42
Figure 10.2: Gas Valve Detail
11)Performacombustiontest.Onhorizontallyventedunits,thesampleprobemaybeinsertedintotheterminal.
Ifthisisnotpossible,andifnosampletapispresentintheventsystem,removetheuetemperaturesensor
andinserttheanalyzerprobeinthesensoropening.OntheCHG150andCHG225theuetemperatureprobe
islocatedbehindthelowervestibuledoor.Fortheboilertooperate,thissensorwillneedtobetemporarily
connectedoutsideoftheboiler.Ifitisremoved,besuretoreturntheuegastemperaturesensortoitsoriginal
positionaftercombustiontestingiscomplete.
CheckCO2(orO2)andCOatbothhighandlowre.Theboilermaybetemporarilylockedintohighorlow
refor15minutesasfollows:
a) Tolocktheboilerinhighre,simultaneouslypressandholdthe“Mode”buttonand“+“buttonuntil
thedisplayashes“H”,indicatingthattheboilerhasbeendriventohighre.Afterthishappens,allowthe
boilertooperateforapproximately5minutesbeforetakingcombustionreadings.
b) Tolocktheboilerinlowre,simultaneouslypressandholdthe“Mode”buttonand“-“buttonuntil
thedisplayashes“L”,indicatingthattheboilerhasbeendriventolowre.Afterthishappens,allow
theboilertooperateforapproximately5minutesbeforetakingcombustionreadings.
Atbothhighandlowre,COreadingsshouldbelessthan75PPM.TypicalCO2readingsareshowninTable
10.3.
Normalmodulationoftheboilershouldreturn15minutesaftertheboilerislockedinhighorlowre.
Table 10.3: Typical CO2/O2 Combustion readings rangeModel Fuel %CO2 %O2
CHG150 Natural Gas 8.2 6.3
CHG225 Natural Gas 8.7 5.4
CHG150 Propane NA NA
CHG225 Propane 10.2 5.4
warNINg
EaCh Chg sErIEs bOIlEr Is TEsTED aT ThE faCTOry aND aDJusTmENTs
To THE AIR-FuEL MIxTuRE ARE NoRMALLy NoT NECESSARy. CoNSuLT A
BuRNHAM REPRESENTATIVE BEFoRE ATTEMPTING To MAkE ANy SuCH
aDJusTmENTs. ImPrOPEr gas ValVE Or mIxTurE aDJusTmENTs COulD
RESuLT IN PRoPERTy DAMAGE, PERSoNAL INjuRy, oR LoSS oF LIFE.