Carrier 50AH024-096 specifications 460-3

Models: 50AH024-096

1 20
Download 20 pages 12.9 Kb
Page 14
Image 14
Manual background

Table 2H — Electrical Data — Upgrade 3 Evaporator Motor with Upgrade 1 Condenser Motor

 

 

VOLTAGE

 

 

 

 

 

 

FAN MOTORS

 

 

 

 

 

 

COMPRESSOR

 

Evaporator

Condenser

POWER SUPPLY

UNIT

V-PH

RANGE

 

 

 

 

 

 

 

(Upgrade 3)

(Upgrade 1)

 

 

50AH

(60 Hz)

 

 

 

 

 

 

 

 

 

 

 

Min

Max

QTY

 

RLA

 

LRA

Hp

FLA

Hp

FLA

Min Ckt

MOCP

 

 

 

 

Amps

Amps

 

 

 

 

 

 

 

 

 

 

 

 

 

024

208/230-1

187

254

1

 

N/A

 

N/A

N/A

N/A

N/A

N/A

N/A

N/A

036

208/230-1

187

254

 

 

N/A

 

N/A

N/A

N/A

N/A

N/A

N/A

N/A

208/230-3

187

254

1

 

N/A

 

N/A

N/A

N/A

N/A

N/A

N/A

N/A

 

460-3

414

508

 

 

N/A

 

N/A

N/A

N/A

N/A

N/A

N/A

N/A

048

208/230-1

187

254

1

 

19.9

 

109.0

1

3.2

1/2

2.5

30.6

50

208/230-3

187

254

 

13.6

 

83.1

1

2.4

1/2

1.8

21.2

35

 

460-3

414

508

 

 

6.1

 

41.0

1

1.2

1/2

0.9

9.7

15

060

208/230-1

187

254

 

 

26.4

 

134.0

1

3.2

1/2

2.5

38.7

65

208/230-3

187

254

1

 

16.0

 

110.0

1

2.4

1/2

1.8

24.2

40

 

460-3

414

508

 

 

7.8

 

52.0

1

1.2

1/2

0.9

11.9

20

072*

208/230-1

187

254

 

 

16.7

 

79.0

1 1/2

6.5

1 1/2

6.5

50.6

65

208/230-3

187

254

2

 

10.4

 

73.0

1 1/2

4.8

1 1/2

4.8

33.0

45

 

460-3

414

508

 

 

5.8

 

38.0

1 1/2

2.4

1 1/2

2.4

17.9

25

096*

208/230-1

187

254

 

 

N/A

 

N/A

N/A

N/A

N/A

N/A

N/A

N/A

208/230-3

187

254

2

 

13.6

 

83.1

2

6.0

2

6.0

42.6

55

 

460-3

414

508

 

 

6.1

 

41.0

2

2.9

2

2.9

19.5

25

Table 2I — Electrical Data — Standard Evaporator Motor with Upgrade 2 Condenser Motor

 

 

VOLTAGE

 

 

 

 

 

 

FAN MOTORS

 

 

 

 

 

 

COMPRESSOR

 

Evaporator

Condenser

POWER SUPPLY

UNIT

V-PH

RANGE

 

 

 

 

 

 

 

(Standard)

(Upgrade 2)

 

 

50AH

(60 Hz)

 

 

 

 

 

 

 

 

 

 

 

Min

Max

QTY

 

RLA

 

LRA

Hp

FLA

Hp

FLA

Min Ckt

MOCP

 

 

 

 

Amps

Amps

 

 

 

 

 

 

 

 

 

 

 

 

 

024

208/230-1

187

254

1

 

N/A

 

N/A

N/A

N/A

N/A

N/A

N/A

N/A

036

208/230-1

187

254

 

 

N/A

 

N/A

N/A

N/A

N/A

N/A

N/A

N/A

208/230-3

187

254

1

 

N/A

 

N/A

N/A

N/A

N/A

N/A

N/A

N/A

 

460-3

414

508

 

 

N/A

 

N/A

N/A

N/A

N/A

N/A

N/A

N/A

048

208/230-1

187

254

 

 

19.9

 

109.0

1/3

1.7

3/4

3.2

29.8

50

208/230-3

187

254

1

 

13.6

 

83.1

1/3

1.3

3/4

2.4

20.7

35

 

460-3

414

508

 

 

6.1

 

41.0

1/3

0.7

3/4

1.2

9.5

15

060

208/230-1

187

254

 

 

26.4

 

134.0

1/3

1.7

3/4

3.2

37.9

65

208/230-3

187

254

1

 

16.0

 

110.0

1/3

1.3

3/4

2.4

23.7

40

 

460-3

414

508

 

 

7.8

 

52.0

1/3

0.7

3/4

1.2

11.6

20

072*

208/230-1

187

254

 

 

N/A

 

N/A

N/A

N/A

N/A

N/A

N/A

N/A

208/230-3

187

254

2

 

N/A

 

N/A

N/A

N/A

N/A

N/A

N/A

N/A

 

460-3

414

508

 

 

N/A

 

N/A

N/A

N/A

N/A

N/A

N/A

N/A

096*

208/230-1

187

254

 

 

N/A

 

N/A

N/A

N/A

N/A

N/A

N/A

N/A

208/230-3

187

254

2

 

13.6

 

83.1

3/4

2.4

3

8.4

41.4

55

 

460-3

414

508

 

 

6.1

 

41.0

3/4

1.2

3

4.0

18.9

25

LEGEND

HACR — Heating, Air Conditioning, and Refrigeration

Hp — Horsepower

FLA — Full Load Amps

LRA — Locked Rotor Amps

MOCP — Maximum Overcurrent Protection (HACR breaker)

RLA — Rated Load Amps

*Unit has two compressors.

14

Page 14
Image 14