ELECTRIC HEATER STATIC PRESSURE DROP

The airflow performance data was developed using fan coils with 10-kw electric heaters (2 elements) in the 001 and 002 size units and 15-kw heaters (3 elements) in the 003 and 004 size units.

001, 002

003, 004

 

 

EXTERNAL STATIC

HEATER

 

PRESSURE

ELEMENTS

KW

CORRECTION

0

0

+0.02

1

3, 5

+0.01

2

8, 10

0

3

9, 15

–0.02

4

20

–0.04

 

 

EXTERNAL STATIC

HEATER

 

PRESSURE

ELEMENTS

KW

CORRECTION

0

0

+0.04

2

8, 10

+0.02

3

9, 15

0

4

20

–0.02

6

18, 24, 30

–0.10

The airflow performance data was developed using fan coils with 10-kw electric heaters (2 elements) in the 001 and 002 units and 15-kw heaters

(3 elements) in the 003 and 004 units. For fan coils with heaters of a different number of elements, the available external static at a given CFM from the curve may be corrected by adding or subtracting available external static pressure as indicated above.

ACCESSORIES

ITEM

ACCESSORY PART NO.*

FAN COIL SIZE USED WITH

Disconnect Kit

KFADK0101DSC

Cooling Controls and Heaters 3-kw through 10-kw

Downflow Base Kit

KFACB0101CFB

001

 

KFACB0201CFB

002

 

KFACB0301CFB

003, 004

Downflow Conversion Kit

KFADC0201SLP

Slope Coil Units — 001, 002

 

KFADC0401ACL

A-Coil Units — 003, 004

Single-Point Wiring Kit

KFASP0101SPK

Only with 15- and 20-kw Fused Heaters

Filter Kit (12 pack)

KFAFK0112SML

001

 

KFAFK0212MED

002

 

KFAFK0312LRG

003, 004

Evaporator Coil

KFAEC0501024

001

 

KFAEC0601036

002

 

KFAEC0301048

003

 

KFAEC0401060

004

Downflow/Horizontal Conversion Gasket Kit

KFAHD0101SLP

All

* Factory authorized and listed, field-installed.

Accessory Kits Description

Suggested and Required Use

1.Disconnect Kit

The kit is used to disconnect electrical power to the fan coil so service or maintenance may be performed safely.

SUGGESTED USE: FH4 units for 3-kw through 10-kw electric resistance heaters and cooling controls.

2.Downflow Base Kit

This kit is designed to provide a 1-in. minimum clearance between unit discharge plenum, ductwork, and combustible materials. It also provides a gap free seal with the floor.

REQUIRED USE: This kit must be used whenever FH4 fan coils are used in downflow applications.

3.Downflow Conversion Kit

Fan coils are shipped from the factory for upflow or horizontal-left applications. Downflow conversion kits provide proper condensate water drainage and support for the coil when used in downflow applications. Separate kits are available for slope coils and A-coils.

REQUIRED USE: This kit must be used whenever FH4A fan coils are used in downflow applications.

4.Single Point Wiring Kit

The single point wiring kit acts as a jumper between L1 and L3 lugs, and between the L2 and L4 lugs. This allows the installer to run 2 heavy-gage, high-voltage wires into the fan coil rather than 4 light-gage, high-voltage wires.

SUGGESTED USE: FH4 fan coils with 15-kw and 20-kw fused heaters only.

5.Fan Coil Filter

The kit consists of 12 fan coil framed filters. These filters collect large dust particles from the return air entering the fan coil and prevent them from collecting on the coil. This process helps to keep the coil clean, which increases heat transfer and in turn the efficiency of the system.

SUGGESTED USE: To replace filters in FH4 fan coils.

6.Evaporator Coil Kit

The kit contains a heating/cooling coil and drain pan.

SUGGESTED USE: Accessory coil used with FH4 fan unit.

7.Downflow/Horizontal Conversion Gasket Kit

This kit provides the proper gasketing of units when applied in either a Downflow or Horizontal application.

REQUIRED USE: FH4 fan coils.

—10—

Page 10
Image 10
Bryant FH4B manual Electric Heater Static Pressure Drop, 001 003, Accessories

FH4B specifications

The Bryant FH4B series heat pumps represent a notable advancement in heating and cooling technology, designed to offer homeowners an efficient and reliable climate control solution. This versatile unit is built with a focus on high performance, energy efficiency, and user-friendly operation.

One key feature of the FH4B is its impressive SEER (Seasonal Energy Efficiency Ratio) rating, which indicates exceptional energy efficiency during cooling operations. Such a high rating not only reflects the advanced engineering of the unit but also ensures lower energy bills over time, making it an eco-friendly choice for environmentally conscious homeowners.

The FH4B series utilizes a two-stage scroll compressor, which operates more quietly than traditional compressors. This dual-stage operation allows the unit to adapt to the heating or cooling requirements effectively, providing consistent comfort while optimizing energy consumption. The compressor’s enhanced efficiency significantly reduces temperature fluctuations, ensuring a more stable indoor climate.

One of the standout technologies of the FH4B is its humidification control. This system is designed to maintain optimal humidity levels within the home, which is essential for comfort and health. By intelligently managing humidity, this feature not only improves air quality but also helps to prevent mold and mildew growth.

In addition to efficiency and comfort, the FH4B series is equipped with advanced communication capabilities. Homeowners can take advantage of smart thermostat compatibility, allowing remote access and control. This means users can regulate their home’s temperature from anywhere, providing unrivaled convenience and flexibility.

Moreover, the unit's design incorporates a robust cabinet and weather-resistant features, ensuring durability and longevity in various outdoor conditions. This means homeowners can rely on the FH4B for consistent performance year after year, regardless of the climate in which they reside.

Overall, the Bryant FH4B series heat pumps combine energy efficiency, advanced technology, and practical features, making them an excellent option for anyone seeking to enhance their home's comfort while keeping energy costs manageable. With its blend of innovation and reliability, the FH4B has established itself as a top choice in residential climate control solutions.