30RA/30RH
Refrigerant charge and electronic control
Undercharge
If there is not enough refrigerant in the system, this is indicated by gas bubbles in the moisture sight glass.
There are two possibilities:
•Small undercharge (bubbles in the sight glass, no significant change in suction pressure).
-After detection and repair the unit can be recharged.
-The replenishment of the charge must always be done in the cooling mode, slowly introducing liquid refrigerant at the suction side, until there are no bubbles in the sight glass.
•Significant undercharge (large bubbles in the sight glass, significant drop in suction pressure).
-Completely drain the refrigerant charge, using a refrigerant recovery unit. After detection and repair check the charge with the unit off, drain the system and recharge the full amount of liquid refrigerant (see Table I) on the suction and discharge side.
-The refrigerant container used must contain a minimum of 10% of its initial charge.
WARNING:
If brazing is to be done, the refrigerant circuit must be filled with nitrogen.
Combustion of refrigerant produces toxic phosgene gas.
IMPORTANT:
-Never use the compressor as a vacuum pump.
-Always add refrigerant via the suction line.
-Refrigerant must be added very slowly.
-The complete refrigerant charge must never be filled into the suction line.
-Do not overcharge the system with refrigerant.
Electronic control
Operation and control of all units is carried out via the electronic control.
The instructions supplied with the control include comprehensive descriptions.
PRO-Dialog Plus electronic control
It also controls the operation of the water pump.
A powerful control system
The PID control algorithm with permanent compensation for the difference between entering and leaving water temperature and anticipation of load variations regulates compressor operation for intelligent leaving water temperature control.
To optimise power absorption, the
Clear and easy-to-use control system
The operator interface is clear and
10 menus offer direct access to all machine controls, including a history of possible faults, for rapid and complete chiller fault diagnosis.
Extended communications capabilities
The system permits remote signalling of any general anomaly for each refrigerant circuit.
Three independent time schedules permit definition of: chiller start/stop, operation at the second
GB - 10