HEATING (48MA) Ð On call for heating from a zone, the forced draft blower will start and the pilot will light. The zone burner will ignite after the pilot has been proven. (Ap- proximately 60 seconds.)

NOTE: A time-delay relay will shut unit down in 180 sec- onds if the unit main gas valve is not open.

HEATING (50ME WITH ELECTRIC HEAT) Ð On a call for heating from a zone, the ®rst-stage heating relay, con- tactor, and heating element are energized. Upon additional calls for heating from that zone, stage 2 is energized in a similar manner. However, second element on 2-element heater assemblies and second and third heating elements on 3-element heater assemblies are energized as described in Outdoor Air Thermostat Adjustment section on page 36.

Heating Lockout (50ME with Electric Heat) Ð If any zone module is operating on mechanical cooling (Compressor[s] is operating), one heating element in each zone module is locked out and zone module cannot be energized. Operation of lockout circuit is independent of outdoor-air thermostat operation.

HEATING (50ME WITH GLYCOL HEATING COILS) Ð On a call for heating from a zone, the heating relay and heat- ing coil solenoid valve for that zone are energized. If 2 or more unit zone modules are joined to serve a common zone, stage 2 of heating thermostat operates remaining heating relays and solenoid valves depending on connection arrangement.

OUTDOOR-AIR DAMPER Ð This control regulates the amount of outdoor air that passes through the outdoor air evaporator coil and enters the return air-stream (Fig. 34 and 35). A knob in the zone control and thermostat panel acti- vates the damper control motor (damper operator). Damper may be fully closed, fully open, or set at any intermediate position by setting the knob as desired. In the fully open po- sition, the damper will permit 25% outdoor air and 75% re- turn air into the unit.

SERVICE

Cabinet Panels and Grilles

SIDE PANELS Ð To remove a panel, remove lower screw on T-fastener. Loosen T-fastener pivot screw. Swing aside T-fastener. Pull bottom of panel out and down.

TOP PANELS Ð Remove end caps from each end of rain covers. Remove panel screws and lift off panels as required. Save end caps and screws for reinstallation.

HEATER ACCESS PANELS Ð See Side Panels section above.

Cleaning Ð Inspect unit interior at the beginning of each heating and cooling season and during each season as op- erating conditions require. Remove unit side panels and top panels to expose unit interior as required.

EVAPORATOR COILS (ZONE COOLING COILS) AND GLYCOL HEATING COILS Ð Clean with a stiff brush, vacuum cleaner, or compressed air.

CONDENSER AND OUTDOOR-AIR COOLING COILS

ÐClean with a stiff brush or vacuum cleaner. If cleaning with compressed air or low-pressure water or steam, guard against damaging compressor, wiring, and nearby controls.

CONDENSATE DRAINS Ð Check and clean annually at start of cooling season.

INDOOR-AIR FILTERS Ð Clean or replace ®lters at start of each heating and cooling season and as often as necessary during each season, depending on operating conditions. Re- fer to Table 1 for type and size of ®lters used. Filter section is shown in Fig. 34 and 35. Indoor-air ®lter tracks will ac- cept 2 layers of one-in. thick ®lters.

OUTDOOR-AIR INLET SCREENS Ð Clean with steam or hot water and mild detergent.

GAS HEATING SECTION Ð Inspect burners and heat ex- changers before each heating season. Remove exhaust grilles to inspect heat exchangers. Clean with wire brush if there is any accumulation of debris. The main burners should also be cleaned if there is any accumulation of debris. Fire each zone to be assured of proper operation. Correct pilot height is 1 to 11¤2 inches.

COMBUSTION AIR FAN Ð Inspect blower wheel for dirt, and remove and clean if necessary.

Air¯ow Switches

INDOOR AIRFLOW SWITCH (AFS1) Ð This switch is located in evaporator fan inlet venturi. This switch will shut down unit if air¯ow through zone modules is insufficient.

COMBUSTION AIRFLOW SWITCH (AFS2) Ð This switch (48MA only) is located in combustion air plenum. This switch will shut down unit heating mode if combustion air is in- sufficient. See Forced-Draft Blower (48MA) section on page 42 for details on combustion air shutter adjustment.

