REQUIRED CLEARANCE TO COMBUSTIBLE MATL.
| INCHES [mm] | |
TOP OF UNIT | 14.00 | [355.6] |
DUCT SIDE OF UNIT | 2.00 | [50.8] |
SIDE OPPOSITE DUCTS | 14.00 | [355.6] |
BOTTOM OF UNIT | 0.50 | [12.7] |
ELECTRIC HEAT PANEL | 36.00 | [914.4] |
REQUIRED CLEARANCE FOR OPERATION AND SERVICING
| INCHES [mm] |
| |
EVAP. COIL ACCESS SIDE | 36.00 | [914.0] |
|
POWER ENTRY SIDE | 36.00 | [914.0] |
|
(EXCEPT FOR NEC REQUIREMENTS) |
|
|
|
UNIT TOP | 48.00 | [1219.2] |
|
SIDE OPPOSITE DUCTS | 36.00 | [914.0] |
|
DUCT PANEL | 12.00 | [304.8] | * |
NEC. REQUIRED CLEARANCES.
| INCHES | [mm] |
BETWEEN UNITS, POWER ENTRY SIDE | 42.00 | [1066.8] |
UNIT AND UNGROUNDED SURFACES, POWER ENTRY SIDE .36.00 | [914.0] | |
UNIT AND BLOCK OR CONCRETE WALLS AND OTHER |
|
|
GROUNDED SURFACES, POWER ENTRY SIDE | 42.00 | [1066.8] |
*MINIMUM DISTANCES: IF UNIT IS PLACED LESS THAN 304.8 [12.00] FROM WALL SYSTEM, THEN SYSTEM PERFORMANCE MAYBE COMPROMISE.
C99006
|
| UNIT WEIGHT | UNIT HEIGHT | CENTER OF GRAVITY | |||
UNIT | ELECTRICAL CHARACTERISTICS | IN. (MM) |
| IN. (MM) |
| ||
|
|
|
| ||||
|
| lb. | kg | ”A” | X | Y | Z |
50GS048 | 324 | 145 | 38.98 (990.2) | 20.0 (508.0) | 17.0 (432.0) | 17.0 (432.0) | |
50GS060 | 389 | 176 | 38.98 (990.2) | 19.0 (482.6) | 16.0 (406.0) | 17.0 (432.0) | |
50GX042 | 321 | 146 | 38.98 (990.2) | 20.5 (520.7) | 16.75 (425.5) | 16.6 (421.6) | |
50GX048 | 326 | 148 | 38.98 (990.2) | 19.5 (495.3) | 17.6 (447.6) | 18.0 (457.2) | |
50GX060 | 399 | 181 | 42.98 (1091.1) | 20.5 (520.7) | 16.2 (412.8) | 17.6 (447.0) | |
|
|
|
|
|
|
|
|
Fig. 3— 50GS048–060 and 50GX042–060 Unit Dimensions
2.Place each of the four (4) metal lifting brackets into the rigging holds in the composite pan.
3.Tighten the ratchet strap unit tight. Lifting brackets should be secure in the rigging holds.
4.Attach the clevis or hook of sufficient strength to hole in the lifting bracket (See Fig. 6).
5.Attach safety straps directly to the field supplied rigging straps or clevis clip. Do not attach the safety straps to the lifting brackets.
6.Use the top of the unit as a spreader bar to prevent the rigging straps from damaging the unit. If the wood top is not available, use a spreader bar of sufficient length to not damage the unit.
4