Carrier 30XA080-500 specifications A30-4415, PT Hydronic Pump Package

Models: 30XA080-500

1 80
Download 80 pages 61.28 Kb
Page 51
Image 51

INSIDE

UNIT

OUTSIDE

UNIT

LEGEND

DDrain,3/4-in. NPT DDrain, 1/4-in. NPT

EExpansion Tank Connection, 3/4-in. NPT FS — Flow Switch

PPPipe Plug, 1/4-in. NPT

PT — Pressure/Temperature Tap T1 — Leaving Water Thermistor T2 — Entering Water Thermistor

VVent, 1/4-in. NPT

*Field-supplied and installed. †Factory-installed option. **Required for open loop systems.

a30-4415

D

V

T1

PP

 

 

 

 

 

Heater

 

 

 

 

 

FS PP

T2

Chilled Water Out

PT HYDRONIC PUMP PACKAGE

D

PT

 

 

D

PT

 

PT

E

PT

 

 

 

D

 

 

Heater

Chilled

Water In

Pressure Relief*

Flexible Connections*

Pressure Reducing

Fill Valve*

Air Separator with Vent*

Strainer/Suction Guide

Reverse Flow Check Valve/Service Valve

Service Valve

Pump

Combination Valve

Isolation Valve*

20 Mesh Stainer**

Fig. 26 — Typical Piping Diagram on 30XA Units with Hydronic Package — Dual Pumps

NOTE: It is recommended for units with the hydronic package that an inlet isolation (shut-off) valve be placed exterior to the unit to allow removal and service of the entire pump assembly, if necessary. The hydronic package is supplied from the factory with a combination valve for isolation of leaving water. Also, if the unit is isolated with valves, a properly sized pressure relief valve is recommended and should be installed in the pip- ing between the unit and the valves, following all applicable local codes.

Air Separation — For proper system operation, it is essential that water loops be installed with proper means to manage air in the system. Free air in the system can cause noise, reduce terminal output, stop flow, or even cause pump failure due to pump cavitation. For closed systems, equipment should be provided to eliminate all air from the system.

The amount of air that water can hold in solution depends on the pressure and temperature of the water/air mixture. Air is less soluble at higher temperatures and at lower pressures. Therefore, separation can best be done at the point of highest water temperature and lowest pressure. Typically, this point would be on the suction side of the pump as the water is return- ing from the system or terminals. This is generally the optimal place to install an air separator, if possible.

1.Install automatic air vents at all high points in the system. (If the 30XA unit is located at the high point of the sys-

51

tem, a vent can be installed on the piping leaving the heat exchanger on the 1/4 in. NPT female port.)

2.Install an air separator in the water loop, at the place where the water is at higher temperatures and lower pres- sures — usually in the chilled water return piping. On a primary-secondary system, the highest temperature water is normally in the secondary loop, close to the decoupler. Preference should be given to that point on the system (see Fig. 27). In-line or centrifugal air separators are read- ily available in the field.

It may not be possible to install air separators at the place of the highest temperature and lowest pressure. In such cases, preference should be given to the points of highest temperature. It is important that the pipe be sized correctly so that free air can be moved to the point of separation. Generally, a water velocity of at least 2 feet per second (0.6 m per second) will keep free air entrained and prevent it from forming air pockets.

Automatic vents should be installed at all physically elevated points in the system so that air can be eliminated during system operation. Provisions should also be made for manual venting during the water loop fill.

UNITS WITH HYDRONIC PUMP PACKAGE — The 30XA090-160 units can be equipped with a factory-installed hydronic pump package consisting of a suction guide/strainer, pump, combination valve, internal piping and wiring con- nected at the factory.

Page 51
Image 51
Carrier 30XA080-500 specifications A30-4415, PT Hydronic Pump Package

30XA080-500 specifications

The Carrier 30XA080-500 is a sophisticated air-cooled chiller designed for large commercial and industrial applications, renowned for its energy efficiency and reliability. This model is part of Carrier's extensive range of chillers, providing an optimal solution for space cooling needs while supporting sustainability goals.

One of the main features of the 30XA080-500 is its advanced scroll compressor technology. This design not only enhances the chiller's efficiency but also ensures quieter operation. The compressors operate with a high efficiency at partial loads, making the 30XA080-500 ideal for buildings with varying cooling demands. The unit also incorporates multiple compressors, allowing for enhanced reliability through redundancy; if one compressor fails, others can maintain performance.

The 30XA080-500 is equipped with high-performance evaporators and condensers which facilitate superior heat exchange. The unit features a fin-and-tube heat exchanger design, optimized for maximum surface area and minimal air resistance, thus enhancing overall performance. Moreover, the chiller is built with microchannel technology, which significantly reduces the refrigerant charge while improving efficiency through better heat transfer.

In terms of controls, the Carrier 30XA080-500 utilizes advanced VFD (Variable Frequency Drive) technology. This allows the system to adjust motor speed to match building loads, further increasing efficiency and reducing energy consumption. The intuitive control options enable users to monitor performance and make adjustments easily, helping optimize system operations in real time.

Another highlight of the 30XA080-500 is its environmentally conscious refrigerant, R-410A, which is known for its low Global Warming Potential (GWP). This makes the unit compliant with current and future environmental regulations, ensuring that users can operate within legal limits while reducing their carbon footprint.

The durability of the 30XA080-500 is enhanced by a rugged construction designed to withstand various weather conditions, making it suitable for outdoor installation. Insulated panels and protective coatings guard against corrosion, extending the lifespan of components and reducing maintenance costs.

In conclusion, the Carrier 30XA080-500 is a high-efficiency chiller that offers advanced technology, reliable performance, and environmental consciousness, making it an excellent choice for modern commercial buildings seeking to balance cooling needs with sustainability and energy savings. Its combination of innovative features positions it as a leader in the chiller market.