Table 1 — Physical Data (cont)

UNIT 50AH

060

 

 

072

 

 

096

OPERATING WEIGHT (lb)

 

 

 

 

 

 

 

Base Unit

960

 

 

1214

 

 

1283

Evaporator/Condenser Sections

421/519

 

 

554/634

 

 

556/701

SHIPPING WEIGHT (lb)*

1093

 

 

1647

 

 

1716

REFRIGERANT TYPE

 

 

 

R-410A

 

Operating Charge (lb-oz)†

8-8

 

 

6-6

 

 

6-6

 

 

COMPRESSOR — TYPE

 

 

 

Scroll

 

Quantity...Model

1...ZPKP51K5E

 

 

2...ZP31K5E

 

 

2...ZP38K5E

 

 

 

Oil (oz)

42

 

 

25

 

 

42

HPS Setting (psig)

 

 

 

 

 

 

 

Cutout

 

650 ± 7

 

 

 

Reset

 

 

 

Manual Reset

 

LPS Setting (psig)

 

 

 

 

 

 

 

Cutout

 

75 ± 7

 

 

 

Reset

 

100 ± 7

 

 

 

CONDENSATE DRAIN CONNECTION

 

 

 

 

 

 

 

Size (in.)...Type

 

 

 

7/8...OD

 

CONDENSER COIL

 

Copper Tubes — Aluminum Fins

 

Size (L x H) (in.)

90 x 30

 

 

40 x 30 (2 coils)

 

 

40 x 30 (2 coils)

 

 

 

Number of Rows...Fins/in.

2...12

 

 

2...20

 

 

2...20

CONDENSER FAN

 

 

 

Centrifugal — Belt Drive

 

Nominal Cfm

3000

 

 

5200

 

 

6400

 

 

Blower Size (in.)

15 x 15

 

 

18 x 18

 

 

18 x 18

Motor Hp (Rpm)

 

 

 

 

 

 

 

Standard Motor

0.33 (1725)

 

 

1.00 (1725)

 

 

1.50 (1725)

Upgrade 1 Motor

0.50 (1725)

 

 

1.50 (1725)

 

 

2.00 (1725)

Upgrade 2 Motor

0.75 (1725)

 

 

 

 

3.00 (1725)

EVAPORATOR COIL

 

Copper Tubes — Aluminum Fins

 

Size (L x H) (in.)

32 x 26

 

 

46 x 28

 

 

46 x 28

 

 

 

Number of Rows...Fins/in.

3...14

 

 

3...14

 

 

3...14

EVAPORATOR AIR FAN

 

 

 

Centrifugal — Belt Drive

 

Nominal Cfm

2000

 

 

2400

 

 

3200

 

 

Blower Size (in.)

12 x 9

 

 

15 x 15

 

 

15 x 15

Motor Hp (Rpm)

 

 

 

 

 

 

 

Standard Motor

0.33 (1725)

 

 

0.50 (1725)

 

 

0.75 (1725)

Upgrade 1 Motor

0.50 (1725)

 

 

0.75 (1725)

 

 

1.00 (1725)

Upgrade 2 Motor

0.75 (1725)

 

 

1.00 (1725)

 

 

1.50 (1725)

Upgrade 3 Motor

1.00 (1725)

 

 

1.50 (1725)

 

 

2.00 (1725)

INDOOR-AIR FILTERS

 

Factory-Supplied Disposable Type

 

Number...Size (in.)

2...18 x 24 x 1

 

 

2...20 x 25 x 1

 

 

2...20 x 25 x 1

 

 

 

INTERCONNECTING TUBING SIZE

 

 

 

 

 

 

 

Suction (Qty...in.)

1...7/8

 

 

1...5/8

 

 

1...7/8

 

 

Liquid (Qty...in.)

1...3/8

 

 

1...3/8

 

 

1...7/8

LEGEND

HPS — High-Pressure Switch

LPS — Low-Pressure Switch

*Shipping weights include base unit plus packaging.

†If components are to be split, additional refrigerant will be needed.

NOTE: If components are to be split, the maximum length of refrigerant tubing to be used is 50 equivalent ft, assuming components will be installed in same horizontal plane. If components are not to be installed in same horizontal plane, contact your Carrier representative for more information. For additional piping information, refer to Carrier System Design Manual, Part 3.

