Toshiba R410A Refrigerant Piping Connection, Optional Installation Parts Local Procure

Models: R410A

1 88
Download 88 pages 10.91 Kb
Page 9
Image 9
Refrigerant Piping Connection

<SM560AT-E>

Refrigerant Piping Connection

 

TAKE NOTICE THESE IMPORTANT Waterproof rubber cap

Base plate

Drain nipple

<SM800AT-E>

Knockout hole

Open

Waterproof rubber cap

4 POINTS BELOW FOR PIPING WORK<Piping connection> Drain nipple

CAUTION

TAKE NOTICE THESE IMPORTANT

4 POINTS BELOW FOR PIPING WORK

1.Keep dust and moisture away from inside the connecting pipes.

2.Tightly connect the connection between pipes and the unit.

3.Evacuate the air in the connecting pipes using

VACUUM PUMP.

4.Check gas leak at connected points.

<Piping connection>

Capacity

Liquid side

Gas side

rank

 

 

 

 

Outer

Thickness

Outer

Thickness

RAV-

diameter

diameter

 

 

 

 

 

SM560

Ø6.4

0.8

Ø12.7

0.8

 

 

 

 

 

SM800

Ø9.5

0.8

Ø15.9

1.0

 

 

 

 

 

When there is a possibility of freezing of drain at the cold district or a snowfall area, be careful for drainage ability of drain. The drainage ability increases when a knockout hole on the base plate is opened. (Open the knockout hole to outside using a screwdriver, etc.)

Optional Installation Parts

(Local Procure)

 

Parts name

Q’ty

 

 

 

A

Refrigerant piping

Each one

Liquid side : Ø6.35 mm or Ø9.52 mm

 

Gas side : Ø12.7 mm or Ø15.9 mm

 

 

 

 

B

Pipe insulating material

1

(polyethylene foam, 6 mm thick)

 

 

 

 

 

C

Putty, PVC tapes

Each one

 

 

 

For Reference

If a heating operation would be continuously performed for a long time under the condition that the outdoor temperature is 0°C or lower, draining of defrosted water may be difficult due to freezing of the bottom plate, resulting in a trouble of the cabinet or fan.

It is recommended to procure an anti-freeze heater locally for a safety installation of the air conditioner.

For details, contact the dealer.

9

Page 9
Image 9
Toshiba R410A Refrigerant Piping Connection, Optional Installation Parts Local Procure, For Reference, <SM560AT-E>