Table 10 — Electric Heater Data

UNIT

HEATER

NO. OF

HEATER

NOMINAL

TEMP

 

208/3/60 VOLTS

 

240/3/60 VOLTS

 

480/3/60 VOLTS

 

 

380/3/50 VOLTS

 

COIL FACE

Total

 

No.

 

Total

 

No.

 

Total

 

No.

 

 

Total

 

No.

 

 

SIZE

AREA

CONTROL

COIL

VELOCITY

RISE

MCA†

Sub-

MOCP

MCA†

Sub-

MOCP

MCA†

Sub-

 

MOCP

MCA†

Sub-

 

MOCP

39L

(sq ft)

STEPS*

kW

(F)

FLA

FLA

FLA

 

FLA

 

(fpm)

 

 

 

 

 

 

 

 

 

Ckt

 

 

 

Ckt

 

 

 

Ckt

 

 

 

 

Ckt

 

 

 

 

 

9

500

26

25

31

1

35

22

27

1

30

11

14

1

 

20

14

17

1

 

20

03

2.2

3

15

500

44

42

52

1

60

36

45

1

50

18

23

1

 

25

23

29

1

 

30

 

 

 

17.2

500

50

48

60

1

60

41

52

1

60

21

26

1

 

30

26

33

1

 

35

 

 

 

8

500

14

22

28

1

30

19

24

1

25

10

12

1

 

20

12

15

1

 

20

 

 

 

10

500

17

28

35

1

35

24

30

1

35

12

15

1

 

20

15

19

1

 

20

 

 

 

17

500

29

47

59

1

60

41

51

1

60

20

26

1

 

30

26

32

1

 

35

06

3.7

6

19.9

500

34

55

69

2

70

48

60

1

60

24

30

1

 

30

30

38

1

 

40

 

 

 

27

500

47

75

94

2

100

65

81

2

90

33

41

1

 

45

41

51

1

 

60

 

 

 

29.8

500

51

83

104

2

110

72

90

2

90

36

45

1**

 

45

45

57

1

 

60

 

 

 

36

500

62

100

125

3††

150

87

108

2

110

43

54

1**

 

60

55

68

2**

 

70

 

 

 

15

500

19

42

52

1

60

36

45

1

50

18

23

1

 

25

23

29

1

 

30

 

 

 

25

500

31

69

87

2

90

60

75

2

80

30

38

1

 

40

38

48

1

 

50

08

5.1

6

35

500

44

97

122

3

125

84

105

2

110

42

53

1

 

60

53

67

2

 

70

39.9

500

50

111

139

3

150

96

120

3

125

48

60

2

 

70

61

76

2

 

80

 

 

 

 

 

 

 

 

43.2

500

54

120

150

3

175

104

130

3

150

52

65

2

 

70

66

82

2

 

90

 

 

 

51

500

64

142

177

3

200

123

154

3

175

61

77

2

 

80

78

97

2

 

100

 

 

 

15

500

15

42

52

1

60

36

45

1

50

18

23

1

 

25

23

29

1

 

30

 

 

 

25

500

26

69

87

2

90

60

75

2

80

30

38

1

 

40

38

48

1

 

50

10

6.2

6

39.9

500

41

111

139

3

150

96

120

3

125

48

60

2

 

70

61

76

2

 

80

47.3

500

49

131

164

3

175

114

142

3

150

57

71

2

 

80

72

90

2

 

90

 

 

 

 

 

 

 

 

51.8

500

53

144

180

3

200

125

156

3

175

62

78

2

 

80

79

98

2

 

100

 

 

 

59.8

500

62

72

90

2

 

100

91

114

2

 

125

 

 

 

19.9

500

17

55

69

2

70

48

60

1

60

24

30

1

 

30

30

38

1

 

40

 

 

 

29.8

500

26

83

104

2

110

72

90

2

90

36

45

1

 

45

45

57

1

 

60

12

7.3

6

39.9

500

35

111

139

3

150

96

120

3

125

48

60

2

 

70

61

76

2

 

80

43

500

38

119

149

3

150

104

129

3

150

52

65

2

 

70

65

82

2

 

90

 

 

 

 

 

 

 

 

51.8

500

45

144

180

3

200

125

156

3

175

62

78

2

 

80

79

98

2

 

100

 

 

 

72

500

63

87

108

2

 

110

110

137

3††

 

150

 

 

 

19.9

500

13

55

69

2

70

48

60

1

60

24

30

1

 

30

30

38

1

 

40

 

 

 

29.8

500

19

83

104

2

110

72

90

2

90

36

45

1

 

45

45

57

1

 

60

 

 

 

39.9

500

25

111

139

3

150

96

120

3

125

48

60

2

 

70

61

76

2

 

80

15

10.0

6

45

500

29

125

156

3

175

108

135

3

150

54

68

2

 

70

68

86

2

 

90

 

 

 

51.8

500

33

144

180

3

200

125

156

3

175

62

78

2

 

80

79

98

2

 

100

 

 

 

65

500

42

78

98

2

 

100

99

124

3

 

125

 

 

 

86

500

55

104

129

3

 

150

131

164

3

 

175

 

 

 

19.9

500

11

55

69

2

70

48

60

1

60

24

30

1

 

30

30

38

1

 

40

 

 

 

25.8

500

14

72

90

2

90

62

78

2

80

31

39

1

 

40

39

49

1

 

50

 

 

 

35

500

19

97

122

3

125

84

105

2

110

42

53

1

 

60

53

67

2

 

