INSTALLATION MANUAL To Personnel Charged in Installation (Electric) Work and Service

Simple Remote Controller

MODEL : RBC-AS21E

Accessory parts

Part Name

Q’ty

Part Name

Q’ty

Remote controller

 

Spacer

2

 

 

 

 

1

Wire joint

 

 

 

2

(200mm-cable

 

 

attached)

 

 

 

Screw

2

Clamper

1

M4 x 25

 

Wood screw

2

Installation Manual

1

 

 

Requirement to install

the remote controller

How to install

the remote controller switch

NOTE 1 :

Avoid to twist the remote controller cable with the power supply cable, etc. or to store them in the same metal pipe, otherwise it causes a malfunc- tion.

NOTE 2 :

Install the remote controller apart from the generation source of noise.

NOTE 3 :

When noise is contained to the power source of the indoor unit, counter measures such as mounting the noise filter is necessary.

How to perform cabling of the remote controller

• Connection diagram

Remote

 

 

 

 

controller

Terminal block for

A

 

W

remote controller

 

B

 

B

cable in indoor unit

 

 

 

 

W : White

Remote controller cable

Connecting

Cable from

B : Black

(Procured locally)

section

Remote controller

 

 

 

 

body

Non polarity, 2 core cable is used.

Use 0.5mm² to 2 mm² cable.

Basic cabling diagram NOTE :

Connect cables without miswiring. (Miswiring breaks the unit.)

In a case to operate an indoor unit from the remote controllers at two positions

Remote controller

Remote controller

 

(Master)

 

(Sub)

 

 

 

 

 

 

 

 

 

 

 

(Sold separately)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Remote controller cable

 

 

 

 

 

 

 

 

 

 

(Procured locally)

Terminal block for remote controller cable

A B

82

Installation place

• Install the remote controller at a position within 1

to 1.5m from the floor, where the average tem-

perature in the room can be felt.

• Do not install the remote controller at a place

exposed to direct sunlight or direct outside air,

such as a side of window, etc.

• Do not install the remote controller at a place

behind something or rear side of something,

where air flow is poor in the room.

• Do not install the remote controller in the freezing

box or refrigerator because water proof or drop-

proof is not applied to this remote controller.

• Be sure to set the remote controller vertically on

In case of using the remote controller as a concealed type

Rear case

Spacer

 

Remote controller

 

body

Wall

Attached wire joint

(White, 2 pcs.)

Remote controller cable

 

Cable from

Wire joint

remote controller body

 

1)Peel the sheath of cable to be connected by approx. 14mm.

2)Twist two cables and pressure-connect them using a wire joint.

3)When an exclusive pressure-connecting tool is not used or soldering connection is used, apply insulation process with an insulation tape.

Indoor unit

Earth

In a case to operate a group control of multiple indoor units from the remote controllers at two positions

*Master and sub remote controllers are operable even if they are installed to any indoor unit.

Remote controller

 

Remote controller

(Master)

 

 

(Sub)

 

 

Remote controller inter-unit

 

 

cable for group control

 

(Sold

 

(Procured locally)

 

(Sold

separately)

 

 

 

separately)

Terminal block

 

 

 

 

for remote

 

 

 

 

controller

A B

A B

A B

A B

cable

 

 

 

 

the wall surface, etc.

How to select the room temp. sensor

The room temperature sensors are equipped in the indoor unit and the remote controller.

One of two sensors works. Usually, the room temperature sensor in the indoor unit is set to work. To select the sensor in the remote controller, turn the remote controller sensor from OFF to ON.

NOTE 1 :

Selecting the sensor in the remote controller is impossible on the sub remote controller.

NOTE 2 :

Do not select the sensor in the remote controller when a remote controller sensor is used. (Because it causes a straying.)

Screws

M4 x 25 or wood screws (2 pcs.)

1.Inserting a minus screwdriver, etc. into the groove at the lower side of the remote controller body, force open the rear case to remove it.

2.Using the attached M4 screws (2 pcs.), fix the rear case of the remote controller.

Before installation, press to open the screw hole with a screwdriver, etc.

Fix it with the spacer, but not so strongly. If the remote controller does not fit closely to the wall, adjust it by cutting off the spacer.

