Carrier 50GS, 50GX Troubleshooting-Cooling, Symptom, Cause, Remedy, Compressor cycles

Models: 50GX 50GS

1 28
Download 28 pages 50.3 Kb
Page 26
Image 26

Table 10—Troubleshooting—Cooling

SYMPTOM

CAUSE

REMEDY

 

Power Failure

Call power company

 

Fuse blown or circuit breaker tripped

Replace fuse or reset circuit breaker

 

 

 

 

Defective thermostat, contractor, transformer, or

Replace component

 

control relay

Compressor and condenser fan will not start.

 

Insufficient line voltage

Determine cause and correct

 

 

Incorrect or faulty wiring

Check wiring diagram and rewire correctly

 

Thermostat setting too high

Lower thermostat setting below

 

room temperature

 

 

 

Faulty wiring or loose connections in compressor

Check wiring and repair or replace

 

circuit

 

 

Compressor will not start but condenser fan

Compressor motor burned out, seized, or internal

Determine cause

overload open

Replace compressor

runs.

Defective run/start capacitor, overload, start relay

Determine cause and replace

 

 

One leg of 3-phase power dead

Replace fuse or reset circuit breaker

 

Determine cause

 

 

Three-phase scroll compressor (50GS048,

Scroll compressor is rotating

Correct the direction of rotation by reversing the

50GX030-060) makes excessive noise, and

3-phase power leads to the unit. Shut down unit

in the wrong direction

there may be a low pressure differential.

to allow pressures to equalize.

 

 

Refrigerant overcharge or undercharge

Recover refrigerant, evacuate system, and re-

 

charge to capacities shown on nameplate

 

 

 

Defective compressor

Replace and determine cause

 

Insufficient line voltage

Determine cause and correct

 

 

 

Compressor cycles

Blocked condenser

Determine cause and correct

(other than normally satisfying thermostat).

Defective run/start capacitor, overload or start

Determine cause and replace

 

relay

 

 

 

Defective thermostat

Replace thermostat

 

Faulty condenser-fan motor or capacitor

Replace

 

Restriction in refrigerant system

Locate restriction and remove

 

 

 

 

Dirty air filter

Replace filter

 

Unit undersized for load

Decrease load or increase unit size

 

Thermostat set too low

Reset thermostat

 

 

 

Compressor operates continuously.

Low refrigerant charge

Locate leak, repair, and recharge

 

 

Leaking valves in compressor

Replace compressor

 

 

Air in system

Recover refrigerant, evacuate system, and re-

 

charge

 

 

 

Condenser coil dirty or restricted

Clean coil or remove restriction

 

Dirty air filter

Replace filter

 

 

 

 

Dirty condenser coil

Clean coil

Excessive head pressure.

Refrigerant overcharged

Recover excess refrigerant

Air in system

Recover refrigerant, evacuate system, and re-

 

 

charge

 

 

 

Condenser air restricted or air short-cycling

Determine cause and correct

 

 

 

 

Low refrigerant charge

Check for leaks, repair and recharge

 

 

 

Head pressure too low.

Compressor valves leaking

Replace compressor

 

Restriction in liquid tube

Remove restriction

 

High heat load

Check for source and eliminate

 

 

 

Excessive suction pressure.

Compressor valves leaking

Replace compressor

 

Refrigerant overcharged

Recover excess refrigerant

 

Dirty air filter

Replace Filter

 

 

 

 

Low refrigerant charge

Check for leaks, repair, and recharge

 

Metering device or low side restricted

Remove source of restriction

Suction pressure too low.

Insufficient evaporator airflow

Increase air quantity

Check filter- replace if necessary

 

 

 

Temperature too low in conditioned area

Reset thermostat

 

 

 

 

Outdoor ambient below 40°F

Install low-ambient kit

 

 

 

 

Field-installed filter-drier restricted

Replace

26

Page 26
Image 26
Carrier 50GX Troubleshooting-Cooling, Symptom, Cause, Remedy, Three-phasescroll compressor 50GS048, Compressor cycles