Carrier 48MA/50ME016-040 specifications Ð Unit 48MA Electrical Data

Models: 48MA/50ME016-040

1 48
Download 48 pages 46.89 Kb
Page 11
Image 11
Table 2 Ð Unit 48MA Electrical Data

Use the following formula to determine the percent volt- age imbalance.

% Voltage Imbalance:

= 100 ×

max voltage deviation from average voltage

average voltage

 

EXAMPLE: Supply voltage is 460-3-60.

AB = 452 v

BC = 464 v

AC = 455 v

452 + 464 + 455

Average Voltage =

3

1371

=

3

= 457

Determine maximum deviation from average voltage.

(AB) 457 − 45 2 = 5 v (BC) 464 − 45 7 = 7 v (AC) 457 − 45 5 = 2 v

Maximum deviation is 7 v.

Determine percent voltage imbalance:

IMPORTANT: If the supply voltage phase imbalance is more than 2%, contact your local electric utility com- pany immediately.

Unit failure as a result of operation on improper line volt- age or excessive phase imbalance constitutes abuse and may cause damage to electrical components. See Tables 2-5 for unit, electric heater, and 50ME electrical application elec- trical data.

Each 50ME electric heat unit is ®tted with a heating lock- out circuit (if equipped with optional heat). If any zone mod- ule is operating on mechanical cooling (compressor is op- erating), the heating element in each zone module is locked out and cannot be energized.

On 50ME units, cooling power supply wires and electric heater power supply wires (if applicable) must be sized ac- cording to the cooling MCA (Minimum Circuit Amps) val- ues and heating MCA values shown on unit nameplate and in Tables 3-5. These wires may be powered by a common power supply (i.e., a pull-box junction), if desired. The com- mon power supply wires from the main power source to the junction must be sized according to the common MCA val- ues shown in Table 5.

% Voltage Imbalance = 100 x

7

UNIT COMMON FEED MINIMUM CIRCUIT AMPS Ð The unit common feed MCA is calculated on the basis of

457

= 1.53%

This amount of phase imbalance is satisfactory as it is below the maximum allowable 2%.

either: the sum of the cooling MCA plus 1¤2 heating MCA on units with 2 heating elements per zone module (or 2¤3 heat- ing MCA on units with 3 heating elements per zone module) or the sum of the evaporator fan motor full load amps, per NEC, plus the full heating MCA, whichever is larger. Field wiring must conform to NEC limitations for Type T wire.

Table 2 Ð Unit 48MA Electrical Data

UNIT

Voltage

VOLTAGE

COMP

COMP

 

OFM

 

COMBUSTION

 

IFM

POWER

RANGE

NO. 1

NO. 2

 

FLA

 

FAN MOTOR

 

SUPPLY

48MA

(3 Ph, 60 Hz)

 

 

 

 

 

Min

Max

RLA

LRA

RLA

LRA

No. 1

No. 2

No. 3

FLA

Hp

 

FLA

MCA

MOCP

 

 

 

 

208/230

187

254

63.6

266

 

 

 

6.6

 

 

 

 

16.2

109.6

125

016

460

414

508

28.6

120

Ð

Ð

6.2

3.0

Ð

1.8

5

 

6.6

49.8

60

 

575

518

632

22.8

96

 

 

 

2.4

 

 

 

 

5.6

39.8

45

 

208/230

187

254

44.4

170

44.4

170

 

6.6

 

 

 

 

24.2

137.5

150

024

460

414

508

19.9

77

19.9

77

6.2

3.0

Ð

1.8

7.5

 

11.0

62.2

70

 

575

518

632

15.7

62

15.7

62

 

2.4

 

 

 

 

9.0

49.4

60

 

208/230

187

254

63.6

266

44.4

170

 

6.6

 

 

 

 

30.8

168.1

200

028

460

414

508

28.6

120

19.9

77

6.2

3.0

Ð

1.8

10

 

13.0

76.1

90

 

575

518

632

22.8

96

15.7

62

 

2.4

 

 

 

 

10.5

60.4

70

 

208/230

187

254

63.6

266

63.6

266

 

6.6

 

 

 

 

30.8

187.3

200

030

460

414

508

28.6

120

28.6

120

6.2

3.0

Ð

1.8

10

 

13.0

84.5

100

 

575

518

632

22.8

96

22.8

96

 

2.4

 

 

 

 

10.5

67.5

90

 

208/230

187

254

63.6

266

63.6

266

 

6.6

6.6

 

15

 

46.2

210.8

225

 

 

 

20

 

61.0

224.6

250

 

 

 

 

 

 

 

 

 

 

 

 

 

034

460

414

508

28.6

120

28.6

120

6.2

3.0

3.0

1.8

15

 

21.0

94.5

100

20

 

26.6

100.5

125

 

 

 

 

 

 

 

 

 

 

 

 

 

 

575

518

632

22.8

96

22.8

96

 

2.4

2.4

 

15

 

16.0

75.6

90

 

 

 

20

 

21.3

80.6

100

 

 

 

 

 

 

 

 

 

 

 

 

 

 

208/230

187

254

80.0

345

80.0

345

 

6.6

6.6

 

15

 

46.2

247.7

300

 

 

 

20

 

61.0

261.5

300

 

 

 

 

 

 

 

 

 

 

 

 

 

040

460

414

508

38.5

150

38.5

150

6.2

3.0

3.0

1.8

15

 

21.0

116.7

150

20

 

27.0

122.7

150

 

 

 

 

 

 

 

 

 

 

 

 

 

 

575

518

632

31.4

120

31.4

120

 

2.4

2.4

 

15

 

16.0

95

125

 

 

 

20

 

21.3

100

125

 

 

 

 

 

 

 

 

 

 

 

 

 

 

LEGEND

COMP Ð Compressor

FLA

Ð Full Load Amps

IFM

Ð Indoor (Evaporator) Fan Motor

LRA

Ð Locked Rotor Amps

MCA

Ð Minimum Circuit Amps

MOCP Ð Maximum Overcurrent Protection

OFM

Ð

Outdoor (Condenser) Fan Motor

RLA

Ð

Rated Load Amps

NOTES:

1.Combustion air fan is a 115-1-60 motor on all units.

2.Condenser fan motor no. 1 is a 208/230-1-60 speed control motor on all units.

11

Page 11
Image 11
Carrier 48MA/50ME016-040 specifications Ð Unit 48MA Electrical Data