Condensing section must be located in same plane as, or above, evaporator section to maintain the liquid refrigerant seal at the expansion device. This permits expansion device to feed liquid refrigerant to evaporator coil properly. To split sections (some of the following steps may be eliminated depending on particular application):
1.Disconnect all electrical power to unit.
2.Remove the 10 size 10 drive screws that hold on the top tie strap.
3.Remove the 8 size
4.Control panel access panels are held on with 2 size 10 drive screws for each panel. A standard
5.Units have resealable fittings. Do not cut refrigerant pip- ing. See Interconnecting Refrigerant Tubing section be- low for procedure on installing tubing.
6.Install evaporator and condensing sections in desired locations.
7.Use sufficient length of refrigerant piping to reconnect piping cut in previous step. Refer to Carrier System Design Manual, Part 3, for additional piping data.
8.Recharge unit with
After splitting sections, additional refrigerant must be added to system to ensure proper refrigerant charge. The amount of refrigerant to be added depends on length of tubing added to system and operating temperatures of system. Refer to Carrier System Design Manual, Chapter 3. Allow unit to operate at least 10 minutes before adjusting refrigerant charge.
Since standard roomtop unit has negligible line losses, split- ting the system can increase line loss and decrease system capacity. Capacity reduction can be determined by referring to Carrier System Design Manual.
INTERCONNECTING REFRIGERANT TUBING — The interconnecting tubing kit comes with all
COUPLING | COUPLING |
(MALE HALF) | (FEMALE HALF) |
SCREWS
FLANGEa50-8551
Fig. 7 — Self Sealing Coupling
For dual circuits, 2 kits are supplied. It is recommended that some refrigerant oil be placed on the coupling threads to facili- tate threading.
Perform the following procedure:
1.For condensing section, hand thread the female halves of the
2.For evaporator section, hand thread the male halves of the
3.Run the interconnecting tubing required.
NOTE: Installations may be made with up to 50 ft equiv- alent line lengths by installing the recommended tube siz- es and adding the necessary refrigerant. For equivalent line lengths greater than 50 ft, contact Carrier for line siz- ing and additional accesories required.
IMPORTANT: On units with more than one refrig- erant circuit, be careful not to intermix lines of the various circuits. If the connections were labeled before disconnecting the couplings, this should not be a problem. Half couplings may be removed to make brazing to the interconnecting tubing more convenient.
| D |
| D |
|
C | A | B | C | A |
EVAPORATOR |
|
| CONDENSING |
SECTION | D | D | SECTION |
C | A | B | C | A |
A — Male |
|
B — Refrigerant piping between sections |
|
C — Female |
|
D — Schrader fittings
Fig. 8 — Tubing Installation
CAUTION
When brazing tubing to the
4.The interconnect tubing kit contains a sufficient number of Schrader access valves to permit installation of one in each end of both the liquid and suction lines of the field- supplied tubing. Each interconnecting line (suction, liq- uid, hot gas) must have one of the supplied Schrader ac- cess fittings installed into the
9