TROUBLESHOOTING

Unit Troubleshooting- Refer to Tables 27-29 and

Fig. 60.

EconoMi$erlV Troubleshooting-- See Table 30

for EconoMi$erlV logic.

A limctional view of the EconoMiSerlV is shown in Fig. 61.

Typic_d settings, sensor ranges, and jumper positions ale also shown. An EconoMiSerIV simulator program is available from Ctuder to help with EconoMi$erIV training and troubleshooting.

ECONOMISERIV PREPARATION -- This procedure is

used to prepare the EconoMiSerIV for troubleshooting. No troubleshooting or testing is done by performing the following procedure.

NOTE: This procedure requires a 9-v battery, 1.2 kilo-ohm

resistol, and a 5.6 kilo-ohln resistor which are not supplied with the EconoMiSerlV.

[ IMPORTANT:tiometers before Bestartingsure totroubleshootingrecordthepositions. of aH poten- ]

1.Disconnect power at TR and TRI. All LEDs should be off. Exhaust fan contacts should be open.

2.Disconnect device at P and PI.

3.Jumper P to PI.

4.Disconnect wires at T and TI. Place 5.6 kilo-ohm resistor across T and TI.

5.Jumper TR to 1.

6.Jumper TR to N.

7.If connected, remove sensor from termimds So and +. Connect 1.2 kilo-ohm 4074EJM checkout resistor across

terminals So and +.

8.Put 620-ohm resistor across terminals SR and +.

9.Set minimum position, DCV set point, and exhaust potentiometers fully CCW (counteMockwise).

10.Set DCV maximum position potentiometer fully CW (clockwise).

11.Set enthalpy potentiometer to D.

12.Apply power (24 vac) to terminals TR and TRI.

DIFFERENTIAL ENTHALPY-- To check differential enthalpy:

1.Make sure EconoMiSerIV prep_uation procedure has been performed.

2.Place 620-ohm resistor across So and +.

3.Place 1.2 kilo-ohm resistor across SR and +. The Free Cool LED should be lit.

4.Remove 620-ohm resistor across So and +. Tile Free Cool LED should turn off.

5.Return EconoMiSerIV settings and wiring to normal after completing troubleshooting.

SINGLE ENTHALPY -- To check single enthalpy:

1. Make sure EconoMiSerIV prepmation procedure has been performed.

2.Set the enthalpy potentiometer to A (fully CCW). The Free Cool LED should be lit.

3.Set the enth_flpy potentiometer to D (fully CW). The Free Cool LED should turn off.

4.Return EconoMiSerlV settings and wiring to normal after completing troubleshooting.

DCV (Demand Controlled Ventilation) AND POWER EXHAUST -- To check DCV and Power Exhaust:

1. Make sure EconoMiSerIV prepmation procedure has been performed.

2.Ensure terminals AQ and AQI _ue open. The LED for both DCV and Exhaust should be off. The actuator

should be fldly closed.

3.Connect a 9-v battery to AQ (positive node) and AQI (negative node). The LED for both DCV and Exhaust

should turn on. The actuator should &ive to between 90 and 95% open.

4.Turn the Exhaust potentiometer CW until the Exhaust LED turns off. The LED should turn off when the

potentiometer is approximately 90%. The actuator should remain in position.

5.Turn the DCV set point potentiometer CW until the DCV LED turns off. The DCV LED should turn off when the

potentiometer is approximately 9-v. Tile actuator should drive fully closed.

6.Turn the DCV and Exhaust potentiometers CCW until the Exhaust LED turns on. The exhaust contacts will

close 30 to 120 seconds after the Exhaust LED turns on.

7.Return EconoMi$erIV settings and wiring to normal after completing troubleshooting.

DCV MINIMUM AND MAXIMUM POSITION -- To check the DCV minimum and maximum position:

1. Make sure EconoMiSerIV preparation procedure has been perforlned.

2.Connect a 9-v battery to AQ (positive node) and AQI

(negative node). The DCV LED should turn on. The actuator should drive to between 90 and 95% open.

3.Turn the DCV Maximum Position potentiometer to mid- point. The actuator should drive to between 20 and 80%

open.

4.Turn the DCV Maximum Position potentiometer to lidly CCW. The actuator should drive fully closed.

