Burnham 81441001R8-3/06 installation instructions Steam

Models: 81441001R8-3/06

1 16
Download 16 pages 6.21 Kb
Page 3
Image 3
Manual background

For Ratings at the following temperatures, multiply the 150° rating by the multiplier of the desired temperature. Temperature – Multiplier

150°

-

1.0

120°

-

.54

 

 

130° - .68

140°

-

110°

-

.42

.82

 

 

 

No. 9A Base-Ray®I=B=R Ratings – Steam and Hot Water (2000 LBS/HR Flow Rate **)

 

Steam

Steam

 

HOT WATER RATINGS IN BTU PER HOUR AT

 

Pressure

Length in

Rating

 

2000 LBS./HR. (FOUR G.P.M.) FLOW RATE**

 

Drop in

Rating

 

 

Lineal Feet*

B.T.U. Per

 

AT AVERAGE WAER TEMPERATURE OF

 

Inches of

Square Feet

 

 

 

Hr. At 215°F

230°F

220°F

210°F

200°F

190°F

180°F

170°F

150°F

Water***

 

 

Per Lin. Ft.

3.40

820

940

880

810

750

690

620

550

410

 

1.5

5.1

1230

1410

1320

1220

1130

1040

930

830

615

1.29

2.0

6.8

1640

1880

1760

1620

1500

1380

1240

1100

820

1.39

2.5

8.5

2050

2350

2200

2030

1880

1730

1550

1380

1025

1.50

3.0

10.2

2460

2820

2640

2430

2250

2070

1860

1650

1230

1.61

3.5

11.9

2870

3290

3080

2840

2630

2420

2170

1930

1435

1.71

4.0

13.6

3280

3760

3520

3240

3000

2760

2480

2200

1640

1.82

4.5

15.3

3690

4230

3960

3650

3380

3110

2790

2480

1845

1.93

5.0

17.0

4100

4700

4400

4050

3750

3450

3100

2750

2050

2.03

5.5

18.7

4510

5170

4840

4460

4130

3800

3410

3030

2255

2.14

6.0

20.4

4920

5640

5280

4860

4500

4140

3720

3300

2460

2.25

6.5

22.1

5330

6110

5720

5270

4880

4490

4030

3580

2665

2.35

7.0

23.8

5740

6580

6160

5670

5250

4830

4340

3850

2870

2.46

7.5

25.5

6150

7050

6600

6080

5630

5180

4650

4130

3075

2.57

8.0

27.2

6560

7520

7040

6480

6000

5520

4960

4400

3280

2.68

8.5

28.9

6970

7990

7480

6890

6380

5870

5270

4680

3485

2.78

9.0

30.6

7380

8460

7920

7290

6750

6210

5580

4950

3690

2.89

9.5

32.3

7790

8930

8360

7700

7130

6560

5890

5230

3895

3.00

10.0

34.0

8200

9400

8800

8100

7500

6900

6200

5500

4100

3.10

10.5

35.7

8610

9870

9240

8510

7880

7250

6510

5780

4305

3.21

11.0

37.4

9020

10340

9680

8910

8250

7590

6820

6050

4510

3.32

11.5

39.1

9430

10810

10120

9320

8630

7940

7130

6330

4715

3.42

12.0

40.8

9840

11280

10560

9720

9000

8280

7440

6600

4920

3.53

12.5

42.5

10250

11750

11000

10130

9380

8630

7750

6880

5125

3.64

13.0

44.2

10660

12220

11440

15030

9750

8970

8060

7150

5330

3.74

13.5

45.9

11070

12690

11880

10940

10130

9320

8370

7430

5535

3.85

14.0

47.6

11480

13160

12320

11340

10500

9660

8680

7700

5740

3.96

14.5

49.3

11890

13630

12760

11750

10880

10010

8990

7960

5945

4.06

15.0

51.0

12300

14100

13200

12150

11250

10350

9300

8250

6150

4.17

15.5

52.7

12710

14570

13640

12560

11630

10700

9610

8530

6355

4.28

16.0

54.4

13120

15040

14080

12960

12000

11040

9920

8800

6560

4.38

16.5

56.1

13530

15510

14520

13370

12380

11390

10230

9080

6765

4.49

17.0

57.8

13940

15980

14960

13770

12750

11730

10540

9350

6970

4.60

17.5

59.5

14350

16450

15400

14180

13130

12080

10850

9630

7175

4.70

18.0

61.2

14760

16920

15840

14580

13500

12420

11160

9900

7380

4.81

18.5

62.9

15170

17390

16280

14990

13880

12770

11470

10180

7585

4.92

19.0

64.6

15580

17860

16720

15390

14250

13110

11780

10450

7790

5.03

19.5

66.3

15990

18330

17160

15800

14630

13460

12090

10730

7995

5.13

20.0

68.0

16400

18800

17600

16200

15000

13800

12400

11000

8200

5.24

20.5

69.7

16810

19270

18040

16610

15380

14150

12710

11280

8405

5.35

21.0

71.4

17220

19740

18480

17010

15750

14490

13020

11550

8610

5.45

21.5

73.1

17630

20210

18920

17420

16130

14840

13330

11830

8815

5.56

22.0

74.8

18040

20680

19360

17820

16500

15180

13640

12100

9020

5.67

I=B=R Ratings are determined from tests made in accordance with the I=B=R Testing and Rating Code for Baseboard Type of Radiation, including an allowance of 15% for heating effect permitted by the Code.

Ratings based on active length. Active length same as total length.

**The Hot Water Ratings at 2000 lb. Flow Rate are limited to installations where the water flow rate through the Base-Ray is greater than 2000 lbs. per hour (four gallons per minute). Where the water flow rate through the Base-Ray is not known, the rating at the standard flow rate of 500 lbs. per hour must be used.

*Add ½" to length for each bushing. Add 5" to length for each valve enclosure.

***Based on ¾" pipe connections.

9A Base-Ray Water Content - 2.5 lbs. or .3 gal. per linear ft.