10/10 | | — | — | 60/60 | | — | | — | 78/80 | | — | | — |
| KFCEH3001F15*** | | 15 | | | 11.3 | 1 | Fuse | 54.2/59.9 | | | 36.2/40.0 | | 18.1/20.0 | 76.3/83.4 | | 53.8/58.5 | | 22.7/25.0 | 4/4 | 6/6 | | 10/10 | | 8/8 | | 10/10 | 10/10 | | 80/90 | 60/60 | 25/25 | 88/89 | | 78/80 | | | 75/76 |
| KFCEH3101C15*** | | 15 | | | 11.3 | 1 | Ckt Bkr | — | | 36.2/40.0 | | 18.1/20.0 | | | — | 53.8/58.5 | | 22.7/25.0 | — | 6/6 | | 10/10 | | — | | 10/10 | 10/10 | | — | 60/60 | 25/25 | — | | 78/80 | | | 75/76 |
| KFCEH1601315 | | 15 | | | 11.3 | 3 | None | 31.3/34.6 | | | — | | — | 47.7/51.8 | | — | | | — | 8/6 | — | | | — | | 10/10 | | — | — | 50/60 | | — | | — | 56/90 | | — | | — |
| KFCEH2001318 | | 18 | | | 13.5 | 3 | None | 37.6/41.5 | | | — | | — | 55.5/60.4 | | — | | | — | 6/6 | — | | | — | | 10/8 | | — | — | 60/70 | | — | | — | 76/77 | | — | | — |
| KFCEH3201F20*** | | 20 | | | 15.0 | 1 | Fuse | 72.3/79.9 | | | 36.2/40.0 | | 36.2/40.0 | 98.9/108.4 | 53.8/58.5 | | 45.3/50.0 | 3/2 | 6/6 | | 8/8 | | 8/6 | | 10/10 | 10/10 | | 100/110 | 60/60 | 50/50 | 85/109 | | 78/80 | | | 59/59 |
| KFCEH3301C20*** | | 20 | | | 15.0 | 1 | Ckt Bkr | — | | 36.2/40.0 | | 36.2/40.0 | | | — | 53.8/58.5 | | 45.3/50.0 | — | 6/6 | | 8/8 | | — | | 10/10 | 10/10 | | — | 60/60 | 50/50 | — | | 78/80 | | | 59/59 |
| KFCEH3401F24†*** | | 24 | | | 18.0 | 3 | Fuse | 50.1/55.4 | | | — | | — | 71.2/77.8 | | — | | | — | 4/4 | — | | | — | | 8/8 | | — | — | 80/80 | | — | | — | 94/95 | | — | | — |
| | 24 | | | 18.0 | 1 | Fuse | 86.7/95.5 | | | — | | — | 116.9/127.9 | — | | | — | 1/1 | — | | | — | | 6/6 | | — | — | 125/150 | | — | | — | 115/116 | | — | | — |
| | | | | | | | | | | | | | | | | |
| KFCEH3501F30†*** | | 30 | | | 22.5 | 3 | Fuse | 62.6/69.2 | | | — | | — | 86.8/95.0 | | — | | | — | 3/3 | — | | | — | | 8/8 | | — | — | 90/100 | | — | | — | 97/98 | | — | | — |
| | 30 | | | 22.5 | 1 | Fuse | 109.0/120.0 | | — | | — | 144.8/158.5 | — | | | — | 0/00 | — | | | — | | 6/6 | | — | — | 150/175 | | — | | — | 117/150 | | — | | — |
| | | | | | | | | | | | | | | | |
| | | | | | | | | | | | | | | | | SMART HEAT ELECTRICAL DATA | | | | | | | | | | | | | | | | | |
| | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | |
| | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | BRANCH CIRCUIT | | | | | | | | | | | | |
| HEATER | | | KW | | INTERNAL | HEATER AMPS | | | Min Ampacity | | | Min Wire Size (AWG) | | | Min Gnd Wire Size | Max Fuse/Ckt Brk Amps | | Max Wire Length |
| | | PHASE | CIRCUIT | | | 208/230V | | | | | | 208/230V** | | | | 208/230V†† | | | | | | | 208/230V | | | | 208/230V | | | | 208/230V (Ft)‡‡ |
| PART NO. | | | | | | | | | | | | | | | | | | | | | | | | | | | | |
| | | | | | | | | PROTECTION | Single | | | Dual Circuit | Single | | Dual Circuit | Single | Dual Circuit | | Single | | Dual Circuit | Single | | Dual Circuit | Single | | Dual Circuit |