5.Turn the Minimum Position potentiometer to midpoint. The actuator should drive to between 20 and 80% open.

6.Turn the Minimum Position Potentiometer lully CW. The actuator should drive fully open.

7.Remove the jumper from TR and N. The actuator should drive fully closed.

8.Return EconoMiSerIV settings and wiring to norm¢fl after completing troubleshooting.

SUPPLY-AIR [NPUT -- To check supply-air input:

1. Make sure EconoMiSerIV preparation procedure has been performed.

2.Set the Enthalpy potentiometer to A. The Free Cool LED turns on. The actuator should drive to between 20 and

80% open.

3.Remove the 5.6 kilo-ohm lesistor and jumper T to TI. The actuator should drive fidly open.

4.Remove the jumper across T and TI. The actuator should drive fully closed.

5.Return EconoMiSerlV settings and wiring to normal after completing troubleshooting.

ECONOMISER IV TROUBLESHOOTING COMPLE- TION -- Tiffs procedure is used to return the EconoMiSerIV

to operation. No troubleshooting or testing is done by perform- ing the following procedure.

1.Disconnect power at TR and TRI.

2.Set enthalpy potentiometer to previous setting.

3.Set DCV maximum position potentiometer to previous setting.

4.Set minimum position, DCV set point, and exhaust potentiometers to previous settings.

5.Remove 620-ohm resistor fix_m terminals SR and +.

6.Remove 1.2 kilo-ohln checkout resistor from terminals So and +. If used, reconnect sensor fix_m terminals So and +.

7.Remove jumper from TR to N.

8.Remove jumper from TR to 1.

9.Remove 5.6 kilo-ohm resistor from T and TI. Reconnect wires at T and TI.

10.Remove jumper from P to PI. Reconnect device at P and PI.

11.Apply power (24 vac) to termimds TR and TRI.

48

Page 48
Image 48
Carrier 48TJ016-028 specifications Unit Troubleshooting- Refer to Tables 27-29

48TJ016-028 specifications

The Carrier 48TJ016-028 is a notable model in the range of packaged rooftop units designed by Carrier, a leader in heating, ventilation, and air conditioning (HVAC) solutions. Tailored specifically for commercial applications, these units provide a blend of efficiency, durability, and reliability, making them suitable for a variety of settings, including offices, retail spaces, and industrial environments.

One of the standout features of the 48TJ series is its energy-efficient performance. Equipped with high-efficiency scroll compressors, these units offer superior cooling capacity while minimizing energy consumption. This aligns with modern sustainability goals, helping businesses reduce their carbon footprint and operational costs. Additionally, the 48TJ units comply with stringent industry standards, such as the ASHRAE 90.1 energy efficiency guidelines, ensuring that users receive a product that meets modern energy performance benchmarks.

The 48TJ016-028 units also include advanced technologies that enhance performance and user comfort. The inclusion of a sophisticated microprocessor control system facilitates precise temperature regulation, allowing for an optimal balance of cooling and heating based on real-time conditions. Moreover, the user-friendly controls make it easy for facility managers to monitor system performance and make adjustments as necessary.

Another notable characteristic of the 48TJ series is its flexible installation options. These rooftop units are designed for easy integration into existing building structures and can be installed on flat or pitched roofs. Their compact design and lightweight construction simplify the installation process while minimizing structural impacts on buildings.

Durability is paramount in the design of the 48TJ units as well. The cabinets are constructed from high-quality materials with corrosion-resistant coatings, ensuring a long lifespan even in harsh environmental conditions. The systems are also equipped with robust insulation to reduce sound levels and improve overall operating efficiency.

Furthermore, the Carrier 48TJ016-028 units offer various options for customization. Users can choose from different airflow configurations, heating options, and accessories, allowing for tailored solutions that meet specific requirements. Whether you are looking for a unit with enhanced filtration, economizer capabilities, or advanced humidity control, the 48TJ series provides the flexibility needed for diverse applications.

In summary, the Carrier 48TJ016-028 units deliver a compelling combination of energy efficiency, advanced technology, and robust construction, making them an ideal choice for commercial HVAC needs. With their versatile features and customizable options, they stand out as reliable solutions for maintaining comfortable indoor environments.