10 O'CLOCK |
2 O'CLOCK |
STRAP |
SUCTION TUBE
8 O'CLOCK
7⁄8 IN. OD & SMALLER
SENSING BULB
4O'CLOCK
LARGER THAN 7⁄8 IN. OD
STEP 6 —Check Defrost Thermostat
Check defrost thermostat to ensure it is properly located and securely attached. There is a liquid header with a brass distributor and feeder tube going into outdoor coil. At the end of the one of the feeder tubes, there is a 3/8 in. O.D. stub tube approximately 2 in. long. (See Fig. 5.) The defrost thermostat should be located on stub tube. Note that there is only one stub tube used with liquid header, and on most units it is the bottom circuit.
FEEDER TUBE
STUB TUBE
25HCR
A81032
Fig. 4 --- Position of Sensing Bulb
Replacing TXV on Puron Indoor Coil
1.Pump system down to 2 psig and recover refrigerant.
2.Remove coil access panel and fitting panel from front of cabinet.
3.Remove TXV support clamp using a
4.Remove Puron TXV using a backup wrench on flare connections to prevent damage to tubing.
5.Using wire cutters, cut equalizer tube off flush with vapor tube inside cabinet.
6.Remove bulb from vapor tube inside cabinet.
7.Braze equalizer
IMPORTANT: Route the equalizer tube of
8.Install TXV with
9.Reinstall TXV support clamp (removed in item 3).
10.Attach TXV bulb to vapor tube inside cabinet, in same location as original was when removed, using supplied bulb clamps (nylon or copper). See Fig. 4 for correct positioning of sensing bulb.
11.Route equalizer tube through suction connection opening (large hole) in fitting panel and install fitting panel in place.
12.Sweat inlet of TXV, marked IN to liquid line. Avoid excessive heat which could damage valve.
13.Install vapor elbow with equalizer adapter to vapor line of line set and vapor connection to indoor coil. Adapter has a
14.Connect equalizer tube of TXV to
15.Proceed with remainder of unit installation.
DEFROST
THERMOSTAT
A97517
Fig. 5 --- Defrost Thermostat Location
STEP 7 —Make Piping Connections
!WARNING
PERSONAL INJURY AND ENVIRONMENTAL HAZARD
Failure to follow this warning could result in personal injury or death.
Relieve pressure and recover all refrigerant before system repair or final unit disposal. Use all service ports and open all
!CAUTION
UNIT DAMAGE HAZARD
Failure to follow this caution may result in equipment damage or improper operation.
If ANY refrigerant tubing is buried, provide a
!CAUTION
UNIT DAMAGE HAZARD
Failure to follow this caution may result in equipment damage or improper operation.
To prevent damage to unit or service valves, observe the following:
S Use a brazing shield
S Wrap service valves with wet cloth or use a heat sink material.
4