Carrier manual UNIT 40RUQ

Models: 40RU

1 40
Download 40 pages 19.52 Kb
Page 5
Image 5
UNIT 40RUQ*

Table 1C — 40RUQ Physical Data, English — Heat Pump Units

UNIT 40RUQ*

25

 

 

NOMINAL CAPACITY (Tons)

20

 

 

OPERATING WEIGHT (lb)

 

Base Unit with TXV

720

Plenum

140

 

 

FANS

 

Qty...Diam. (in.)

2...15

Nominal Airflow (cfm)

8000

Airflow Range (cfm)

6000--- 10000

Nominal Motor Hp (Standard Motor)

 

208/230---3---60 and 460---3---60

5.0

575---3---60

5.0

Motor Speed (rpm)

 

208/230---3---60 and 460---3---60

1745

575---3---60

1745

 

 

REFRIGERANT

R--- 410A

Operating charge (lb)

3.5/3.5

(approx per circuit){

DIRECT---EXPANSION COIL

Enhanced Copper Tubes, Aluminum Sine--- Wave Fins

Max Working Pressure (psig)

650

Face Area (sq ft)

19.9

No. of Splits

2

No. of Circuits per Split

2

Split Type...Percentage

Face....50/50

Rows...Fins/in.

4...15

 

 

PIPING CONNECTIONS,

 

Quantity...Size (in.)

 

DX Coil — Suction (ODF)

2...11/8

DX Coil — Liquid Refrigerant (ODF)

2...5/8

Steam Coil, In (MPT)

1...21/2

Steam Coil, Out (MPT)

1...11/2

Hot Water Coil, In (MPT)

1...2

Hot Water Coil, Out (MPT)

1...2

Condensate (PVC)

1...11/4 ODM/1 IDF

FILTERS

Throwaway — Factory Supplied

Quantity...Size (in.)

4...16 x 20 x 2

 

4...16 x 24 x 2

Access Location

Right or Left Side

 

 

STEAM COIL}

 

Max Working Pressure (psig at 260° F)

20

Total Face Area (sq ft)

13.33

Rows...Fins/in.

1...10

 

 

HOT WATER COIL}

 

Max Working Pressure (psig)

150

Total Face Area (sq ft)

13.33

Rows...Fins/in.

2...8.5

Water Volume

 

(gal)

13.9

(ft3)

1.85

LEGEND

DX — Direct Expansion

TXV — Thermostatic Expansion Valve

{Units are shipped without refrigerant charge.

}Field installed accessory only.

40RU

5

Page 5
Image 5
Carrier manual UNIT 40RUQ