30RH
Physical data and electrical data - Model RH
E N G L I S H
Table I: Physical data - Model RH
30RH |
| 017 | 021 | 026 | 033 |
Net cooling capacity* | kW | 16.70 | 21.60 | 24.60 | 29.00 |
|
|
|
|
|
|
Net heating capacity** | kW | 18.80 | 24.80 | 27.80 | 34.00 |
|
|
|
|
|
|
Operating weight |
|
|
|
|
|
without hydronic module | kg | 235 | 265 | 285 | 315 |
with hydronic module | kg | 255 | 285 | 315 | 345 |
Refrigerant charge | kg | 7.15 | 7.84 | 9.30 | 11.00 |
|
|
|
|
|
|
Compressor |
| One scroll compressor |
|
|
|
|
|
|
|
|
|
Control system |
| Pro |
|
|
|
|
|
|
|
| |
| One plate heat exchanger |
|
| ||
Net water volume | l | 1.50 | 1.88 | 2.16 | 2.82 |
Water connections (MPT gas) | inches | 1 | 1 | ||
Maximum water pressure | kPa | 1000 | 1000 | 1000 | 1000 |
(unit without hydronic module) |
|
|
|
|
|
|
| ||||
Hydronic module | Pump, mesh filter, expansion tank, flow switch, pressure gauges, automatic air purge valve and drain plug, | ||||
| flow control valve and safety valve. |
|
|
| |
Pump |
| One |
|
| |
Available pressure*** | kPa | 142 | 125 | 155 | 149 |
Water inlet connection (MPT gas) | inches | ||||
Water outlet connection (MPT gas) | inches | 1 | 1 | ||
Drain tap coupling (MPT gas) | inches | 1/2 | 1/2 | 1/2 | 1/2 |
Closed expansion tank water volume | l | 8 | 8 | 8 | 8 |
|
|
|
|
|
|
Water fill system (option) |
|
|
|
|
|
Inlet/outlet diameter (MPT gas) | inches | 1/2 | 1/2 | 1/2 | 1/2 |
|
|
|
|
| |
| One, copper tubes and aluminium fins |
|
| ||
Tube diameter | inches | 3/8 | 3/8 | 3/8 | 3/8 |
No. of rows |
| 3 | 2 | 3 | 4 |
Tubes/row |
| 52 | 60 | 60 | 60 |
Fin spacing | mm | 1.81 | 1.81 | 1.81 | 1.81 |
Fan |
| Two, axial type with two speeds |
|
| |
Diameter | mm | 500 | 610 | 610 | 610 |
No. of blades |
| 5 | 5 | 5 | 5 |
Air flow (high speed) | l/s | 2222 | 3611 | 3111 | 3333 |
Fan speed (high speed) | r/s | 12.83 | 10.83 | 11.67 | 11.83 |
|
|
|
|
|
|
**The ratings indicated refer to an evaporator entering/leaving temperature of 12/7 ° C,and air entering the condenser at 35 ° C.
**The ratings indicated refer to a condenser entering/leaving temperature of 40/45 ° C,and air entering the condenser at 7 ° C d.b.and 6 ° C w.b.
***At nominal water flow rate during cooling.
Table II: Electrical data - Model RH
30RH |
| 017 | 021 | 026 | 033 |
|
|
|
|
|
|
Power supply |
|
|
| ||
Voltage range | V |
|
|
| |
Nominal power input* | kW | 6.21 | 7.95 | 9.13 | 11.83 |
Effective power input** | kW | 6.30 | 8.10 | 9.30 | 12.00 |
Nominal current drawn* | A | 10.75 | 14.80 | 18.70 | 23.65 |
Effective current drawn** | A | 10.90 | 15.05 | 19.05 | 24.00 |
Maximum power drawn*** | kW | 7.87 | 10.8 | 12.23 | 14.95 |
Maximum current drawn*** | A | 13.50 | 20.00 | 22.50 | 28.00 |
Starting current | A | 87 | 132 | 134 | 139 |
Pump power input | kW | 0.65 | 0.68 | 0.89 | 0.93 |
|
|
|
|
|
|
*Based on an outdoor entering air temperature of 35 ° C db, an evaporator entering water temperature of 12 ° C and an evaporator leaving water temperature of 7 ° C, unit without hydronic module
**The power and current values indicated refer to Eurovent Standard conditions.
***The power and current values indicated refer to an evaporator leaving water temperature of 10 ° C and a condenser entering air temperature of 46 ° C.
GB - 3