Carrier 25HCR INSTALLATION -Check Equipment and Job Site Unpack Unit, Inspect Equipment

Models: 25HCR

1 10
Download 10 pages 60.41 Kb
Page 3
Image 3
INSTALLATION

INSTALLATION

STEP 1 Check Equipment and Job Site

Unpack Unit

Move to final location. Remove carton taking care not to damage unit.

Inspect Equipment

File claim with shipping company prior to installation if shipment is damaged or incomplete. Locate unit rating plate on unit corner panel. It contains information needed to properly install unit. Check rating plate to be sure unit matches job specifications.

STEP 2 Install on a Solid, Level Mounting Pad

If conditions or local codes require the unit be attached to pad, tie down bolts should be used and fastened through knockouts provided in unit base pan. Refer to unit mounting pattern in Fig. 3 to determine base pan size and knockout hole location.

For hurricane tie downs, contact distributor for details and PE Certification (Professional Engineer), if required.

On rooftop applications, mount on level platform or frame. Place unit above a load-bearing wall and isolate unit and tubing set from structure. Arrange supporting members to adequately support unit and minimize transmission of vibration to building. Consult local codes governing rooftop applications.

Roof mounted units exposed to winds above 5 mph may require wind baffles. Consult the Service Manual - Residential Split System Air Conditioners and Heat Pumps for wind baffle construction.

NOTE: Unit must be level to within ±2° (±3/8 in./ft.) per compressor manufacturer specifications.

STEP 3 Clearance Requirements

When installing, allow sufficient space for airflow clearance, wiring, refrigerant piping, and service. Allow 30-in. clearance to service end of unit and 48 in. above unit. For proper airflow, a 6-in. clearance on 1 side of unit and 12 in. on all remaining sides must be maintained. Maintain a distance of 24 in. between units. Position so water, snow, or ice from roof or eaves cannot fall directly on unit.

3/8 ---in. Dia. Tiedown

Knockouts in Basepan

(2) Places

 

 

View From Top

 

 

 

 

 

UNIT BASE PAN

TIEDOWN KNOCKOUT LOCATIONS

DIMENSIONS

A

B

C

 

 

 

 

26 X 26

9–1/8

4–7/16

21–1/4

 

 

 

 

31–1/2 X 31–1/2

9–1/8

6–9/16

24–11/16

35 X 35

9–1/8

6–9/16

28–7/16

 

 

 

 

A05177

Fig. 3 ---Clearance Requirements

On rooftop applications, locate unit at least 6 in. above roof surface.

STEP 4 Operating Ambient

The minimum outdoor operating ambient in cooling mode is 55°F, and the maximum outdoor operating ambient in cooling mode is 125°F. The maximum outdoor operating ambient in heating mode is 66 °F.

STEP 5 Install TXV

NOTE: Applies to non-TXVindoor units only. If installing a rated and approved indoor coil without a factory installed R-22 TXV, remove and replace the fixed orifice or PuronR TXV expansion device with an R-22 TXV.

!CAUTION

UNIT OPERATION HAZARD

Failure to follow this caution may result in equipment damage or improper operation.

All indoor coil units must be installed with a hard shut off R-22 TXV metering device.

IMPORTANT: If not factory installed, the TXV should be mounted as close to the indoor coil as possible and in a vertical, upright position. Avoid mounting the inlet tube vertically down. Valve is more susceptible to malfunction due to debris if inlet tube is facing down. A factory-approved filter drier must be installed in the liquid line.

Installing TXV in Place of Piston

1.Pump system down to 2 psig and recover refrigerant.

2.Remove hex nut from piston body. Use backup wrench on fan coils.

3.Remove and discard factory-installed piston. Be sure Teflon seal is in place.

4.Reinstall hex nut. Finger tighten nut plus 1/2 turn. NOTE: If the piston is not removed from the body, TXV will not function properly.

!CAUTION

EQUIPMENT DAMAGE HAZARD

Failure to follow this caution may result in equipment damage or improper operation.

Use a brazing shield and wrap TXV with wet cloth or use heat sink material.

5.Install TXV on indoor coil liquid line. Sweat swivel adapter to inlet of indoor coil and attach to TXV outlet. Use backup wrench to avoid damage to tubing or valve. Sweat inlet of TXV, marked “IN” to liquid line. Avoid excessive heat which could damage valve.

6.Install vapor elbow with equalizer adapter to suction tube of line set and suction connection to indoor coil. Adapter has a 1/4-in. male connector for attaching equalizer tube.

7.Connect equalizer tube of TXV to 1/4-in. equalizer fitting on vapor line adapter.

8.Attach TXV bulb to horizontal section of suction line using clamps provided. Insulate bulb with field-supplied insulation tape. See Fig. 4 for correct positioning of sensing bulb.

9.Proceed with remainder of unit installation.

25HCR

3

Page 3
Image 3
Carrier 25HCR INSTALLATION -Check Equipment and Job Site Unpack Unit, Inspect Equipment, Clearance Requirements