Toshiba R410A Accessory And Refrigerant, Selection Of Installation, Refrigerant Piping, Air purge

Models: R410A

1 88
Download 88 pages 10.91 Kb
Page 6
Image 6
2 ACCESSORY AND REFRIGERANT

2 ACCESSORY AND REFRIGERANT

Accessory and Installation Parts

1

3

 

Outdoor unit

 

Protective bush

Installation manual x 1

 

(For SM800AT only)

Drain nipple

 

 

2

4

Guard material for

 

 

 

 

passage part

Waterproof rubber cap

 

(For SM800AT only)

Refrigerant Piping

Piping kit used for the conventional refrigerant cannot be used.

Use copper pipe with 0.8 mm or more thickness for Ø6.4, Ø9.5, Ø12.7.

Use copper pipe with 1.0 mm or more thickness for Ø15.9.

Flare nut and flare works are also different from those of the conventional refrigerant. Take out the flare nut attached to the main unit of the air conditioner, and use it.

3 SELECTION OF INSTALLATION

Before installation

Be careful to the following items before installation.

Length of refrigerant pipe

<SM560AT-E>

Length of refrigerant pipe

 

connected to

Item

indoor/outdoor unit

 

 

 

20m or shorter

Addition of refrigerant is

unnecessary at the local site.

 

 

 

*21m to 30m

<Addition of refrigerant>

Add 20g of refrigerant for every

 

1m of pipe which exceeds 20m.

 

 

*Caution at addition of refrigerant

When the total length of refrigerant pipe exceeds 20m, add 20g/m of refrigerant and the maximum total length of pipe is 30m.

(Max. amount of additional refrigerant is 200g.)

Charge the refrigerant accurately. Overcharge may cause a serious trouble of compressor.

<SM800AT-E>

Length of refrigerant pipe

 

connected to

Item

indoor/outdoor unit

 

 

 

20m or shorter

Addition of refrigerant is

unnecessary at the local site.

 

 

 

*21m to 50m

<Addition of refrigerant>

Add 40g of refrigerant for every

 

1m of pipe which exceeds 20m.

 

 

*Caution at addition of refrigerant

When the total length of refrigerant pipe exceeds 20m, add 40g/m of refrigerant and the maximum total length of pipe is 50m.

(Max. amount of additional refrigerant is 1200g.)

Charge the refrigerant accurately. Overcharge may cause a serious trouble of compressor.

Air purge

For air purge, use a vacuum pump.

Do not use refrigerant charged in the outdoor unit for air purge. (The refrigerant for air purge is not con- tained in the outdoor unit.)

Electrical cabling

Be sure to fix the power cables and indoor/outdoor connecting cables with clamps so that they do not contact with the cabinet, etc.

6

Page 6
Image 6
Toshiba R410A Accessory And Refrigerant, Selection Of Installation, Accessory and Installation Parts, Refrigerant Piping