Service Switch Ð A control circuit service switch is located in the power and condensing control box (Fig. 34 and 35). Shut down unit (compressors, fans, and control cir- cuits) at this switch.

Do not use compressor circuit breakers to start and stop compressors except in emergency.

Time Guard Control Circuit Ð Each compressor circuit has a 5-minute delay before restarting compressor af- ter shutdown for any reason. On starting, Time Guard device timer causes a delay of 15 seconds after thermostat closes before compressor starts. On compressor shutdown, timer re- cycles for 4 minutes, 45 seconds. During this time, compres- sor cannot restart.

On 2-compressor units, no. 2 compressor will not start for at least 21¤2 minutes after no. 1 compressor starts. See Capacity Control Pressure Switches section below.

Capacity Control Pressure Switches (CCP) (2-Compressor Units Only) Ð These switches are connected to the suction side of the system on compressor no. 2. Approximately 21¤2 minutes after compressor no. 2 starts, the timer makes the circuit to CCP1 and CCP2 to operate compressor no. 2 as follows:

1.CCP1 is open (opens at 63 psig; closes at 83 psig). This prevents cycling of compressor no. 2 at start-up.

2.CCP2 is closed (opens at 54 psig; closes at 78 psig).

3.Holding relay no. 2 (HR2) is deenergized.

When the suction pressure reaches 83 psig, CCP1 closes to energize HR2 and compressor no. 2. Compressor no. 2 will then be operated by CCP2.

Compressor Oil Ð Compressors have their own oil sup- ply. Compressor crankcases on 2-compressor units are in- terconnected. Loss of oil due to a leak in the system should be the only reason for adding oil after unit has been in op- eration. A sight glass is provided in the crankcase intercon- nection line or on the compressor crankcase. Remove end panels to gain access to compressors. Sight glass on 06D compressor should be about 1¤3 to 2¤3 full of oil. Sight glass on 06E compressor should be about 1¤8 to 1¤2 full of oil.

Compressor data is shown in Table 1 and on dataplate at- tached to compressor body. Refer to 06D or 06E Compres- sor Service Manual for additional compressor service information.

39

Page 39
Image 39
Carrier 48MA/50ME016-040 Service, Cabinet Panels and Grilles, Air¯ow Switches, Condenser and OUTDOOR-AIR Cooling Coils

48MA/50ME016-040 specifications

The Carrier 48MA/50ME016-040 series represents a significant advancement in the field of commercial HVAC systems, designed to provide reliable, efficient, and effective climate control solutions for various applications. These units are widely recognized for their durability and performance, making them a top choice for building owners and managers seeking optimal comfort and energy efficiency.

One of the main features of the Carrier 48MA/50ME series is its advanced scroll compressor technology. The scroll compressors are known for their reliability and efficiency, which leads to reduced energy consumption and lower operating costs. This high-efficiency design not only contributes to significant energy savings but also minimizes noise levels, enhancing the overall comfort of the environment.

The units are equipped with a unique microprocessor-based control system that offers precise temperature control and flexibility. This technology allows for easy integration with building management systems, enabling users to monitor and control their HVAC systems remotely, thereby optimizing performance and energy use. The programmable thermostats help to tailor the operation of the units to meet the specific needs of the users, ensuring maximum comfort at all times.

In addition to its robust performance features, the Carrier 48MA/50ME series also boasts a comprehensive line of options for customization. These options include various cooling capacities ranging from 16 to 40 tons, allowing the equipment to cater to different building sizes and requirements. The series is also designed with a compact footprint, making it suitable for rooftop installations where space is at a premium.

Another important characteristic of the series is its environmentally friendly refrigerant options. Carrier prioritizes the use of refrigerants with low global warming potential, contributing to a more sustainable approach to HVAC solutions. This commitment to environmental responsibility not only complies with regulations but also meets the increasing demand for greener technologies.

Furthermore, the robust construction of the Carrier 48MA/50ME series ensures long-lasting performance in even the harshest conditions. The units are designed to withstand various environmental factors, making them ideal for both commercial and industrial applications. Overall, the Carrier 48MA/50ME016-040 series stands out as a reliable choice for efficient and effective heating and cooling solutions, equipped with innovative technologies that prioritize performance, sustainability, and user comfort.