Carrier 40RU manual Electrical Data, Standard Motors, Electrical Data, Alternate Motors

Models: 40RU

1 40
Download 40 pages 19.52 Kb
Page 20
Image 20
Table 4 – Electrical Data, Standard Motors

Table 4 – Electrical Data, Standard Motors

 

 

 

 

 

VOLTAGE

FAN MOTOR

 

UNIT

---V---PH

Hz{

Hp (kW)

 

FLA

 

 

 

 

 

LIMITS

 

 

 

 

 

 

 

 

 

 

40RUA*25

208/230---

3---

60

187---

253

5.0 (3.73)

 

14.7/13.6

 

 

 

 

 

 

 

 

 

460

3---

60

414

506

5.0 (3.73)

 

6.8

40RUQ*25

 

40RUS*25

575

3---

60

518

632

5.0 (3.73)

 

5.1

 

 

 

 

 

 

 

 

 

 

 

40RUA*28

208/230---

3---

60

187---

253

7.5 (5.59)

 

21.4/19.4

 

 

 

 

 

 

 

 

 

460

3---

60

414

506

7.5 (5.59)

 

9.7

40RUS*28

 

 

 

 

 

 

 

 

 

 

575

3---

60

518

632

7.5 (5.59)

 

7.8

 

 

 

 

 

 

 

 

 

 

 

40RUA30

208/230---

3---

60

187---

253

10.0 (7.46)

 

28.0/25.2

 

 

 

 

 

 

 

 

 

460

3---

60

414

506

10.0 (7.46)

 

12.6

40RUS30

 

 

 

 

 

 

 

 

 

 

575

3---

60

518

632

10.0 (7.46)

 

10.3

 

 

 

 

 

 

 

 

 

 

 

 

POWER SUPPLY

Minimum

MOCP

Circuit Amps

 

 

 

18.4/17.0

30/25

 

 

8.5

15

 

 

6.4

15

 

 

26.9/24.3

45/40

12.120

9.8

15

 

 

35.0/31.5

60/50

15.825

12.920

40RU

See Legend and Notes below.

Table 5 – Electrical Data, Alternate Motors

 

 

 

 

 

VOLTAGE

FAN MOTOR

 

UNIT

V---PH

Hz{

 

 

 

Hp (kW)

 

FLA

 

 

 

 

 

LIMITS

 

 

 

 

 

 

 

 

 

 

40RUA*25

208/230---

3---

60

187---

253

7.5 (5.59)

 

21.4/19.4

 

 

 

 

 

 

 

 

 

460

3---

60

414

506

7.5 (5.59)

 

9.7

40RUQ*25

 

40RUS*25

575

3---

60

518

632

7.5 (5.59)

 

7.8

 

 

 

 

 

 

 

 

 

 

 

40RUA*28

208/230---

3---

60

187---

253

10.0 (7.46)

 

28.0/25.2

40RUA*30

 

 

 

 

 

 

 

 

 

460

3---

60

414

506

10.0 (7.46)

 

12.6

40RUS*28

 

 

 

 

 

 

 

 

 

 

575

3---

60

518

632

10.0 (7.46)

 

10.3

40RUS*30

 

 

 

 

 

 

 

 

 

 

 

POWER SUPPLY

Minimum

MOCP

Circuit Amps

 

 

 

26.9/24.3

45/40

12.120

9.8

15

 

 

35.0/31.5

60/50

15.825

12.920

See Legend and Notes below.

Legend and Notes for Tables 4 and 5

LEGEND:

FLA

---

Full Load Amps

MOCP

---

Maximum Overcurrent Protection

{Motors are designed for satisfactory operation within 10% of normal voltage shown. Voltages should not exceed the limits shown in the Voltage Limits column.

NOTES:

1.Minimum circuit amps (MCA) and MOCP values are calcu- lated in accordance with The NEC. Article 440.

2.Motor FLA values are established in accordance with Under- writers’ Laboratories (UL). Standard 1995.

3.Unbalanced 3-Phase Supply Voltage

Never operate a motor where a phase imbalance in supply voltage is greater than 2%. Use the formula in the example (see column to the right) to determine the percentage of volt- age imbalance.

4.Installation with Accessory Electric Heaters

Size the Field Power Wiring between the heater TB1 and the 40RU indoor fan motor per NEC Article 430--- 28 (1) or (2) (depends on length of conduit between heater enclosure and 40RU power entry location). Install wires in field--- installed conduit.

Example: Supply voltage is 230-3-60

% Voltage Imbalance = 100 x

max voltage deviation from average voltage

 

average voltage

 

AB = 393 v

BC = 403 v

AC = 396 v

Average Voltage =

(393 + 403 + 396)

=

1192

 

 

3

3

 

 

=397

Determine maximum deviation from average voltage. (AB) 397 – 393 = 4 v

(BC) 403 – 397 = 6 v (AC) 397 – 396 = 1 v Maximum deviation is 4 v.

Determine percent of voltage imbalance.

% Voltage Imbalance

= 100 x

6

 

397

 

 

 

= 1.5%

 

This amount of phase imbalance is satisfactory as it is below the maximum allowable 2%.

IMPORTANT: If the supply voltage phase imbalance is more than 2%, contact your local electric utility company immediately.

20