Burnham 53A, AL-26A, 79A, 40A manual VI. Service Instructions

Models: 40A 79A AL-26A

1 22
Download 22 pages 45 Kb
Page 17
Image 17
VI. Service Instructions

VI. Service Instructions

A.The Alliance™ is intended to provide a service life of many years. Components that require service, however, may be subject to failure. Failure to use the correct procedures or parts in these circumstances may make the water heater unsafe.

The owner should arrange to have the following inspections and simple maintenance procedures performed by qualified service personnel at the frequencies suggested.

1.Boiler and Domestic Water Piping (Annual) Check all piping for signs of leakage at joints, unions, and shut-off valves. Repair as needed.

2.Temperature-Pressure Relief Valve (Annual) Follow instructions packed with valve.

3.Sediment (Annual, but harsh water quality may dictate more frequent service)

Depending on water conditions, a varying amount of sediment may collect in the tank. Levels requiring service are indicated by a small temperature difference in the supply and return lines. (See also "Scale" below.) Repeated flushing usually clears such material. As a preventive measure, water should be drawn from the tank at the drain valve until it runs clear.

4.Scale (Annual)

Hard water may cause scale to build-up on the outside of the heat exchanger coil. A water softener will prevent this problem. (See also "Sediment" above.) Symptoms would be reduced recovery capacity or reduced temperature differential between boiler supply and return lines. Repeated flushing should resolve the problem. If not, proceed to B.

B. Chemical cleaning of heat exchanger coil

1.To avoid water damage to nearby areas in subsequent steps, shut off the cold water supply to the water heater.

2.Make a note of the temperature control setting on the water heater, then turn the unit off.

3.Relieve the water pressure in the tank by opening a hot water faucet. This will reduce the risk of scald injury.

4.Remove the relief valve from the water heater taking care to avoid contact with the hot water

which may drain out of the lines leading to the domestic uses.

5.Drain the water heater until the water within the tank is even with the top of the heat exchanger coil. The water heater cover plate should be removed from the tank to view the inside of the tank and assure the coil is just covered with water.

6.Using a funnel, pour one gallon of commercial ice maker cleaning solution into the tank through the cover plate opening. Follow solution manufacturer's instructions, cautions and warnings.

7.Set the water heater's temperature control to its highest setting and operate the system until the control is satisfied. Boiler may cycle on its high limit several times during this period. If the tank temperature setting has not been satisfied after 45 minutes of boiler operation, turn aquastat to the lowest setting to stop boiler operation.

8.Allow heated solution to set in tank for 30 minutes.

9.Drain tank completely using fittings and hose, as required, to reach a floor drain.

10.Fill the water heater's tank with fresh, cold, conditioned water and drain completely at least two

(2) times to flush all cleaning solution from the tank.

11.Reinstall the relief valve, cover plate, and piping.

12.Open the cold water supply and fill the tank with water. Then purge air from lines and tank by operating hot and cold water faucets in the house.

13.Return the temperature control to the setting noted in Step 2.

C. Alternate heat exchanger coil cleaning methods

The chemical cleaning process is most effective if done properly. Other methods may also give satisfactory results including, high velocity water wash using a wand through the cover plate.

17

Page 17
Image 17
Burnham 53A, AL-26A, 79A, 40A manual VI. Service Instructions