Carrier 38YRA instruction manual Safety Considerations, Installation

Models: 38YRA

1 8
Download 8 pages 50.8 Kb
Page 1
Image 1

38YRA Heat PumpÐOutdoor Section

Installation and Start-Up Instructions

NOTE: Read the entire instruction manual before starting the installation.

This symbol indicates a change since last issue.

SAFETY CONSIDERATIONS

Improper installation, adjustment, alteration, service, maintenance, or use can cause explosion, fire, electrical shock, or other conditions which may cause personal injury or property damage. Consult a qualified installer, service agency, or your distributor or branch for information or assistance. The qualified installer or agency must use factory-authorized kits or accessories when modifying this product. Refer to the individual instructions pack- aged with the kits or accessories when installing.

Follow all safety codes. Wear safety glasses and work gloves. Use quenching cloth for brazing operations. Have fire extinguisher available. Read these instructions thoroughly and follow all warnings or cautions attached to the unit. Consult local building codes and the National Electrical Code (NEC) for special instal- lation requirements.

Recognize safety information. This is the safety-alert symbol . When you see this symbol on the unit or in instructions and manuals, be alert to the potential for personal injury.

Understand the signal word DANGER, WARNING, or CAU- TION. These words are used with the safety-alert symbol. DAN- GER identifies the most serious hazards which will result in severe personal injury or death. WARNING signifies hazards which could result in personal injury or death. CAUTION is used to identify unsafe practices which would result in minor personal injury or product and property damage.

Before installing or servicing system, always turn off main power to system. There may be more than 1 disconnect switch. Turn off accessory heater power if applicable. Elec- trical shock can cause personal injury or death.

INSTALLATION

Step 1ÐCheck Equipment and Jobsite

UNPACK UNIT Ð Move to final location. Remove carton taking care not to damage unit.

INSPECT EQUIPMENT Ð File claim with shipping company, prior to installation, if shipment is damaged or incomplete. Locate unit rating plate on unit corner panel. (See Fig. 2.) It contains information needed to properly install unit. Check rating plate to be sure unit matches job specifications.

Step 2ÐInstall on a Solid, Level Mounting Pad

If conditions or local codes require the unit be attached to pad, tie-down bolts should be used and fastened through knockouts provided in unit base pan. Refer to unit mounting pattern in Fig. 2 to determine base pan size and knockout hole location.

When installing, allow sufficient space for airflow clearance, wiring, refrigerant piping, and service. Allow 30-in. clearance to service end of unit and 48 in. above unit. For proper airflow, a 6-in.

A92446

Fig. 1ÐModel 38YRA

clearance on 1 side of unit and 12 in. on all remaining sides must be maintained. Maintain a distance of 24 in. between units. Position so snow, ice, and water from roof or eaves cannot fall directly on unit.

On rooftop applications, locate unit at least 6 in. above roof surface. Place unit above a load-bearing wall and isolate unit and tubing set from structure.

Arrange supporting members to adequately support unit and minimize transmission of vibration to building. Consult local codes governing rooftop applications.

Step 3ÐElevate Unit

For proper drainage the heat pump must be raised off the mounting surface. Fig. 4 shows unit with accessory support feet installed. Use accessory heat pump snow rack in areas where prolonged subfreezing temperatures or heavy snow occur. Refer to separate Installation Instructions packaged with the accessories.

For proper unit operation and reliability, this unit must be installed with the field-supplied balance port, hard shut-off TXV. Do not install with evaporator coils having capillary tube metering devices.

Step 4ÐRemove Indoor AccuRater® Piston and Install

TXV

After removing existing AccuRater from indoor coil, install field-supplied bi-flow hard shut-off TXV kit. (See Fig. 5 and 6.) For TXV kit part number and charging instruction, refer to TXV label in your unit. If the indoor unit (fan coil) comes factory- equipped with a bi-flow hard shut-off TXV, no TXV change is required.

Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.

Book

1

4

PC 101

Catalog No. 533-890

Printed in U.S.A.

Form 38YRA-2SI

Pg 1

8-95

Replaces: 38YRA-1SI