Outdoor units may be connected to indoor section using accessory tubing package or
There are no
If refrigerant tubes or indoor coil are exposed to atmosphere, they must be evacuated to 500 microns to eliminate contamination and moisture in the system.
Outdoor Unit Connected to Factory-Approved Indoor Unit
Outdoor unit contains correct system refrigerant charge for operation with approved ARI rated indoor unit when connected by 15 ft. of
Refrigerant Tubing and Sweat Connections
Connect vapor tube to fitting on outdoor unit vapor service valves (see Table 2). Connect liquid tubing to adapter tube on liquid service valve. Use refrigerant grade tubing.
!CAUTION
UNIT DAMAGE HAZARD
Failure to follow this caution may result in equipment damage or improper operation.
Service valves must be wrapped in a
Remove plastic retainer holding outdoor piston in liquid service valve, leaving the piston and piston retainer inside the valve. Connect sweat/flare adapter provided, to valve. (See Fig. 6.) Connect refrigerant tubing to fittings on outdoor unit vapor and liquid service valves. Service valves are closed from factory and ready for brazing. After wrapping service valve with a wet cloth, tubing set can be brazed to service valve using either silver bearing or
PISTON BODY
PISTON
PISTON
RETAINER
SWEAT/FLARE ADAPTER
A05226
Fig. 6 --- Liquid Service Valve
25HCR
| Table |
| |
|
|
| |
| REQUIRED FOR | REQUIRED FOR LONG LINE APPLICA- | |
Accessory | PLICATIONS | ||
TIONS* (Over 80 ft.) | |||
| (Below 55 °F) | ||
|
| ||
Crankcase Heater | Yes | Yes | |
Evaporator Freeze Thermostat | Yes | No | |
Winter Start Control | Yes | No | |
Accumulator | No | No | |
Compressor Start Assist Capacitor and Relay | Yes | Yes | |
Support Feet | Recommended | No | |
Liquid Line Solenoid Valve | No | See |
*For Tubing Set lengths between 80 and 200 ft. horizontal or 20 ft. vertical differential (250 ft. Total Equivalent Length), refer to the Long Line Guidelines for Air Conditioners and Heat Pumps using
Table
|
|
|
|
|
|
UNIT SIZE | LIQUID |
| VAPOR (up to 80 ft.*) | ||
Connection Diameter |
| Tube | Connection Diameter | Rated Tube Diameter | |
|
| Diameter | |||
|
|
|
|
| |
018, 024 | 3/8 |
| 3/8 | 5/8 | 5/8 |
030, 036 | 3/8 |
| 3/8 | 3/4 | 3/4 |
042, 048 | 3/8 |
| 3/8 | 7/8 | 7/8 |
060 | 3/8 |
| 3/8 | 7/8 |
Notes:
1.Tube diameters are for total equivalent lengths up to 80 ft..
2.Do not apply capillary tube or fixed orifice indoor coils to these units.
*For Tubing Set lengths between 80 and 200 ft. horizontal or 20 ft. vertical differential (250 ft.Total Equivalent Length), refer to the Longline Guideline
5