40RU
Table 1D — 40RUA Physical Data, SI — Heat Pump Units
UNIT 40RUQ* | 25 | |
|
| |
NOMINAL CAPACITY (kW) | 70 | |
|
| |
OPERATING WEIGHT (kg) |
| |
Base Unit with TXV | 326 | |
Plenum | 44 | |
|
| |
FANS |
| |
Qty...Diam. (mm) | 2...381 | |
Nominal Airflow (L/s) | 3775 | |
Airflow Range (L/s) | ||
Nominal Motor kW (Standard Motor) |
| |
3.73 | ||
3.73 | ||
Motor Speed (r/s) |
| |
29.1 | ||
29.1 | ||
|
| |
REFRIGERANT | ||
Operating charge (kg) | 1.59/1.59 | |
(approx per circuit){ | ||
Enhanced Copper Tubes, Aluminum | ||
Max Working Pressure (kPag) | 4482 | |
Face Area (sq m) | 1.85 | |
No. of Splits | 2 | |
No. of Circuits per Split | 2 | |
Split Type...Percentage | Face...50/50 | |
Fins/m | 591 | |
|
| |
PIPING CONNECTIONS, |
| |
Quantity...Size (in.) |
| |
DX Coil — Suction (ODF) | 2...11/8 | |
DX Coil — Liquid Refrigerant (ODF) | 2...5/8 | |
Steam Coil, In (MPT) | 1...21/2 | |
Steam Coil, Out (MPT) | 1...11/2 | |
Hot Water Coil, In (MPT) | 1...2 | |
Hot Water Coil, Out (MPT) | 1...2 | |
Condensate (PVC) | 1...11/4 ODM/1 IDF | |
FILTERS | Throwaway — Factory Supplied | |
Quantity...Size (mm) | 4...406 x 610 x 51 | |
4...406 x 508 x 51 | ||
| ||
Access Location | Right or Left Side | |
|
| |
STEAM COIL} |
| |
Max Working Pressure (kPag at 126° C) | 138 | |
Total Face Area (sq m) | 1.24 | |
Rows...Fins/m | 1...394 | |
|
| |
HOT WATER COIL} |
| |
Max Working Pressure (kPag) | 1034 | |
Total Face Area (sq m) | 1.24 | |
Rows...Fins/m | 2...335 | |
Water Volume |
| |
(L) | 52.6 | |
(m3) | 0.052 |
LEGEND
DX — Direct Expansion
TXV — Thermostatic Expansion Valve
{Units are shipped without refrigerant charge.
}Field installed accessory only.
6