ACCESSORY REMOTE CONTROL PANEL Ð This central- station control can be set to override zone thermostat mode settings to lock out heating or cooling for the entire unit. The DAY/NIGHT switch and damper position knob provide in- space, central control of damper position. Panel also houses the ®lter light to indicate reduced air¯ow and need for clean ®lters. See Fig. 29. Install remote control panel in accor- dance with instructions shipped with this accessory.
Reheat Humidity Control Ð Control is achieved in any module by wiring a humidistat in parallel with the cool- ing thermostat. If zone thermostat drops below setting of heat- ing thermostat because the humidistat is closed (cooling coil is energized), the heating mode will be energized to reheat the air in order to maintain zone space temperature. A typi- cal humidistat hookup is shown in Fig. 30.
Optional Economizer Ð Adjust optional economizer as described in Optional Economizer section on page 42.
Optional Exhaust Damper Ð Adjust optional ex- haust damper as described in Optional Exhaust Damper sec- tion on page 42.
START-UP
After unit is installed, perform the following checks and procedures, and complete
Evaporator Fan Ð Fan belt and pulley are shipped at- tached to fan assembly. The
Compressor Rail Shipping Bolts Ð Loosen ship- ping bolts beneath compressor rails so that rails ¯oat freely. Do not loosen or remove bolts that attach compressors to rails.
Refrigerant Valves Ð Open compressor discharge serv- ice valve. Check that the suction service, hot gas shutoff, and the liquid line shutoff valves are also open. See Fig. 31.
Zone Module Gas Valves (48MA) Ð Each zone mod- ule has its own combination gas valve and pressure regula- tor to which gas is supplied by one of the 2 main manual gas valves (Fig. 32).
|
| LEGEND |
| |
APS | Ð Air Pressure Switch | OR | Terminal (Circuit Board, | |
MCR Ð Master Cooling Relay | Field or Accessory Conn.) | |||
| ||||
MHR Ð Master Heating Relay |
| |||
| Accessory or Field Wiring | |||
MUR | Ð Master Unit Relay |
| ||
| Factory Wiring | |||
NC | Ð Normally Closed |
| ||
NO | Ð Normally Open |
| Circuit Board Run |
Fig. 29 Ð Remote Control Panel Accessory Connections