warNINg
OUTDOOR COMBUSTION AIR MUST BE PIPED TO THE AIR INTAKE. NEVER PIPE COMBUSTION
AIR FROM AREAS CONTAINING CONTAMINATES SUCH AS SWIMMING POOLS AND LAUNDRY
ROOM EXHAUST VENTS. CONTAMINATED COMBUSTION AIR WILL DAMAGE THE BOILER
ANDMAYCAUSEPROPERTYDAMAGE,PERSONALINJURYORLOSSOFLIFEANDWILLVOID
THEMANUFACTURER’SWARRANTY.
V Air for VentilationAirforcombustionmustalwaysbeobtaineddirectlyfromoutdoors,howeversufcientairforventilationmust
stillbeprovidedintheboilerroom.Airforventilationisrequiredtokeepvariousboilercomponentsfromover-
heatingandisalwaysobtainedfromindoors.Toensureanadequateventilationairsupply,performthefollowing
steps:
Step1:Determinewhethertheboileristobeinstalledinaconnedspace-AconnedspaceisdenedbytheNa-
tional Fuel Gas Codeashavingavolumelessthan50cubicfeetper1000BTU/hrinputofallappliancesinstalled
inthatspace.Todeterminewhethertheboilerroomisaconnedspace:
1) TotaltheinputofallappliancesintheboilerroominthousandsofBTU/hr.Roundtheresulttothenext
highest1000BTU/hr.
2) Findthevolumeoftheroomincubicfeet.Thevolumeoftheroomincubicfeetis:
Length(ft)xwidth(ft)xceilingheight(ft)
Incalculatingthevolumeoftheboilerroom,considerthevolumeofadjoiningspacesonlyifnodoorsare
installedbetweenthem.Ifdoorsareinstalledbetweentheboilerroomandanadjoiningspace,donotconsider
thevolumeoftheadjoiningspace,evenifthedoorisnormallyleftopen.
3) DividethevolumeoftheboilerroombytheinputinthousandsofBTU/hr.Iftheresultislessthan50,the
boilerroomisaconnedspace.
Example:
A CHG225 and a water heater are to be installed in a room measuring 6ft – 3 in x 7ft with an 8 ft ceiling. The
water heater has an input of 30000 BTU/hr:
Total input in thousands of BTU/hr = (225000 BTU/hr + 30000 BTU/hr) / 1000 = 255 MBTU/hr
Volume of room = 6.25 ft x 7 ft x 8 ft = 350 ft3
350/255 = 1.37. Since 1.37 is less than 50, the boiler room is a conned space.
Step2a:Iftheboileristobeplacedinaconnedspace,providetwoopeningsintotheboilerroom,onenearthe
oorandoneneartheceiling.Thetopedgeoftheupperopeningmustbewithin12”oftheceilingandthebottom
edgeoftheloweropeningmustbewithin12”oftheoor(Fig5.1).Theminimumopeningdimensionis3inches.
• IftheCHGboileristheonlygas-burningapplianceintheboilerroom,theseopeningsmusteachhavea
minimumfreeareaof100squareinches.
• Ifothergas-burningappliancesareintheboilerroom,sizetheopeningsinaccordancewiththeappliance
manufacturer’sinstructionsortheNational Fuel Gas Code.Minimumopeningfreeareais100square
inchesevenifopeningrequirementsforotherappliancesareless.
• Ifthetotalvolumeofboththeboilerroomandtheroomtowhichtheopeningsconnectislessthan50
cubicfeetper1000BTU/hroftotalapplianceinput,installapairofidenticalopeningsintoathirdroom.
Connectadditionalroomswithopeningsuntilthetotalvolumeofallroomsisatleast50cubicfeetper
1000BTU/hrofinput.
• The“freearea”ofanopeningtakesintoaccounttheblockingeffectofmesh,grills,andlouvers.Where
screensareused,theymustbenonerthan¼”(4x4)mesh.