70

18

11.74

6

45

500

25

125

156

3

175

108

135

3

150

54

68

2

 

70

68

86

2

 

90

 

 

 

51.8

500

28

144

180

3

200

125

156

3

175

62

78

2

 

80

79

98

2

 

100

 

 

 

78

500

43

94

117

2

 

125

119

148

3

 

150

 

 

 

94

500

51

113

141

3

 

150

143

179

3

 

200

 

 

 

19.9

500

9

55

69

2

70

48

60

1

60

24

30

1

 

30

30

38

1

 

40

 

 

 

25.8

500

12

72

90

2

90

62

78

2

80

31

39

1

 

40

39

49

1

 

50

 

 

 

35

500

16

97

122

3

125

84

105

2

110

42

53

1

 

60

53

67

2

 

70

21

14.21

6

45

500

20

125

156

3

175

108

135

3

150

54

68

2

 

70

68

86

2

 

90

51.8

500

23

144

180

3

200

125

156

3

175

62

78

2

 

80

79

98

2

 

100

 

 

 

 

 

 

 

 

79.8

500

36

96

120

3

 

125

121

152

3

 

175

 

 

 

92

500

41

111

138

3

 

150

140

175

3

 

175

 

 

 

116

500

52

140

175

3

 

175

 

 

 

 

30

500

11

83

104

2

110

72

90

2

100

36

45

1

 

50

46

57

1

 

60

 

 

 

39.9

500

14

111

139

3

150

96

120

3

125

48

60

2

 

70

61

76

2

 

80

 

 

 

50

500

18

139

174

3

175

120

151

3

175

60

75

2

 

80

76

95

2

 

100

25

17.79

6

65

500

23

181

226

4

250

157

196

4

200

78

98

2

 

100

99

124

3

 

125

79.8

500

29

222

277

5

300

192

240

5

250

96

120

3

 

125

121

152

3

 

175

 

 

 

 

 

 

 

 

96.5

500

35

268

335

6

350

232

291

5

300

116

145

3

 

150

147

183

4***

 

200

 

 

 

110

500

39

265

331

6

350

132

166

3

 

175

167

209

4***

 

225

 

 

 

145

500

52

175

218

4***

 

225

221

276

5†††

 

300

 

 

LEGEND

ARI

Air Conditioning and Refrigeration Institute

AWG

American Wire Gage

FLA

Full Load Amps

kW

Kilowatts

MCA

Minimum Circuit Amps

MOCP — Maximum Overcurrent Protection

*Standard control steps are listed under the Control Step heading. “Free” additional steps of control are optionally available when the number of subcircuits exceeds the standard number of control steps.

†MCA = 1.25 x FLA; for proper wire sizing, refer to Table 310-16 of the NEC. **2 control steps in this voltage.

††3 control steps in this voltage.

***4 control steps in this voltage.

†††5 control steps in this voltage.

NOTES:

1.Subcircuits are internal heater circuits of 48 amps or less.

2.Electric heat performance is not within the scope of ARI standard 430 certification.

3.To avoid damage due to overheating, minimum face velocity cannot fall below 350 fpm.

27

Page 27
Image 27
Carrier 39LC, 39LB, 39LD, 39LA, 39LE, 39LF, 39LH03-25, 39LG specifications Electric Heater Data, Steps FLA

39LG, 39LH03-25, 39LD, 39LE, 39LB specifications

The Carrier 39 series, encompassing models 39LA, 39LF, 39LC, 39LB, and 39LE, represents a prominent line of rooftop packaged units that combine robust performance, energy efficiency, and advanced technology for commercial applications. Designed to provide reliable heating and cooling solutions, these units stand out for their versatility and innovative features.

The 39LA model offers high efficiency and flexibility, making it ideal for various building types. It incorporates advanced economizer capabilities that enhance indoor air quality while reducing energy costs. The unit is equipped with a dual-walled cabinet, which not only improves durability but also ensures quiet operation, making it suitable for noise-sensitive environments.

The 39LF model further enhances energy savings, featuring a unique hybrid heat pump system. This system allows for both heating and cooling through an integrated design, reducing the need for separate systems and streamlining maintenance requirements. The 39LF also boasts high Seasonal Energy Efficiency Ratio (SEER) ratings, contributing to lower operating costs without compromising comfort.

The 39LC variant excels in humid climates, employing advanced dehumidification technologies that effectively manage indoor moisture levels. This model is often utilized in environments such as gyms, restaurants, and hotels where humidity control is vital. Its variable-speed compressors adjust output based on demand, optimizing energy consumption while maintaining consistent comfort levels.

The 39LB model focuses on enhanced filtration and air quality improvements. Its engineered design accommodates high-efficiency particulate air (HEPA) filters, crucial for spaces that require stringent air quality standards. This model also includes smart controls that allow for precise temperature adjustments, ensuring optimal comfort in any setting.

Finally, the 39LE unit emphasizes user-friendly interfaces and smart technology integration. The built-in Wi-Fi capability enables remote monitoring and operation, allowing managers to adjust settings from anywhere, improving overall energy management. Additionally, the 39LE’s compatibility with Building Management Systems (BMS) facilitates seamless integration into existing setups.

In summary, the Carrier 39 series 39LA, 39LF, 39LC, 39LB, and 39LE present a comprehensive array of features designed for various commercial heating and cooling applications. With an emphasis on energy efficiency, advanced air quality management, and user-friendly technology, these units continue to set the standard for rooftop packaged units in the industry. Their innovative characteristics not only enhance comfort but also promote sustainability, making them a smart choice for modern commercial environments.