FAN COIL ELECTRICAL DATA
(UNITS WITHOUT ELECTRICAL HEAT)
|
|
| MIN | BRANCH CIRCUIT | |
UNIT | VOLTS |
| CKT | Min Wire |
|
SIZE | (1 PHASE) | FLA | AMPS | Size AWG* | Fuse Amps |
001 | 208/230 | 1.8 | 2.3 | 14 | 15 |
002 | 208/230 | 2.7 | 3.4 | 14 | 15 |
003 | 208/230 | 4.3 | 5.4 | 14 | 15 |
004 | 208/230 | 5.4 | 6.8 | 14 | 15 |
*Use copper wire only. 75°C must be used in this application. When using
FLA — Full Load Amps
NOTE: If branch circuit wire length exceeds 100 ft., consult NEC
ELECTRIC HEATER INTERNAL PROTECTION*
|
| FUSES | CKT BKR |
HEATER KW | PHASE | QTY/SIZE | QTY/SIZE† |
3 | 1 | — | — |
5 | 1 | — | 1/60 |
8 | 1 | — | 1/60 |
10 | 1 | — | 1/60 |
15 | 1 | 2/30 – 2/60 | 2/60 |
20 | 1 | 4/60 | 2/60 |
24 | 3/1 | 6/60 | — |
30 | 3/1 | 6/60 | — |
9 | 1/3** | — | — |
15 | 3 | — | — |
18 | 3 | — | — |
*
**KFCEH1401N09 is single phase only.
†Circuit breakers are 2 pole.
ELECTRIC HEATERS
|
|
|
| INTERNAL |
|
|
HEATER | KW |
| STAGES (KW | CIRCUIT | FAN COIL SIZE | HEATING CAP. ** |
PART NO. | @ 240V | VOLTS/PHASE | OPERATING) | PROTECTION | USED WITH | @ 230V |
KFCEH0401N03 | 3 | 230/1 | 3 | None | 001 | 9,400 |
KFCEH0501N05 | 5 | 230/1 | 5 | None | 001, 002 | 15,700 |
KFCEH0801N08 | 8 | 230/1 | 8 | None | 25,100 | |
KFCEH0901N10 | 10 | 230/1 | 10 | None | 31,400 | |
KFCEH3201F20 | 20 | 230/1 | 5, 20 | Fuse‡ | 62,800 | |
KFCEH1601315 | 15 | 230/3 | 5, 15 | None | 47,100 | |
KFCEH2001318 | 18 | 230/3 | 6, 12, 18 | None | 003, 004 | 56,500 |
KFCEH3401F24 | 24 | 230/3* | 8, 16, 24 | Fuse | 003, 004 | 75,300 |
KFCEH3501F30 | 30 | 230/3* | 10, 20, 30 | Fuse | 003, 004 | 94,100 |
KFCEH2401C05 | 5 | 230/1 | 5 | Circuit Breaker | 001, 002 | 15,700 |
KFCEH2501C08 | 8 | 230/1 | 8 | Circuit Breaker | 001, 002 | 25,100 |
KFCEH2601C10 | 10 | 230/1 | 10 | Circuit Breaker | 31,400 | |
KFCEH3301C20 | 20 | 230/1 | 5, 20 | Circuit Breaker | 62,800 | |
KFCEH2901N09 | 9 | 230/1† | 3, 9 | None | 28,200 | |
KFCEH3001F15 | 15 | 230/1 | 5, 15 | Fuse‡ | 47,100 | |
KFCEH3101C15 | 15 | 230/1 | 5, 15 | Circuit Breaker | 47,100 |