1” (25mm) MIN.
TRAP OUTLET
2” (50mm) MIN.
C99013
Fig. 7—Condensate Trap
Table 3—Minimum Airflow for Safe Electric Heater
Operation (Cfm)
SIZE
018 | 024 | 030 | 036 | 042 | 048 | 060 |
700 | 800 | 1000 | 1200 | 1400 | 1600 | 2000 |
5.It is recommended that the unit base insulation around the perimeter of the vertical
6.Cover both horizontal duct openings with the duct covers from the accessory duct cover kit. Ensure opening is
7.After completing unit conversion, perform all safety checks and power up unit.
NOTE: The design and installation of the duct system must be in accordance with the standards of the NFPA for installation of
Adhere to the following criteria when selecting, sizing, and installing the duct system:
8.Units are shipped for side shot installation.
9.Select and size ductwork,
10.Use flexible transition between rigid ductwork and unit to prevent transmission of vibration. The transition may be screwed or bolted to duct flanges. Use suitable gaskets to ensure weathertight and airtight seal.
11.All units must have
12.Size all ductwork for maximum required airflow (either heating or cooling) for unit being installed. Avoid abrupt duct size increases or decreases or performance may be affected.
13.Adequately insulate and weatherproof all ductwork located outdoors. Insulate ducts passing through unconditioned space, and use vapor barrier in accordance with latest issue of Sheet Metal and Air Conditioning Contractors National Association (SMACNA) and Air Conditioning Contractors of America (ACCA) minimum installation standards for heating and air conditioning systems. Secure all ducts to building structure.
14.Flash, weatherproof, and
SUPPLY | RETURN |
DUCT | DUCT |
OPENING | OPENING |
C99011
Fig. 8—Supply and Return Duct Opening
Step 8—Install Electrical Connection
The unit cabinet must have an uninterrupted, unbroken electrical ground to minimize the possibility of personal injury if an electrical fault should occur. This ground may consist of an electrical wire connected to the unit ground lug in the control compartment, or conduit approved for electrical ground when installed in accordance with NEC (National Electrical Code) ANSI/NFPA (latest edition) and local elec- trical codes. In Canada, follow Canadian Electrical Code CSA (Canadian Standards Association) C22.1 and local electrical codes. Failure to adhere to this warning could result in personal injury or death.
9