Carrier 42GW installation manual

Models: 42GW

1 18
Download 18 pages 29.55 Kb
Page 6
Image 6

42 GW

 

Avoid...

E N G L I S H

MAX 3 m

MAX 3 m

... any obstruction of the unit air intake or supply grilles.

... exposure to direct sunshine, when the unit is operating in the

 

cooling mode; always use shutters or shades.

 

... positions too close to heating sources which may damage the unit.

... exposure to oil vapours.

... connecting condensate piping to sewage system drain without appropriate trap. Trap height must be calculated according to the unit discharge head in order to allow sufficient and continuous water evacuation.

... installation in areas with high frequency waves.

MAX. 200 mm

... only partial insulation of the piping.

Non-level installation which will cause condensate dripping.

... ascending sections of condensate drain piping.

These may only be used near the unit with a maximum height difference of 200 mm from the top of the unit.

... flattening or kinking the refrigerant pipes or condensate pipes.

... horizontal sections or curves of condensate drain piping with less than 2% slope.

...slack on electrical connections.

GB - 5

Page 6
Image 6
Carrier 42GW installation manual