30RA/30RH
Water connections
E N G L I S H
Ethylene glycol curve
°C |
| |
ATTENTION: | ||
mixture | ||
The pump leakproof | ||
components are not suitable | ||
for use with propylene | ||
glycol. | ||
| ||
| ||
|
| |
Weight concentration of ethylene glycol in water % | CAUTION: | |
| Using water with glycol may | |
| make it necessary to change the | |
| configuration of the control | |
| system. | |
|
|
Make the plate heat exchanger hydraulic connections with the necessary components, using material which will guarantee that the screwed joints are leakproof.
The typical hydraulic circuit diagram shows a typical water circuit installation in an air conditioning system.
For an application with a water circuit, the following recommendations must be taken into account:
1.The pump must be fitted immediately before of the heat exchanger and after the connection to the system return (unit without hydronic module).
2.It is advisable to install
These valves (ball, globe or butterfly valves) should produce a minimum loss of charge when they are open.
3.Provide unit and system drains and vents at the lowest system point.
4.Install purges in the higher sections of the installation.
5.Pressure ports and pressure gauges should be installed upstream and downstream of the water pump (unit without hydronic module).
6.Thermometers should be installed in the unit water inlet and outlet.
7.All piping must be adequately insulated and supported.
Installation of the following components is obligatory:
1.A flow switch should be installed in a straight horizontal stretch with a length of at least five times the line diameter on either side.
The flow switch must be positioned in the exchanger inlet pipe. It must be electrically connected in accordance with the wiring diagram (only unit without hydronic module).
If this is not possible, the installation should incorporate a protection device which is activated when there is no water circulating in the heat exchanger.
2.The presence of particles in the water can lead to obstructions in the heat exchanger.
It is therefore necessary to protect the heat exchanger inlet with an extractable mesh filter.
The filter mesh gauge must be at least 10 mesh/cm2.
The standard supply of the unit with hydronic module includes a mesh filter to be fitted during installation.
3.After assembling the system, or repairing the circuit, the whole system must be thoroughly cleaned with special attention paid to the state of the filters.
4.Pump flow rate control is made through a flow control valve supplied with the unit with hydronic module, which must be installed on the delivery pipe during installation.
5.In case of water refrigeration at temperatures lower than 5° C, or
if the unit is installed in areas where temperatures drop below 0° C, water must be mixed with a proper quantity of ethylene glycol (see the curve above).
Use the curve to determine the correct ethylene glycol concentration for the temperature.
Frost protection
The plate heat exchanger and the water connections of the hydronic module pump may be damaged in spite of the
Frost protection of the plate heat exchanger and of the circuit inside the hydronic module is always guaranteed down to
IMPORTANT:
Both the appliance main switch (Q1) and the auxiliary protection switch for the electric heaters (QF101) must always be in the closed position (the positions of Q1 and QF101 are indicated in the wiring diagram).
GB - 7