Burnham 81441001R8-3/06 installation instructions Steam

Models: 81441001R8-3/06

1 16
Download 16 pages 6.21 Kb
Page 2
Image 2
Steam

For Ratings at the following temperatures, multiply the 150° rating by the multiplier of the desired temperature. Temperature – Multiplier

150°

-

1.0

130°

-

.68

110°

-

.42

 

 

 

120°

-

.54

100°

-

.32

140°

-

.82

 

 

 

 

 

 

No. 9A Base-Ray®I=B=R Ratings – Steam and Hot Water (500 LBS/HR Flow Rate **)

 

Steam

Steam

 

HOT WATER RATINGS IN BTU PER HOUR AT

 

Pressure

Length in

Rating

 

500 LBS./HR. (ONE G.P.M.) FLOW RATE**

 

Drop in

Rating

 

 

Lineal Feet*

B.T.U. Per

 

AT AVERAGE WAER TEMPERATURE OF

 

Inches of

Square Feet

 

 

 

Hr. At 215°F

230°F

220°F

210°F

200°F

190°F

180°F

170°F

150°F

Water***

 

 

Per Lin. Ft.

3.40

820

890

830

770

710

650

590

520

390

 

1.5

5.1

1230

1340

1250

1160

1070

980

890

780

585

.10

2.0

6.8

1640

1780

1660

1540

1420

1300

1180

1040

780

.10

2.5

8.5

2050

2230

2080

1930

1780

1630

1480

1300

975

.11

3.0

10.2

2460

2670

2490

2310

2130

1950

1770

1560

1170

.12

3.5

11.9

2870

3120

2910

2700

2490

2280

2070

1820

1365

.13

4.0

13.6

3280

3560

3320

3080

2840

2600

2360

2080

1560

.14

4.5

15.3

3690

4010

3740

3470

3200

2930

2660

2340

1755

.14

5.0

17.0

4100

4450

4150

3850

3550

3250

2950

2600

1950

.15

5.5

18.7

4510

4900

4570

4240

3910

3580

3250

2860

2145

.16

6.0

20.4

4920

5340

4980

4620

4260

3900

3540

3120

2340

.17

6.5

22.1

5330

5790

5400

5010

4620

4230

3840

3380

2535

.18

7.0

23.8

5740

6230

5810

5390

4970

4550

4130

3640

2730

.18

7.5

25.5

6150

6680

6230

5780

5330

4880

4430

3900

2925

.19

8.0

27.2

6560

7120

6640

6160

5680

5200

4720

4160

3120

.20

8.5

28.9

6970

7570

7060

6550

6040

5530

5020

4420

3315

.21

9.0

30.6

7380

8010

7470

6930

6390

5850

5310

4680

3510

.22

9.5

32.3

7790

8460

7890

7320

6750

6180

5610

4940

3705

.22

10.0

34.0

8200

8900

8300

7700

7100

6500

5900

5200

3900

.23

10.5

35.7

8610

9350

8715

8090

7460

6830

6200

5460

4095

.24

11.0

37.4

9020

9790

9130

8470

7810

7150

6490

5720

4290

.25

11.5

39.1

9430

10240

9550

8860

8170

7480

6790

5980

4485

.26

12.0

40.8

9840

10680

9960

9240

8520

7800

7080

6240

4680

.26

12.5

42.5

10250

11130

10380

9630

8880

8130

7380

6500

4785

.27

13.0

44.2

10660

11570

10790

10010

9230

8450

7670

6760

5070

.28

13.5

45.9

11070

12020

11210

10400

9590

8780

7970

7020

5265

.29

14.0

47.6

11480

12460

11620

10780

9940

9100

8260

7280

5460

.30

14.5

49.3

11890

12910

12040

11170

10300

9430

8550

7540

5655

.30

15.0

51.0

12300

13350

12450

11550

10650

9750

8850

7800

5850

.31

15.5

52.7

12710

13800

12870

11940

11010

10080

9150

8060

6045

.32

16.0

54.4

13120

14240

13280

12320

11360

10400

9440

8320

6240

.33

16.5

56.1

13530

14690

13700

12710

11720

10730

9470

8580

6435

.34

17.0

57.8

13940

15130

14110

13090

12070

11050

10030

8840

6630

.34

17.5

59.5

14350

15580

14530

13480

12430

11380

10330

9100

6825

.35

18.0

61.2

14760

16020

14940

13860

12780

11700

10620

9360

7020

.36

18.5

62.9

15170

16470

15360

14250

13140

12030

10920

9620

7215

.37

19.0

64.6

15580

16910

15770

14630

13490

12350

11210

9880

7410

.38

19.5

66.3

15990

17360

16190

15020

13850

12680

11510

10140

7605

.38

20.0

68.0

16400

17800

16600

15400

14200

13000

11800

10400

7800

.39

20.5

69.7

16810

18250

17020

15790

14560

13330

12100

10660

7995

.40

21.0

71.4

17220

18690

17430

16170

14910

13650

12390

10920

8190

.41

21.5

73.1

17630

19140

17850

16560

15270

13980

12690

11180

8385

.42

22.0

74.8

18040

19580

18260

16940

15620

14300

12980

11440

8580

.42

I=B=R Ratings are determined from tests made in accordance with the I=B=R Testing and Rating Code for Baseboard Type of Radiation, including an allowance of 15% for heating effect permitted by the Code.

Ratings based on active length. Active length same as total length.

**The Hot Water Ratings at 500 lb. Flow Rate are based on a standard water flow rate of 500 lbs. per hour (one gallon per minute) through the Base-Ray. These ratings should be used for all installations except as noted under 2000 Lb. Flow Rate.

*Add ½" to length for each bushing. Add 5" to length for each valve enclosure.

***Based on ¾" pipe connections.

2

Page 2
Image 2
Burnham 81441001R8-3/06 installation instructions Steam