3.Connect the remote controller cable (2 cores) to the cable from the remote controller body. Connect the remote controller cable without miswiring upon confirmation of the terminal numbers of the indoor unit. (If applyied

AC 220/230/240V, may damage the unit.)

4.Install the remote controller body to hooks on the rear case and putting into the hooks.

Requirement for installation of

multiple remote controllers

“2 remote controller control” means that one or multiple units are operated by the multiple remote controllers.

• How to install

For 2 remote controller control, install the remote controllers in the following procedure.

1.Set one of the set multiple remote controllers to the master remote controller.

(At shipment from factory)

2.For other remote controllers, turn the remote controller address switch on the remote controller P.C. board from OFF to ON. They function as sub remote controllers under the above condition.

 

 

 

Indoor unit

 

 

 

 

Indoor unit

 

 

 

 

Indoor unit

 

 

 

 

Indoor unit

 

 

 

No.1

 

 

 

 

No.2

 

 

 

 

No.3

 

 

 

 

No.N

 

 

 

 

Earth

Earth

Earth

Earth

Remote controller test run setup

1.Push key after keeping [CHECK] button pushed on the remote controller for 4 seconds or more.

During the test run, “TEST” is displayed on LCD.

The temperature cannot be controlled if [TEST] is displayed. Do not use [TEST] in a case other than a test run, otherwise an excessive load is applied on the machine.

2.Use [TEST] in one of HEAT, COOL, and FAN operation modes.

NOTE :

The outdoor unit does not operate for approx. 3 minutes after the power supply has been turned on or the operation has stopped.

3.After the test run has finished, push [CHECK] button again to check “TEST” on LCD has gone off. (For this remote controller, a release function of 60 minutes timer is provided to prevent consecutive test runs.)

85464359428000 (EN)

Page 82
Image 82
Toshiba R410A Accessory parts, Requirement for installation Multiple remote controllers, Remote controller test run setup

R410A specifications

Toshiba R410A is a highly regarded refrigerant known for its efficiency and environmental benefits. This hydrofluorocarbon (HFC) mixture is widely used in various air conditioning and refrigeration applications due to its excellent thermodynamic properties. One of the standout features of R410A is its superior energy efficiency, which contributes to lower energy consumption and reduced CO2 emissions in HVAC systems.

One significant advantage of R410A over older refrigerants, such as R22, is its lower ozone depletion potential (ODP). R410A has an ODP of zero, making it a more environmentally friendly choice. This characteristic aligns with global initiatives aimed at protecting the ozone layer and promoting sustainable practices. The shift to R410A has been supported by government regulations in many countries, phasing out older, more harmful refrigerants.

Toshiba has incorporated advanced technologies in its R410A compatible products, enhancing performance and reliability. Among these technologies is the inverter technology that allows the compressor to operate at variable speeds. This functionality leads to improved temperature regulation, reduced noise levels, and further energy savings. Inverter systems provide precise control over the cooling and heating processes, allowing for a comfortable indoor environment while minimizing wastage of energy.

R410A also exhibits excellent heat transfer properties, which boosts cooling capacity. This feature makes it suitable for large-scale HVAC systems, including commercial and industrial applications. Its high-pressure characteristics enable the design of more compact and efficient components, allowing for smaller units and easier installation.

Furthermore, Toshiba's dedication to technological innovation is visible in its commitment to research and development. The company continuously strives to optimize systems that utilize R410A, focusing on reliability and longevity. This includes improved compressor designs, enhanced heat exchangers, and the integration of smart controls that adapt to the varying load conditions in real-time.

In terms of safety, R410A is classified as non-toxic and non-flammable under normal conditions, making it a safe choice for use in residential and commercial settings. However, it is important to note that R410A operates at higher pressures compared to traditional refrigerants, necessitating proper equipment design and handling procedures.

In conclusion, Toshiba R410A stands out in the market for its energy efficiency, environmental safety, and technological advancements. It is an ideal refrigerant for modern HVAC applications, contributing to both comfort and sustainability. As the industry continues to evolve, R410A remains a pivotal element in the quest for responsible and efficient refrigeration solutions.