Bryant FH4B manual FAN Coil Electrical Data Units Without Electrical Heat, Electric Heaters

Models: FH4B

1 12
Download 12 pages 140 b
Page 7
Image 7

FAN COIL ELECTRICAL DATA

(UNITS WITHOUT ELECTRICAL HEAT)

 

 

 

MIN

BRANCH CIRCUIT

UNIT

VOLTS

 

CKT

Min Wire

 

SIZE

(1 PHASE)

FLA

AMPS

Size AWG*

Fuse Amps

001

208/230

1.8

2.3

14

15

002

208/230

2.7

3.4

14

15

003

208/230

4.3

5.4

14

15

004

208/230

5.4

6.8

14

15

*Use copper wire only. 75°C must be used in this application. When using non-metallic (NM) sheathed cable, wire size required should be based on that of 60°C conductors, instead of wire sizes shown in table above per NEC 1999 Article 336-26.

FLA — Full Load Amps

NOTE: If branch circuit wire length exceeds 100 ft., consult NEC 215-2 to determine maximum wire length. Use 2% voltage drop.

ELECTRIC HEATER INTERNAL PROTECTION*

 

 

FUSES

CKT BKR

HEATER KW

PHASE

QTY/SIZE

QTY/SIZE†

3

1

5

1

1/60

8

1

1/60

10

1

1/60

15

1

2/30 – 2/60

2/60

20

1

4/60

2/60

24

3/1

6/60

30

3/1

6/60

9

1/3**

15

3

18

3

*5-, 8-, 10-kw factory-installed heat has no internal protection. 15-kw factory-installed heat is internally protected with fuses.

**KFCEH1401N09 is single phase only.

Circuit breakers are 2 pole.

ELECTRIC HEATERS

 

 

 

 

INTERNAL

 

 

HEATER

KW

 

STAGES (KW

CIRCUIT

FAN COIL SIZE

HEATING CAP. **

PART NO.

@ 240V

VOLTS/PHASE

OPERATING)

PROTECTION

USED WITH

@ 230V

KFCEH0401N03

3

230/1

3

None

001

9,400

KFCEH0501N05

5

230/1

5

None

001, 002

15,700

KFCEH0801N08

8

230/1

8

None

001–004

25,100

KFCEH0901N10

10

230/1

10

None

001–004

31,400

KFCEH3201F20

20

230/1

5, 20

Fuse‡

002–004

62,800

KFCEH1601315

15

230/3

5, 15

None

002–004

47,100

KFCEH2001318

18

230/3

6, 12, 18

None

003, 004

56,500

KFCEH3401F24

24

230/3*

8, 16, 24

Fuse

003, 004

75,300

KFCEH3501F30

30

230/3*

10, 20, 30

Fuse

003, 004

94,100

KFCEH2401C05

5

230/1

5

Circuit Breaker

001, 002

15,700

KFCEH2501C08

8

230/1

8

Circuit Breaker

001, 002

25,100

KFCEH2601C10

10

230/1

10

Circuit Breaker

001–004

31,400

KFCEH3301C20

20

230/1

5, 20

Circuit Breaker

002–004

62,800

KFCEH2901N09

9

230/1†

3, 9

None

002–004

28,200

KFCEH3001F15

15

230/1

5, 15

Fuse‡

001–004

47,100

KFCEH3101C15

15

230/1

5, 15

Circuit Breaker

001–004

47,100

—7—

Page 7
Image 7
Bryant FH4B FAN Coil Electrical Data Units Without Electrical Heat, Electric Heater Internal Protection, Electric Heaters