6.Check fan speed with a strobe-type tachometer or use the following formula: Obtain the motor rpm from the fan motor nameplate and read sheave pitch diameters marked on the fan and motor pulleys, or estimate the pitch diame- ters by using the pulley outside diameters.

Then:

 

 

Motor Rpm x Motor Sheave

Fan Rpm =

 

 

Pitch Diameter (in.)

 

Fan Sheave Pitch Diameter (in.)

 

Example:

 

 

Actual

 

 

 

 

 

Approximate

Nameplate Motor

=

1760

1760

 

Rpm

 

 

Mtr Sheave Pitch

=

8.9 in.

9.0 (OD)

Diameter

 

Fan Sheave Pitch

=

12.4 in.

12.5 (OD)

Diameter

 

Fan Rpm

 

=

1760 x 8.9

1760 x 9

 

 

=

12.4

12.5

 

 

 

=

1263 Rpm

1267 Rpm

Refer to Table 1, Physical Data for maximum allowable fan speeds for standard wheels. Excessive fan speed may result in condensate carryover from cooling coil or fan motor overload and wheel failure.

7.Check direction of rotation (see Fig. 36). Arrow on drive side of fan housing indicates correct direction of rotation.

Fig. 36 — Fan Wheel Rotation

8.Check vibration. If excessive vibration occurs, check for the following:

a.Variable sheave (if air balance of system has been accomplished: replace sheave with fixed sheave for continuous application).

b.Drive misalignment.

c.Mismatched, worn or loose belts.

d.Wheel or sheaves loose on shaft.

e.Loose bearings.

f.Loose mounting bolts.

g.Motor out of balance.

h.Sheaves eccentric or out of balance.

i.Vibration isolators improperly adjusted.

j.Out-of-balance or corroded wheel (rebalance or replace if necessary).

k.Accumulation of material on wheel (remove excess material).

COILS

Chilled Water Coil — Typical coil vents, drains, and lifting points are shown in Fig. 17.

DX Coil — Charge refrigerant. Also refer to condensing unit service and installation instructions. Refrigerant operating charge for unit coil is shown in Table 1.

SERVICE

General

1.Place a suitable walkway to protect floor insulation whenever entering the fan section.

2.Review Safety Considerations at beginning of these in- structions. Good safety habits are important tools when performing service procedures.

3.To make speed measurements, use a strobe-style tachom- eter or calculate per Step 6 of Start-Up, Check List.

Fan Motor Replacement

1.Shut off motor power.

2.Disconnect and tag power wires at motor terminals.

3.Loosen motor brace-to-mounting-rail attaching bolts. Loosen belt tensioning bolts to adjust the motor position so V-belts can be removed without stretching over grooves.

4.Mark belt as to position. Remove and set aside belts.

5.Remove motor to motor bracket holddown bolts.

6.Remove motor pulley and set aside.

7.Remove motor.

8.Install new motor. Reassemble by reversing Steps 1-6. Be sure to reinstall multiple belts in their original position. Use a complete new set if required. Do not stretch belts over sheaves. Review the sections on motor and sheave installation, sheave alignment and belt tensioning dis- cussed previously (Fig. 13-15).

9.Reconnect motor leads and restore power. Check fan for proper rotation as described in Start-Up, Check List.

Coil Cleaning

DETERGENT — Spray mild detergent solution on coils with garden-type sprayer. Rinse with fresh water. Check to ensure condensate line is free. Excess water from cleaning may flood unit if condensate line is plugged.

STEAM — Remove coil to facilitate cleaning and prevent damage to unit insulation. See Coil Removal section which follows.

Winter Shutdown (Chilled Water Coil Only) — It is recommended that auxiliary drain piping be added to coil piping if yearly winterizing of coils is anticipated. This auxilia- ry piping should be located at the highest and lowest point on the respective header connection for each coil.

ANTIFREEZE METHODS OF COIL PROTECTION

1.Close coil water supply and return valves.

2.Drain coil as follows:

Method I — ‘Break’ flange of coupling at each header location. Separate flange or coupling connection to facili- tate coil draining.

Method II — Open both valves to auxiliary drain piping.

3.After coil is drained, Method I, connect line with a service valve and union from upper nozzle to an antifreeze reser- voir. Connect a self-priming reversible pump between the low header connection and the reservoir. Method II, make connection to auxiliary drain valves.

4.Fill reservoir with any inhibited antifreeze acceptable to code and underwriter authority.

5.Open service valve and circulate solution for 15 minutes; then check its strength.

30

Page 30
Image 30
Carrier 39LH03-25, 39LB, 39LD, 39LA, 39LC, 39LE, 39LF, 39LG specifications Service, General, Fan Motor Replacement, Coil Cleaning

39LG, 39LH03-25, 39LD, 39LE, 39LB specifications

The Carrier 39 series, encompassing models 39LA, 39LF, 39LC, 39LB, and 39LE, represents a prominent line of rooftop packaged units that combine robust performance, energy efficiency, and advanced technology for commercial applications. Designed to provide reliable heating and cooling solutions, these units stand out for their versatility and innovative features.

The 39LA model offers high efficiency and flexibility, making it ideal for various building types. It incorporates advanced economizer capabilities that enhance indoor air quality while reducing energy costs. The unit is equipped with a dual-walled cabinet, which not only improves durability but also ensures quiet operation, making it suitable for noise-sensitive environments.

The 39LF model further enhances energy savings, featuring a unique hybrid heat pump system. This system allows for both heating and cooling through an integrated design, reducing the need for separate systems and streamlining maintenance requirements. The 39LF also boasts high Seasonal Energy Efficiency Ratio (SEER) ratings, contributing to lower operating costs without compromising comfort.

The 39LC variant excels in humid climates, employing advanced dehumidification technologies that effectively manage indoor moisture levels. This model is often utilized in environments such as gyms, restaurants, and hotels where humidity control is vital. Its variable-speed compressors adjust output based on demand, optimizing energy consumption while maintaining consistent comfort levels.

The 39LB model focuses on enhanced filtration and air quality improvements. Its engineered design accommodates high-efficiency particulate air (HEPA) filters, crucial for spaces that require stringent air quality standards. This model also includes smart controls that allow for precise temperature adjustments, ensuring optimal comfort in any setting.

Finally, the 39LE unit emphasizes user-friendly interfaces and smart technology integration. The built-in Wi-Fi capability enables remote monitoring and operation, allowing managers to adjust settings from anywhere, improving overall energy management. Additionally, the 39LE’s compatibility with Building Management Systems (BMS) facilitates seamless integration into existing setups.

In summary, the Carrier 39 series 39LA, 39LF, 39LC, 39LB, and 39LE present a comprehensive array of features designed for various commercial heating and cooling applications. With an emphasis on energy efficiency, advanced air quality management, and user-friendly technology, these units continue to set the standard for rooftop packaged units in the industry. Their innovative characteristics not only enhance comfort but also promote sustainability, making them a smart choice for modern commercial environments.