OPTIONAL NON-FUSED DISCONNECT -- On units with

the optiomfl non-fused disconnect, incoming power will be wired into the disconnect switch. Refer to Fig. 16 for wiring

for 100 and 200 amp disconnect switches. Units with an MOCP under 100 will use the 100 amp disconnect switch.

Units with an MOCP over 100 will use the 200 amp discon- nect switch. Refer to the applicable disconnect wMng diagram.

To prevent breakage during shipping, the disconnect handle and shaft are shipped and packaged inside the unit control box. Install the disconnect handle before unit operation. To install

the handle and shaft, perform the following procedure:

1.Open the control box door and remove the handle and shaft from shipping location.

2.Ix_osen the Allen bolt located on the disconnect switch. The bolt is located on the square hole and is used to hold the shaft in place. The shaft cannot be inserted until the Allen bolt is moved.

3.Insert the disconnect shaft into the squae hole on the dis- connect switch. The end of the shaft is specially cut and the shaft can only be inserted in the correct orientation.

4.Tighten the Allen bolt to lock the shaft into position.

5.Close the control box dool:

6.Attach the handle to the external access door with the two

screws provided. When the handle is in the ON position, the handle will be vertical. When the handle is in the OFF

position, the handle will be horizontal.

7.Turn the handle to the OFF position and close the dool: The handle should fit over the end of the shaft when the door is closed.

8.The handle must be in the OFF position to open the con- trol box dool:

OPTIONAL CONVENIENCE OUTLET-- On units with

optiomfl convenience outlet, a 115-v GFI (ground fault inter- rupt) convenience outlet receptacle is provided for field wiring. Field wiring should be run through the 7Is-in. knockout pro-

vided in the basepan near the return air opening.

THERMOSTAT ASSEMBLY

Lu

q

z

cc

o

_,

cc

 

I

cc

m

a_

Z

_

m

Z

 

 

o

m

 

 

Fig. 15 --Field Control Thermostat Wiring

 

 

UNIT WIRING

 

6T3

4T2

2T1

LOAD

lO0

BLK,

YEL.

BLU.

 

 

 

 

 

AMP

 

 

 

I

 

 

 

 

[ NON_:EPDOWDEIRsCONNE_T

_--

_

_ OA:

'

 

 

 

 

I

;_ ;__T2Ej

 

 

 

 

FIELD

POWER

SUPPLY

 

5L3

3L2

1L1

LINE

 

UNIT WIRING

 

 

 

 

 

200

BLK.

YEL.

BLU,

 

 

 

 

 

AMP

4--+--t--- '

 

 

 

 

[ NON FUSED DISCONNECT

__i _i_

Lli E j

 

 

 

 

 

FIELD

POWER

SUPPLY

 

 

 

 

 

NOTE: The disconnect takes the place of TB-1 as shown on the unit wiring diagram label and the component arrangement label.

Fig. 16- Optional Non-Fused Disconnect Wiring

12

Page 12
Image 12
Carrier 48TJ016-028 specifications Field Control Thermostat Wiring, Thermostat Assembly

48TJ016-028 specifications

The Carrier 48TJ016-028 is a notable model in the range of packaged rooftop units designed by Carrier, a leader in heating, ventilation, and air conditioning (HVAC) solutions. Tailored specifically for commercial applications, these units provide a blend of efficiency, durability, and reliability, making them suitable for a variety of settings, including offices, retail spaces, and industrial environments.

One of the standout features of the 48TJ series is its energy-efficient performance. Equipped with high-efficiency scroll compressors, these units offer superior cooling capacity while minimizing energy consumption. This aligns with modern sustainability goals, helping businesses reduce their carbon footprint and operational costs. Additionally, the 48TJ units comply with stringent industry standards, such as the ASHRAE 90.1 energy efficiency guidelines, ensuring that users receive a product that meets modern energy performance benchmarks.

The 48TJ016-028 units also include advanced technologies that enhance performance and user comfort. The inclusion of a sophisticated microprocessor control system facilitates precise temperature regulation, allowing for an optimal balance of cooling and heating based on real-time conditions. Moreover, the user-friendly controls make it easy for facility managers to monitor system performance and make adjustments as necessary.

Another notable characteristic of the 48TJ series is its flexible installation options. These rooftop units are designed for easy integration into existing building structures and can be installed on flat or pitched roofs. Their compact design and lightweight construction simplify the installation process while minimizing structural impacts on buildings.

Durability is paramount in the design of the 48TJ units as well. The cabinets are constructed from high-quality materials with corrosion-resistant coatings, ensuring a long lifespan even in harsh environmental conditions. The systems are also equipped with robust insulation to reduce sound levels and improve overall operating efficiency.

Furthermore, the Carrier 48TJ016-028 units offer various options for customization. Users can choose from different airflow configurations, heating options, and accessories, allowing for tailored solutions that meet specific requirements. Whether you are looking for a unit with enhanced filtration, economizer capabilities, or advanced humidity control, the 48TJ series provides the flexibility needed for diverse applications.

In summary, the Carrier 48TJ016-028 units deliver a compelling combination of energy efficiency, advanced technology, and robust construction, making them an ideal choice for commercial HVAC needs. With their versatile features and customizable options, they stand out as reliable solutions for maintaining comfortable indoor environments.