![Fig. 2— 50GS018-042 and 50GX024-036 Unit Dimensions](/images/new-backgrounds/33713/337135x1.webp)
REQUIRED CLEARANCE TO COMBUSTIBLE MATL. | INCHES [mm] | REQUIRED CLEARANCE FOR OPERATION AND SERVICING | INCHES [mm] | |||||||||
|
|
|
|
|
|
|
| |||||
TOP OF UNIT |
| 14.00 [355.6] | EVAP. COIL ACCESS SIDE | ............................................................ |
| 36.00 [914.0] | ||||||
DUCT SIDE OF UNIT | 2.00 [50.8] | POWER ENTRY SIDE |
| 42.00 [1066.8] | ||||||||
SIDE OPPOSITE DUCTS | 14.00 [355.6] | (EXCEPT FOR NEC REQUIREMENTS) |
|
|
| |||||||
BOTTOM OF UNIT | 0.50 [12.7] | UNIT TOP |
| 48.00 [1219.2] | ||||||||
ELECTRIC HEAT PANEL | 36.00 [914.4] | SIDE OPPOSITE DUCTS |
| 36.00 [914.0] | ||||||||
NEC. REQUIRED CLEARANCES. |
|
| DUCT PANEL |
| 12.00 [304.8] * | |||||||
INCHES [mm] | *MINIMUM DISTANCES: IF UNIT IS PLACED LESS THAN 304.8 [12.00] FROM | |||||||||||
|
| |||||||||||
BETWEEN UNITS, POWER ENTRY SIDE | 42.00 [1066.8] |
| WALL SYSTEM, THEN SYSTEM PERFORMANCE MAYBE COMPROMISE. | |||||||||
UNIT AND UNGROUNDED SURFACES, POWER ENTRY SIDE .36.00 [914.0] |
|
|
|
|
|
|
|
| ||||
UNIT AND BLOCK OR CONCRETE WALLS AND OTHER |
|
|
|
|
|
|
|
|
|
| ||
GROUNDED SURFACES, POWER ENTRY SIDE | 42.00 [1066.8] |
|
|
|
|
|
|
|
| |||
|
|
|
|
|
|
|
|
|
|
| C99007 | |
|
|
|
|
|
|
|
|
|
|
| ||
|
| UNIT WEIGHT |
| UNIT HEIGHT |
| CENTER OF GRAVITY | ||||||
UNIT | ELECTRICAL CHARACTERISTICS |
| IN. (MM) |
|
| IN. (MM) |
|
| ||||
|
|
|
|
|
|
|
| |||||
|
| lb. |
| kg |
| ”A” |
| X | Y |
| Z | |
50GS018 | 254 |
| 115.2 |
| 35.02 (889.5) |
| 20.0 (508.0) | 13.0 (330.2) |
| 15.0 (381.0) | ||
50GS024 | 260 |
| 117.9 |
| 35.02 (889.5) |
| 19.0 (482.6) | 13.0 (330.2) |
| 15.0 (381.0) | ||
50GS030 | 258 |
| 117.0 |
| 35.02 (889.5) |
| 19.0 (482.6) | 14.0 (355.6) |
| 15.0 (381.0) | ||
50GS036 | 268 |
| 121.6 |
| 37.02 (940.3) |
| 20.0 (508.0) | 14.0 (355.6) |
| 13.0 (330.2) | ||
50GS042 | 294 |
| 133.3 |
| 35.02 (889.5) |
| 19.0 (482.6) | 14.0 (355.6) |
| 13.0 (330.2) | ||
50GX024 | 270 |
| 122.5 |
| 37.02 (940.3) |
| 18.5 (469.9) | 14.5 (368.3) |
| 16.0 (406.4) | ||
50GX030 | 291 |
| 132.0 |
| 39.02 (991.1) |
| 19.5 (495.3) | 15.5 (393.7) |
| 17.6 (447.0) | ||
50GX036 | 299 |
| 135.6 |
| 35.02 (889.5) |
| 19.5 (495.3) | 15.25 (387.4) |
| 16.5 (419.1) |
Fig. 2— 50GS018-042 and 50GX024-036 Unit Dimensions
Accessory lifting kit is only to be used with Small Packaged units which have a composite base pan with molded rigging holds.
of wear, structural deformation, or cracks. Particular attention should be paid to excessive wear at hoist hooking points and load support areas. Brackets or straps showing any kind of wear in these areas must not be used and should be discarded.
INSTALLATION
INSPECTION
Prior to initial use, and at monthly intervals, all rigging brackets and straps should be visually inspected for any damage, evidence
1.Position the lifting bracket assembly around the base of the unit. Leave the top shipping skid on the unit to act as a spreader bar. Be sure the strap does not twist.