| | | 240v | | 208v | | | | Circuit | | | L1,L2 | | | L3,L4 | Circuit | | L1,L2 | | | L3,L4 | Circuit | L1,L2 | | L3,L4 | | Circuit | | L1,L2 | L3,L4 | Circuit | | L1,L2 | L3,L4 | Circuit | | L1,L2 | | L3,L4 |
| KFCEH0101H10 | | 10 | | | 7.5 | | 1 | None | 32.5/35.9 | | | — | | | — | 44.0/48.3 | | — | | | — | 8/8 | — | | | — | | 10/10 | | — | — | 45/50 | | — | | — | 60/61 | | — | | — |
| KFCEH0201H15 | | 15 | | | 11.3 | 1 | Fuse | 54.2/59.9 | 39.7/43.9 | 14.4/16.0 | 73.2/80.3 | 49.7/54.9 | 23.4/25.4 | 4/4 | 8/6 | | 10/10 | | 8/8 | | 10/10 | 10/10 | | 80/90 | 50/60 | 25/30 | 92/92 | | 53/85 | | | 73/74 |
| KFCEH0301H20 | | 20 | | | 15.0 | 1 | Fuse | 72.3/79.9 | 36.2/40.0 | 36.2/40.0 | 97.2/106.7 | 52.0/56.8 | 45.3/50.0 | 3/2 | 6/6 | | 8/8 | | 8/6 | | 10/10 | 10/10 | | 100/110 | 60/60 | 50/50 | 87/111 | | 81/82 | | | 93/93 |
| | | | | | | | | | FIELD MULTIPOINT WIRING OF 24-AND 30-KW SINGLE PHASE | | | | | | | | | | | |
| | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | |
| | | KW | | | HEATER AMPS | | | | MIN AMPACITY | | | | | MIN WIRE SIZE (AWG) | | MIN GND | | MAX FUSE/CKT BKR AMPS | | | MAX WIRE LENGTH | |
| HEATER PART NO. | | | PHASE | | | 208/230V | | | | | | | | 208/230V** | | | | | | 208/230V†† | | | | | | | | 208/230V | | | | | 208/230V (FT)‡‡ | |
| | | | | | | | | | | | | | | | | | | | | | | | | WIRE SIZE | | | | | | | | |
| | 240V | | 208V | | | L1,L2 | | L3,L4 | | L5,L6 | | L1,L2 | | L3,L4 | | | L5,L6 | | L1,L2 | L3,L4 | | L5,L6 | | 208/230V | | L1,L2 | | L3,L4 | | L5,L6 | | L1,L2 | | L3,L4 | | | L5,L6 |
| KFCEH3401F24† | 24 | | 18.0 | | 1 | 28.9/32.0 | | 28.9/32.0 | | 28.9/32.0 | | 44.7/48.5 | | 36.2/40.0 | | 36.2/40.0 | | 8/8 | 8/8 | | | 8/8 | | | 10/10 | | 45/50 | | 40/40 | | 40/40 | | 59/60 | | 73/73 | | | 73/73 |
| KFCEH3501F30† | 30 | | 22.5 | | 1 | 36.2/40.0 | | 36.2/40.0 | | 36.2/40.0 | | 53.8/58.5 | | 45.3/50.0 | | 45.3/50.0 | | 6/6 | 8/8 | | | 8/8 | | | 10/10 | | 60/60 | | 50/50 | | 50/50 | | 78/80 | | 59/59 | | | 59/59 |
†Field convertible to 1 phase, single or multiple supply circuit.
‡ Field convertible to 3 phase.
** Includes blower motor amps of largest fan coil used with heater.
††Copper wire must be used. If other than uncoated (non-plated), 75°C ambient, copper wire (solid wire for 10 AWG and smaller, stranded wire for larger than 10 AWG) is used, consult applicable tables of the National Electric Code (ANSI/NFPA 70).
‡‡Length shown is as measured 1 way along wire path between unit and service panel for a voltage drop not to exceed 2%.
***Heaters are Intelligent Heat capable when used with the FK, FV fan coils and corporate 2-speed programmable thermostat (TSTATBBP2S01-A), or Thermidistat™ Control (TSTATBBPRH01-B). NOTES: 1. For fan coil sizes 018-036.
2.For fan coil sizes 042-060 and all FK4D, FV4B sizes.
3.Single circuit application of F15 and F20 heaters requires single-point wiring kit accessory