Burnham 20_PV_I manual Boiler Model, Minimum Suction Pressure

Models: 20_PV_I

1 32
Download 32 pages 11.1 Kb
Page 23
Image 23
Table 8: Minimum Suction Pressure

Table 8: Minimum Suction Pressure

Boiler Model

Minimum Suction Pressure

 

 

203PV

-0.50 inches w.c.

 

 

204PV

-0.50 inches w.c.

 

 

205PV

-0.80 inches w.c.

 

 

206PV

-0.80 inches w.c.

 

 

I.Lubrication. There are no parts requiring lubrication by service technician or owner. Circulator bearings are water lubricated. Blower motor bearings are factory sealed.

Figure 20: Procedure for Measuring Fan Suction

Pressure

23

Page 23
Image 23
Burnham 20_PV_I manual Boiler Model, Minimum Suction Pressure, Procedure for Measuring Fan Suction Pressure