Step 4 — Rig and Place Unit — Move and store unit in horizontal position. Provide space around unit for service, filter access, ductwork, and overhead clearance as indicated in Fig. 2-5.

Using suitable hydraulic lift source, raise unit up to meet bottom of the 8 threaded rods suspended from ceiling (12 rods for units with air-side economizer). Center unit so that the 8 or 12 threaded rods can be easily inserted into the factory-drilled holes at each end. Refer to Fig. 6 for rigging details.

Apply washers and locknuts on ends of each of the 8 or 12 rods.

Tighten locknuts sufficiently so that unit weight is support- ed entirely by the 8 or 12 rods. Level unit within the space by adjusting locknuts.

IMPORTANT: Unit must be level to operate properly.

NOTE: For split systems, 8 (or 12) suspension rods are required (4 for each section and 4 for economizer if required). Refer to Splitting Systems section below.

Step 5 — Make Condensate Piping Connec- tions — One 7/8-in. OD pipe thread condensate drain con- nection is provided for the evaporator section.

Step 6 — Install Ductwork — Use flexible ductwork to attach duct to unit and to help control transmission of vibra- tions to building structures. Attach ductwork to the return and supply ends of both coils.

If unit is located with condenser close to outside of building, install a field-supplied rainhood. Hood intake dimensions should be same as condenser return-air dimensions. In addi- tion, install a triple-layer bird screen over rainhood intake to eliminate possibility of insects, birds, water, or debris from entering unit. Ensure hood and/or louvers are installed correct- ly to avoid condenser air recirculation.

Step 7 — Split Systems (Factory Option, if Required) — The Roomtop® 50AH units may be split into 2 sections, if desired, with condensing section mounted remotely horizontally. The unit must be ordered with the “Splittable” cabinet type as shown in the unit model number nomenclature. See Fig. 1. All splittable units come with the interconnecting tubing kit.

Sections installed in the same horizontal plane may be sepa- rated by up to 50 equivalent ft of tubing. Use type L copper or better.

8

Page 8
Image 8
Carrier 50AH024-096 specifications 060 072 096 Operating Weight lb Base Unit 960, Centrifugal Belt Drive Nominal Cfm

50AH024-096 specifications

The Carrier 50AH024-096 is a highly efficient and robust air conditioning unit designed to meet the cooling demands of both residential and commercial applications. This model stands out for its advanced technology and reliable performance, making it a preferred choice among HVAC professionals and end-users alike.

One of the main features of the Carrier 50AH024-096 is its high-efficiency compressor, which is designed to provide optimal cooling while minimizing energy consumption. With a variable speed operation, the compressor adjusts its output to the cooling needs of the space, ensuring maximum comfort and energy savings. This feature not only enhances the unit’s efficiency but also contributes to a quieter operation, as it can throttle down to a lower speed during less demanding conditions.

The Carrier 50AH024-096 also boasts an environmentally friendly refrigerant, which is crucial in today’s market where energy efficiency and eco-friendliness are at the forefront of consumer choices. By utilizing R-410A refrigerant, this unit helps reduce the impact on ozone depletion while providing effective cooling performance.

In terms of construction, the Carrier 50AH024-096 features a durable, corrosion-resistant cabinet that ensures longevity and durability. The design allows for easy access to internal components for maintenance and service, which is an essential aspect for HVAC professionals. Additionally, the unit is equipped with advanced filter systems that ensure the indoor air quality remains high by trapping dust, allergens, and other particulates.

One of the standout characteristics of the Carrier 50AH024-096 is its compatibility with smart thermostats and advanced control systems. This allows users to integrate their cooling system into a smart home ecosystem, enabling remote access and control via mobile devices. This feature not only enhances user convenience but also promotes energy management by allowing for adjustments based on occupancy and preferences.

Energy Star certified, the Carrier 50AH024-096 is designed to exceed minimum efficiency standards, ensuring that consumers not only receive a reliable product but also experience long-term savings on energy bills.

In conclusion, the Carrier 50AH024-096 represents a significant investment in comfort, efficiency, and durability. With its advanced features and technologies, it addresses the modern needs of cooling systems, making it an excellent choice for anyone looking to upgrade their HVAC system. Whether for residential or commercial use, this model delivers both performance and peace of mind.